Plan Review Notes For Permit 15031312 |
Permit Number |
15031312 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-11-17 15:06:53 | 1) SUBMIT COMPLETE SPECIFICATIONS/INSTALL MANUAL FOR | | THE TANKLESS WATER HEATER. THE ONE SHEET THAT WAS | | SUBMITTED IS INADEQUATE.WPB AMEND. TO FBC SEC. 107.2.1. | | 2) THE WATER CLOSETS IN THE DWELLING UNITS SHALL BE | | LOCATED 18 INCHES FROM AN ADJACENT WALL PER THE FAIR | | HOUSING GUIDELINES, NOT 16"-18" AS NOTED ON THE | | PLANS.THE 18 INCHES FROM THE CENTERLINE OF THE WATER | | CLOSET TO THE WALL IS AN ABSOLUTE MEASUREMENT AND WILL | | ACCOMMODATE A GRAB BAR AND THE SHOULDERS OF A PERSON | | SEATED ON THE TOILET. | | 3) SHT.A.6.14.1. - TYPICAL UNIT #15 - THE DOOR ON THE | | ACCESSIBLE SHOWER IN THE MASTER BATH WILL NOT ALLOW A | | PERSON IN A WHEELCHAIR ACCESS TO THE CONTROLS AND THE | | SHOWER DOOR ENCROACHES INTO THE REQUIRED CLEAR FLOOR | | SPACE ADJACENT TO THE SHOWER OPENING PREVENTING ACCESS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|