Plan Review Notes
Plan Review Notes For Permit 15040099
Permit Number 15040099
Review Stop G
Sequence Number 2
Notes
Date Text
2015-04-07 08:03:05***NOTE*** - THIS REVIEW SUPERCEDES REVIEW # 1 AS THAT
 REVIEW STOP IS LOCKED AND THE REVIEW COULD NOT BE
 COMPLETED. T.LARGE.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED
 PER THE 2010 FBCR SEC. G2404.3. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 2) SUBMIT A GAS RISER DIAGRAM FOR REVIEW. CLEARLY SHOW
 ALL CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS, THE
 PIPE SIZE, THE GAS PSI, THE TYPE OF PIPE MATERIAL, AND
 THE SIZE & CORRESPONDING EHD NUMBER OF CORRUGATED
 STAINLESS STEEL TUBING (CSST).2010 WPB AMEND. TO 2010
 FBC SEC. 107.3.5.3.
 3) INDICATE THE TYPE OF GAS .WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 4) SHOW THE BTU LOAD OF THE APPLIANCES ON THE GAS
 RISER.2010 WPB AMEND. TO 2010 FBC SEC. 107.3.5.3.
 5) SHOW THE TOTAL DISTANCE FROM THE POINT OF DELIVERY
 (METER) TO THE MOST REMOTE GAS OUTLET. 2010 FBCR
 SEC.G2413.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  