Plan Review Notes
Plan Review Notes For Permit 15031312
Permit Number 15031312
Review Stop M
Sequence Number 3
Notes
Date Text
2015-12-03 10:39:263RD REVIEW 2010 MECHANICAL
 PERMIT #15031312
 12/3/15
  
 1) THE REVISED AC LOAD CALCULATIONS FOR THE MITSUBISHI
 FCU?S FOR CORRIDORS 3RD AND 5TH LEVEL INDICATE 1 TON OF
 COOLING FOR EACH CORRIDOR, HOWEVER THE AC SCHEDULES ARE
 INDICATING 10 TON UNITS HAVE BEEN SELECTED FOR THOSE
 AREAS: PLEASE CLARIFY AND NOTE THAT NO O/A AIR DATA IS
 SHOWN IN THE CALCULATIONS.
 2) THE ENERGY EFFICIENCY FORM 506-2010 WAS SUBMITTED
 AGAIN WITHOUT THE COMPLIANCE CHECKLIST COMPLETED-
 PLEASE COMPLY.
 3) REVISED MITSUBISHI REFRIGERANT PIPING DIAGRAM SHEET
 1-1: A) THE DIAGRAM INDICATES CU-R-2, BUT THE SCHEDULE
 INDICATES CU-R-5. B)THE DIAGRAM INDICATES AC- 2-5 WHICH
 IS NOT IN THE AC EQUIPMENT SCHEDULE. C) AC-1A-2 SHOWN
 IN THE SCHEDULE IS NOT SHOWN IN THE DIAGRAM.
 4) REVISED PIPING DIAGRAM SHEET 1-2: A) CU-R-1 IS SHOWN
 IN THE DIAGRAM/CU-R-4 IN THE SCHEDULE. B) MITSUBISHI
 PKFY MODELS ARE SHOWN IN THE DIAGRAM/PLFY MODELS IN THE
 SCHEDULE.
 5) THE REVISED PLAN INDICATES DRYER BOOSTER FANS TO BE
 USED IN UNITS 2, 3, AND 4. PLEASE NOTE THE WEST PALM
 BEACH FIRE DEPARTMENT PROHIBITS THE USE OF BOOSTER FANS
 IN HIGH-RISE BUILDINGS.
 6) SHEET A2.1.1: PLACE A NOTE ON THE PLAN TO IDENTIFY
 THE LOCATIONS OF THE 2HR. FIRE-RATED DUCT ENCLOSURES,
 AND INDICATE ON WHICH SHEET THE ASSEMBLY DETAILS CAN BE
 FOUND.
 7) SHEET M4.03: NOA #09-0720.01 NOTED IN THE CONDENSER
 UNIT DETAIL IS EXPIRED. PLEASE PROVIDE A CURRENT NOA #.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  