2016-02-16 12:15:12MECHANICAL PROVISOS:
 PERMIT #15031312
 333 DOWNTOWN
 2/16/16
  
 1) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING AND
 BALANCING IS REQUIRED IN ACCORDANCE WITH SECTION
 503.2.9 FBC-10 ENERGY CONSERVATION.
 503.2.9.1: AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING
 AND BALANCING.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT A WRITTEN
 BALANCE REPORT BE PROVIDED TO THE OWNER OR THE
 DESIGNATED REPRESENTATIVE OF THE BUILDING OWNER FOR
 HVAC SYSTEMS SERVING ZONES WITH A TOTAL CONDITIONED
 AREA EXCEEDING 5000 SQUARE FEET (465 M2). AIR
 DISTRIBUTION SYSTEMS SHALL BE TESTED, ADJUSTED, AND
 BALANCED BY A LICENSED ENGINEER OR A COMPANY OR
 INDIVIDUAL HOLDING A CURRENT CERTIFICATION FROM A
 RECOGNIZED TESTING AND BALANCING AGENCY ORGANIZATION IN
 ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING
 STANDARDS.
 EXCEPTIONS:
 A) BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES
 OF 15 TONS OR LESS PER SYSTEM MAY BE TESTED AND
 BALANCED BY A MECHANICAL CONTRACTOR LICENSED TO DESIGN
 AND INSTALL SUCH SYSTEM(S).
 B) BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES
 OF 65,000 BTU/H OR LESS PER SYSTEM ARE EXEMPT FROM THE
 REQUIREMENTS OF THIS SECTION.
  
 2) THE PERMIT IS BEING ISSUED WITHOUT APPROVED
 SUBMITTALS FOR MECHANICAL EQUIPMENT AND COMPONENTS
 INCLUDING ROOF TOP HVAC STANDS AND CURBS, EXTERIOR
 LOUVERS, FIRE AND FIRE/SMOKE DAMPERS, OUTSIDE AIR
 MOTORIZED DAMPERS, SMOKE DETECTORS, C0 AND NITROGEN
 DETECTORS, REFRIGERANT PIPING INSULATION, AC EQUIPMENT
 ETC. PLEASE REVIEW THE FOLLOWING:
 DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  