Plan Review Notes For Permit 15031365 |
Permit Number |
15031365 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-09 07:52:42 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. STOP WORK ORDER AND THE APPLICATION INCLUDE FRAMING, | | BUT NO FRAMING DETAIL OR SCOPE WAS PROVIDED, FBC 107. | | PROVIDE A PLAN WHICH SHOWS LOCATION AND A DETAIL FOR | | FRAMING REPAIRS. | | | | 2. REVISE PLANS (OR PROVIDE ONE FLOOR PLAN) WHICH | | PROVIDES ROOM DESIGNATIONS, FBC 2010 RESIDNETIAL 310, | | EXISTING BUILDING 604.1. | | | | 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | FAC9N-3. | | | | 4. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND | | OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. | | | | TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION | | NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | HEIGHT: | | | | STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS | | - AWNING, CASEMENT, SINGLE HUNG? | | | | STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. | | CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE | | WINDOW IS FULLY OPEN. | | | | STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE. | | THIS CAN BE OBTAINED FROM THE MANUFACTURER. | | |
|