Date |
Text |
2015-04-13 13:25:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| THE PROPOSED OCCUPANCY IS NOT INDICATED. |
| |
| PROVIDE AN EQUIPMENT AND SHELVING ( IF APPROPRIATE) |
| PLAN, AND/OR PROPOSED FLOOR LAYOUT PLAN SHOWING THE |
| INTERIOR OF THE OCCUPANCY. |
| |
| COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL BE |
| PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| SAFETY FEATURES AND EQUIPMENT. |
| |
| NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE. ANY |
| AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH |
| CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE AND |
| PRE-APPROVED (PRIOR TO INSTALLATION) BY THE BUREAU OF |
| FIRE PREVENTION. |
| |
| PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING |
| MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT |
| MORE THAN ONE RELEASING OPERATION. THE RELEASING |
| MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION |
| THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. |
| THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING |
| OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT |
| GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO |
| OPERATE. |
| |
| A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY |
| DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS |
| PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH |
| LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE |
| DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO |
| OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED. |
| |