Plan Review Notes
Plan Review Notes For Permit 15031313
Permit Number 15031313
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-04-03 11:52:07THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) SHEET T, INCORRECT EDITIONS OF FIRE CODES.THE
 PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH
 EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING THE
 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) SHEET A1.1 INDICATES PROJECTIONS INTO THE MEANS OF
 EGRESS IN TWO(2) PLACES. PROJECTIONS WITHIN THE MEANS
 OF EGRESS OF NOT MORE THAN 4 1/2 INNCHES ON EACH SIDE
 SHALL BE PERMITTED AT A HEIGHT OF 38 IN. AND BELOW.
 THOSE PROJECTIONS SHALL NOT EXCEED 4 1/2 INCHES INTO
 THE CORRIDOR.
  
 3) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
  