2015-04-03 15:54:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE PROVIDE A NOTE INDICATING THE BELOW INFORMATION: |
| |
| 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF |
| THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE |
| INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND |
| ALL OTHER APPLICABLE CODES OR STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2009 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2010 EDITION. |
| |
| 2) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF |
| THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE |
| AND COMPLIANCE. |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| |
| 3) BARRIERS FORMING THE ELVATOR LOBBY SHALL HAVE A |
| MINIMUM FIRE PROTECTION RATING OF 1 HOUR. THE PROPOSED |
| ELEVATOR LOBBY/MAIN ENTRANCE DOOR, D 1, IS NOT |
| INDICATED AS HAVING ANY FIRE PROTECTION RATING AND IS |
| NOT APPROVED. |
| |
| 4) COMPLETE LIFE SAFETY PLANS SHALL BE PROVIDED THAT |
| ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON |
| PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, |
| EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE |
| EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES |
| AND EQUIPMENT. |
| |