2015-04-07 12:32:531) SUBMIT MANUF. SPECIFICATIONS FOR THE PUMP/BASIN
 UNIT. WPB AMEND. TO FBC 107.2.1.
 2) THE SANITARY RISER DIAGRAM ON SHT. M2.1 SHOWS A 1
 1/2" DISCHARGE AND THE PLUMBING PLAN SHOWS A 2"
 DISCHARGE. CLARIFY.
 3) A FULL OPEN VALVE SHALL BE LOCATED ON THE DISCHARGE
 SIDE OF THE CHECK VALVE PER SEC. 712.2 OF 2010 FPC.
 4) THE CONNECTION OF THE EJECTOR TO THE BUILDING
 DRAIN/BUILDING SEWER PER 2010 FPC SEC.712.3.5 AND SHALL
 CONNECT A MINIMUM OF 10 FEET FROM THE BASE OF ANY SOIL
 OR WASTE STACK.
 5) THE PUMP SHALL HAVE THE MINIMUM CAPACITY AS
 SPECIFIED IN 2010 FPC SEC.712.4.2 AND TABLE 712.4.2.
  