2015-11-17 15:06:531) SUBMIT COMPLETE SPECIFICATIONS/INSTALL MANUAL FOR
 THE TANKLESS WATER HEATER. THE ONE SHEET THAT WAS
 SUBMITTED IS INADEQUATE.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE WATER CLOSETS IN THE DWELLING UNITS SHALL BE
 LOCATED 18 INCHES FROM AN ADJACENT WALL PER THE FAIR
 HOUSING GUIDELINES, NOT 16"-18" AS NOTED ON THE
 PLANS.THE 18 INCHES FROM THE CENTERLINE OF THE WATER
 CLOSET TO THE WALL IS AN ABSOLUTE MEASUREMENT AND WILL
 ACCOMMODATE A GRAB BAR AND THE SHOULDERS OF A PERSON
 SEATED ON THE TOILET.
 3) SHT.A.6.14.1. - TYPICAL UNIT #15 - THE DOOR ON THE
 ACCESSIBLE SHOWER IN THE MASTER BATH WILL NOT ALLOW A
 PERSON IN A WHEELCHAIR ACCESS TO THE CONTROLS AND THE
 SHOWER DOOR ENCROACHES INTO THE REQUIRED CLEAR FLOOR
 SPACE ADJACENT TO THE SHOWER OPENING PREVENTING ACCESS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  