2015-04-02 13:02:04 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15031368 |
| ADD: 625 N. FLAGLER DR. # 700 |
| CONT: CHANDLIER CONSTRUCTION |
| TEL: ( 561-791-6934 |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE:THURS. APRIL 02/ 2015 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET A-0.1 LIST THIS PROJECT AS A BUSINESS |
| OCCUPANCY, THAT IT IS NOT A MIXED USE OCCUPANCY. THE |
| SHEET DOES NOT HAVE THE OCCUPANCY SEPARATION CHECKED OR |
| THE EXCEPTIONC CHECKED EITHER. SHEET A-2.1 SHOWS THE |
| TENANTCY AS A SINGLE TENANT FULL FLOOR BUILD-OUT. THE |
| FLOOR PLATE APPROXIMATELY 12,992 SQ. FT. OF BUSINESS |
| OCCUPANCY. THE ROOMS NUMBERS IDENTIFIED AS 704,708,710 |
| & 720 ARE ALL CONSIDERED A ASSEMBLY USAGE NOT BUSINESS. |
| WHEN THE SQUARE FOOT AREAS ARE TOTALED TOGETHER(1,927 |
| SQ. FT.) THEY ARE OVER THE 10 % OF THE FLOOR PLATE AND |
| THE FLOOR PLATE BECOMES A MIXED USE OCCUAPANCY. |
| |
| 2010 FBC-B 08.2.1 AREA LIMITATIONS. AGGREGATE ACCESSORY |
| OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 PERCENT OF |
| THE BUILDING AREA OF THE STORY IN WHICH THEY ARE |
| LOCATED AND SHALL NOT EXCEED THE TABULAR VALUES IN |
| TABLE 503, WITHOUT BUILDING AREA INCREASES IN |
| ACCORDANCE WITH SECTION 506 FOR SUCH ACCESSORY |
| OCCUPANCIES. |
| |
| THE DESIGNER OF RECORD WILL NEED TO INDICATE THE DESIGN |
| REQUIREMENTS AS EITHER COMPLYING WITH: |
| FBC-B 508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR |
| PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS |
| OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED |
| OCCUPANCIES. |
| OR |
| FBC-B 508.4 SEPARATED OCCUPANCIES. BUILDINGS OR |
| PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS |
| OF THIS SECTION SHALL BE CONSIDERED AS SEPARATED |
| OCCUPANCIES. |
| |
| 2) SHEET A2.2 SHOWS THE INSTALATION OF MARBLE AND TILE |
| FLOORING. THE PLANS DO NOT INDICATE IF THERE IS A |
| INTENT TO INSTALL A CRACK ISOLATION MEMBRANE BEFORE THE |
| INSTALATION OF EITHER MARBLE OR TILE. IF SO THE CRACK |
| ISOLATION MEMBRANE INSULATION WILL NEED TO COMPLY WITH |
| FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| 3) SHEET A-2-1 THE CONFERENCE ROOM # 720, 1927 SQ. FT./ |
| 15= 46 OCCUPANTS. SHEET A-3.1 THE DOOR SCHEDULE LIST |
| THIS DOOR IDENTIED AS DOOR D4 AND A ALTERNATE SLIDING |
| DOOR DESIGN. THE 2010 FBC-B 1008.1.2 DOES NOT ALLOW FOR |
| SLIDDING DOORS AS A PART OF A MEANS OF EGRESS WHEN THE |
| OCCUPANT LOAD IS GREATER THAN 10. |
| |
| 4) SHEET A-3.2 DETAIL # 05 SHOWS A ACCESSIBLE BREAK |
| ROOM COUNTERAND SINK, THE PLANS DO NOT INDICATE |
| COMPLIANCE WITH : 2010 FBC-ACCESSIBILITY CODE 606.3. |
| HEIGHT. |
| |
| 5) SHEET A-4.1 DETAIL # 1 THE WOMENS RESTROOM THE NEW |
| ACCESSIBLE TOLIET COMPARTMENT IS ONLY 7'-0" THIS WILL |
| NOTE MEET THE REQUIREMENTS OF ACCESSIBILITY CODE |
| 604.3.2. OVERLAP AND SIZE OF CLEARANCE AT WATER CLOSET. |
| |
| |