2015-05-01 06:14:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15031368
 ADD: 625 N. FLAGLER DR. # 700
 CONT: CHANDLIER CONSTRUCTION
 TEL: ( 561-791-6934
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:FRI. MAY 01/ 2015
 ACTION: DENIED
  
 NOTICE PLANS WILL NOT BE APPROVED WITH VOIDED SHEETS
 INSERTED INTO THE PLANS. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
 1) 2ND REQUEST. THE COVERSHEET A-0.1 LIST THIS PROJECT
 AS A BUSINESS OCCUPANCY, THAT IT IS NOT A MIXED USE
 OCCUPANCY. THE SHEET DOES NOT HAVE THE OCCUPANCY
 SEPARATION CHECKED OR THE EXCEPTIONC CHECKED EITHER.
 SHEET A-2.1 SHOWS THE TENANTCY AS A SINGLE TENANT FULL
 FLOOR BUILD-OUT. THE FLOOR PLATE APPROXIMATELY 12,992
 SQ. FT. OF BUSINESS OCCUPANCY. THE ROOMS NUMBERS
 IDENTIFIED AS 704,708,710 & 720 ARE ALL CONSIDERED A
 ASSEMBLY USAGE NOT BUSINESS. WHEN THE SQUARE FOOT AREAS
 ARE TOTALED TOGETHER(1,927 SQ. FT.) THEY ARE OVER THE
 10 % OF THE FLOOR PLATE AND THE FLOOR PLATE BECOMES A
 MIXED USE OCCUAPANCY.
  
 2010 FBC-B 508.2.1 AREA LIMITATIONS. AGGREGATE
 ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10
 PERCENT OF THE BUILDING AREA OF THE STORY IN WHICH THEY
 ARE LOCATED AND SHALL NOT EXCEED THE TABULAR VALUES IN
 TABLE 503, WITHOUT BUILDING AREA INCREASES IN
 ACCORDANCE WITH SECTION 506 FOR SUCH ACCESSORY
 OCCUPANCIES.
  
 THE DESIGNER OF RECORD WILL NEED TO INDICATE THE DESIGN
 REQUIREMENTS AS EITHER COMPLYING WITH:
 FBC-B 508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR
 PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS
 OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED
 OCCUPANCIES.
 OR
 FBC-B 508.4 SEPARATED OCCUPANCIES. BUILDINGS OR
 PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS
 OF THIS SECTION SHALL BE CONSIDERED AS SEPARATED
 OCCUPANCIES.
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 BUILDING OFFICIALS ASSOCIATION OF FLORIDA INFORMAL
 INTERPRETATION REPORT NUMBER 6506
 DATE: THU JUN 3 2010
 REPORT: 6506
 CODE: BUILDING CODE YEAR: 2007
 SECTION: 508.3.1
 QUESTION:
 IS IT THE INTENT OF FLORIDA BUILDING CODE - BUILDING
 SECTION 508.3.1, EXCEPTION 1, TO NOT REQUIRE FIRE
 SEPARATION BETWEEN THE
 PRIMARY OCCUPANCY AND MULTIPLE ACCESSORY OCCUPANCIES,
 WHEN EACH ACCESSORY OCCUPANCY IS LESS THAN 750 SQ. FEET
 EACH OR
 ONLY WHEN THE TOTAL OF ALL ACCESSORY OCCUPANCIES IS
 LESS THAN 750 SQ. FEET IN AREA?
 COMMENT:
 AN EXAMPLE WOULD BE A BUSINESS OCCUPANCY WITH ONE
 ACCESSORY AREA OF 700SF FOR GATHERINGS AND MEETINGS AND
 A SECOND
 ACCESSORY AREA OF 650SF FOR FITNESS AND WORKOUT. IS THE
 EXCEPTION LIMITATION OF 750 S.F. MAX APPLIED TO EACH
 ACCESSORY AREA, IN
 WHICH CASE THIS BUILDING WOULD COMPLY, OR TO THE
 COMBINED TOTAL OF THE TWO ACCESSORY AREAS, IN WHICH
 CASE IT WOULD NOT?
 ANSWER:
 NO. CONSIDERING BOTH SPACES TO BE ASSEMBLY USES LOCATED
 ON THE SAME FLOOR, THE EXCEPTION TO FLORIDA BUILDING
 CODE - BUILDING
 SECTION 508.3.1 WOULD NOT REQUIRE SEPARATION OF EITHER
 SPACE. HOWEVER, THE SECTION TO WHICH THE EXCEPTION
 RELATES WOULD LIMIT
 THE AGGREGATE ACCESSORY OCCUPANCIES TO 10% OF THE AREA
 OF THE FLOOR ON WHICH THEY ARE LOCATED. IF THE AREA OF
 TWO COMBINED
 ASSEMBLY USES EXCEEDED 10%, THEN AT LEAST ONE OF THE
 ASSEMBLY USES WOULD REQUIRE FIRE RESISTANT RATED
 SEPARATION OF 2 HOURS IN
 A NON-SPRINKLED BUILDING AND 1 HOUR IN A BUILDING
 SPRINKLED THROUGHOUT.
 COMMENTARY:
 NONE.
 NOTICE:
 THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN
 COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC,
 AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS
 INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE
 INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE.
 THIS INTERPRETATION IS INFORMAL, NON-BINDING AND
 SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL
 BUILDING OFFICIAL.
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 ---------------------------------------------
  
 2) COMPLIED. SHEET A2.2 SHOWS THE INSTALATION OF MARBLE
 AND TILE FLOORING. THE PLANS DO NOT INDICATE IF THERE
 IS A INTENT TO INSTALL A CRACK ISOLATION MEMBRANE
 BEFORE THE INSTALATION OF EITHER MARBLE OR TILE. IF SO
 THE CRACK ISOLATION MEMBRANE INSULATION WILL NEED TO
 COMPLY WITH FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200. PLEASE PROVIDE TESTING REPORTS IN COMPLIANCE WITH
 SECTION 2010 FBC-B 603.1.2 EXCEPTION # 2, FLAMESPREAD.
  
 3) 2ND REQUEST. SHEET A-2-1 THE CONFERENCE ROOM # 720,
 1927 SQ. FT./ 15= 46 OCCUPANTS. SHEET A-3.1 THE DOOR
 SCHEDULE LIST THIS DOOR IDENTIED AS DOOR D4 AND A
 ALTERNATE SLIDING DOOR DESIGN. THE 2010 FBC-B 1008.1.2
 DOES NOT ALLOW FOR SLIDDING DOORS AS A PART OF A MEANS
 OF EGRESS WHEN THE OCCUPANT LOAD IS GREATER THAN 10.
  
 THE USE OF THE WORDS ALTERNATE AND OR CAN NOT BE USED,
 INFORMATION ON PLANS HAS TO BE SPECIFIC TO THE
 TECHNICAL CODES. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 4-5) COMPLIED>
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  