Plan Review Notes
Plan Review Notes For Permit 15040016
Permit Number 15040016
Review Stop B
Sequence Number 1
Notes
Date Text
2015-04-06 08:05:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040016
 ADD: 701 N. ROSEMARY AVE.
 CONT: ADVANCED CONSTRUCTION
 TEL: (561)262-6037
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1ST REVIEW
 DATE: MON. APRIL 06/2015
 ACTION: DENIED
  
 1) SHEET AD103 NEEDS TO SHOW AN ACCESSIBLE ENTRANCE TO
 THE BUILDING FROM THE ACCESSIBILE PARKING SPACE AND
 ACCESS AISLE. ICE MACHINE BLOCKS THE SIDEWALK AND
 SEE THE REQUIRED WIDTH OF SIDEWALK AND TURNING FOR
 ENTRY AT DOOR.
  
 2010 FL ACCESSIBILITY CODE 206.2.1 SITE ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 SEE ACCESS. CODE FIGURE 404.2.4.1 (HOR I) DEPENDING ON
 IF THERE IS A DOOR CLOSER.
  
 2) SHEET AD103 WILL NEED TO SHOW THE W. P. B. CITY
 STANDARD OF DOUBLE STRIPING SEE W.P. B. MUNI CODE
 SECTION 94-485.
  
 3) SHEET AD201 INDICATES WHERE THE NEW ADDITION IS TO
 THE EXISTING BUILDING TO FLUSH UO THE NEW PAVEMENT TO
 THE EXISTING SIDE WALK. THIS SHEET NOR AD103 SHOW THE
 PROPOSED GRADES NOR THE TRANSITION OF GRADE ELEVATION
 AT THE EXISTING SIDEWALK VERSES THE PAVEMENT. 2010 FL
 ACCESS. CODE 502.4. 502.4 FLOOR OR GROUND SURFACES.
 PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN
 LEVEL ARE NOT PERMITTED.
 EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE
 PERMITTED.
  
 4) PLANS DO NOT INDICATE COMPLIANCE WITH 2010 FL
 ACCESS. CODE 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 5) THE PLANS INDICATE NEW WINDOWS AND DOORS, THERE IS
 NO WIND DESIGN CRITERIA:
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 6A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6B) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. DOORS ARE NOT IDENTIFIED.
 CIRCLE WIDTH, LENGHT, GLAZING TYPE, FASTENERS AND
 ASSOCIATED PRESSURES.
 (B) WINDOWS. CIRCLE WIDTH, LENGHT, GLAZING TYPE,
 FASTENERS AND ASSOCIATED PRESSURES.
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, CIRCLE WIDTH, LENGHT, GLAZING
 TYPE, FASTENERS AND ASSOCIATED PRESSURES.
 (D) ROOFING PRODUCTS AND ASSEMBLIES NO PRODUCT
 APPROVALS WERE SUBMITTED.
  
 6C) SHEET AD201 INDICATES THE WINDOWS TO BE SLIDERS
 WHERE AS THE PRODUCT APPROVAL SUBMITTED WAS FOR
 ALUMINUM STOREFRONT SYSTEM.
  
 6D) SHEET AD201 ALSO INDICATES A NEW MOTORIZED SECURITY
 SHUTTER.
  
 7) SHEET AD201 SHOWS A ROOF CURB AND WHAT APPEARS TO BE
 INSULATED ROOF WITH PITCH TO A ROOF SCUPPER, NOTE THERE
 IS NO CALCULATION FOR RAIN/ ROOF AREA NOR STHE MINIMUM
 SIZE OF SCUPPER.
 7A) FBC-B P] 1503.4 ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES,
 DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL
 COMPLY WITH SECTION 1503 AND THE FLORIDA BUILDING CODE,
 PLUMBING, CHAPTER 11.
  
 7B) 1503.4.2 SCUPPERS. WHERE REQUIRED FOR ROOF
 DRAINAGE, A SCUPPER SHALL BE PLACED LEVEL WITH THE ROOF
 SURFACE IN A WALL OR PARAPET. THE SCUPPER SHALL BE
 LOCATED AS DETERMINED BY THE SLOPE AND THE CONTRIBUTING
 AREA OF THE ROOF. THE EXTERIOR FACING OR LINING OF A
 SCUPPER, IF METAL, SHALL BE THE SAME AS FLASHING
 MATERIAL REQUIRED BY SECTIONS 1503 THROUGH 1510 FOR THE
 PARTICULAR TYPE OF COVERING SPECIFIED FOR THE BUILDING.
 FOR OTHER TYPE MATERIALS, FOLLOW MANUFACTURER?S
 SPECIFICATIONS.
  
 7C) 1503.4.1 SECONDARY DRAINAGE REQUIRED.
 SECONDARY (EMERGENCY) ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON.
  
 7D) 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 7E) 1503.7 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 8)SHEET AS201 SHOW DETAIL 2 OOF FRAMING FOR THE
 SIDEWALL & NEW ROOF. THIS DETAIL FAILS TO PROVIDE THE
 CONNECTION TO THE EXISTING ROOF FRAMING, DOES THE
 EXISTING LAST FRAMING MEMBER GET DOUBLED? DOES THIS
 FRAMING MEMBER REQUIRE ADDITIONAL STAPPING FOR THE
 ADDITIONAL UPLIFT OF A LARGER TRIBUTARY AREA AND BEING
 PART OF THE MWFRS?
  
 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  