Plan Review Notes
Plan Review Notes For Permit 15040099
Permit Number 15040099
Review Stop G
Sequence Number 1
Notes
Date Text
2015-04-07 06:56:351) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED
 PER THE 2010 FBCR SEC. G2404.3. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 2) SUBMIT A GAS RISER DIAGRAM FOR REVIEW. CLEARLY SHOW
 ALL CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS, THE
 PIPE SIZE, THE TYPE OF PIPE MATERIAL,AND THE SIZE &
 CORRESPONDING EHD NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING (CSST).
 3) INDICATE THE TYPE OF GAS .
 4) SHOW THE BTU LOAD OF THE APPLIANCE ON THE GAS RISER.