Plan Review Notes
Plan Review Notes For Permit 15031368
Permit Number 15031368
Review Stop B
Sequence Number 1
Notes
Date Text
2015-04-02 13:02:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15031368
 ADD: 625 N. FLAGLER DR. # 700
 CONT: CHANDLIER CONSTRUCTION
 TEL: ( 561-791-6934
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:THURS. APRIL 02/ 2015
 ACTION: DENIED
  
 1) THE COVERSHEET A-0.1 LIST THIS PROJECT AS A BUSINESS
 OCCUPANCY, THAT IT IS NOT A MIXED USE OCCUPANCY. THE
 SHEET DOES NOT HAVE THE OCCUPANCY SEPARATION CHECKED OR
 THE EXCEPTIONC CHECKED EITHER. SHEET A-2.1 SHOWS THE
 TENANTCY AS A SINGLE TENANT FULL FLOOR BUILD-OUT. THE
 FLOOR PLATE APPROXIMATELY 12,992 SQ. FT. OF BUSINESS
 OCCUPANCY. THE ROOMS NUMBERS IDENTIFIED AS 704,708,710
 & 720 ARE ALL CONSIDERED A ASSEMBLY USAGE NOT BUSINESS.
 WHEN THE SQUARE FOOT AREAS ARE TOTALED TOGETHER(1,927
 SQ. FT.) THEY ARE OVER THE 10 % OF THE FLOOR PLATE AND
 THE FLOOR PLATE BECOMES A MIXED USE OCCUAPANCY.
  
 2010 FBC-B 08.2.1 AREA LIMITATIONS. AGGREGATE ACCESSORY
 OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 PERCENT OF
 THE BUILDING AREA OF THE STORY IN WHICH THEY ARE
 LOCATED AND SHALL NOT EXCEED THE TABULAR VALUES IN
 TABLE 503, WITHOUT BUILDING AREA INCREASES IN
 ACCORDANCE WITH SECTION 506 FOR SUCH ACCESSORY
 OCCUPANCIES.
  
 THE DESIGNER OF RECORD WILL NEED TO INDICATE THE DESIGN
 REQUIREMENTS AS EITHER COMPLYING WITH:
 FBC-B 508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR
 PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS
 OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED
 OCCUPANCIES.
 OR
 FBC-B 508.4 SEPARATED OCCUPANCIES. BUILDINGS OR
 PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS
 OF THIS SECTION SHALL BE CONSIDERED AS SEPARATED
 OCCUPANCIES.
  
 2) SHEET A2.2 SHOWS THE INSTALATION OF MARBLE AND TILE
 FLOORING. THE PLANS DO NOT INDICATE IF THERE IS A
 INTENT TO INSTALL A CRACK ISOLATION MEMBRANE BEFORE THE
 INSTALATION OF EITHER MARBLE OR TILE. IF SO THE CRACK
 ISOLATION MEMBRANE INSULATION WILL NEED TO COMPLY WITH
 FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 3) SHEET A-2-1 THE CONFERENCE ROOM # 720, 1927 SQ. FT./
 15= 46 OCCUPANTS. SHEET A-3.1 THE DOOR SCHEDULE LIST
 THIS DOOR IDENTIED AS DOOR D4 AND A ALTERNATE SLIDING
 DOOR DESIGN. THE 2010 FBC-B 1008.1.2 DOES NOT ALLOW FOR
 SLIDDING DOORS AS A PART OF A MEANS OF EGRESS WHEN THE
 OCCUPANT LOAD IS GREATER THAN 10.
  
 4) SHEET A-3.2 DETAIL # 05 SHOWS A ACCESSIBLE BREAK
 ROOM COUNTERAND SINK, THE PLANS DO NOT INDICATE
 COMPLIANCE WITH : 2010 FBC-ACCESSIBILITY CODE 606.3.
 HEIGHT.
  
 5) SHEET A-4.1 DETAIL # 1 THE WOMENS RESTROOM THE NEW
 ACCESSIBLE TOLIET COMPARTMENT IS ONLY 7'-0" THIS WILL
 NOTE MEET THE REQUIREMENTS OF ACCESSIBILITY CODE
 604.3.2. OVERLAP AND SIZE OF CLEARANCE AT WATER CLOSET.
  
  