2015-05-07 16:08:08THE FOLLOWING ITEMS NEED ATTEN/CORRECTION FOR A
 SUCCESSFUL REVIEW:
 PG. E1.1
 1. EVEN IF AS EXISTING, THE LIFE SAFETY ILLUMINATION
 SHALL BE SHOWN ON THE PLANS TO VERIFY COMPLIANCE
 2, OFFICE RM 409 IS MISSING AN EXIT SIGN ABOVE THE DOOR
 AS WELL AS EMERGENCY LIGHTING INSIDE THE ROOM. AS PER
 NEC700.16, THERE CANT BE A ROOM LEFT IN TOTAL DARKNESS
 IN THE EVEN OF A POWER FAILURE.
 PG. E1.2
 1. ACCORDING TO THE NOTES, THE AREA ABOVE THE CEILING
 IS ALL A PLENUM, MAKE CERTAIN THAT THE NEW TRANSFORMER
 INDICATED ABOVE THE CEILING IT THE IT ROOM IS LISTED
 FOR A PLENUM.
 PG. E2.1
 1. VENDING MACHINES AND/OR THEIR CIRCUIT SHALL COMPLY
 WITH NEC422..51
 2. NEW PANEL "LC" AS WELL AS ALL EXISTING, SHALL BEAR
 THE REQUIRED FLASH PROTECTION DECAL AS INDICATED IN
 NEC110.16
 3. THE RISER DIAGRAM IS NOT COMPLETE. THE RISER DIAGRAM
 SHALL INCLUDE IN ADDITION TO ALL THE EXISTING LOADS,
 THE STANDBY GENERATOR AS WELL.