Plan Review Notes
Plan Review Notes For Permit 15031312
Permit Number 15031312
Review Stop E
Sequence Number 3
Notes
Date Text
2015-12-02 18:52:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF
 THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 PG. E2.1.1
 1. REAR MAIN LOBBY DOOR INTO VEHICULAR AREA MAY BE
 MISSING AN EXIT LIGHT.
 2. NO EXIT LIGHTS IN THE VEHICULAR AREA.
 3. EXIT LIGHT MISSING AT DOOR IN ROOM 136 TO PARKING
 AREA.
 4. NEC 408.4(B) SHOW LOCATION OF SOURCE OF POWER AND
 DISCONNECT. ALL SWITCHBOARDS SHALL BE MARKED TO
 INDICATE ORIGIN OF POWER.
 PG. E2.2.1
 1. FBC-B SECTION 1011.1 EXIT SIGN PLACEMENT SHALL BE
 SUCH THAT THERE IS NO MORE THAN 100 FT. BETWEEN SIGNS.
 2. BIKE STG. ROOM 209 MISSING AUTOMATIC LIGHTING
 CONTROL
 PG. E2.3.1, E2.4.1, E2.5.1, E2.6.1
 1. FBC-B SECTION 1011.1 EXIT SIGN [PLACEMENT SHALL BE
 SUCH THAT THERE IS NO MORE THAN 100 FT. BETWEEN SIGNS.
 PG. E2.7.1
 1. NEC 406.8(B) ALL 15 AND 20 AMP 125 TO 250 VOLT
 NON-LOCKING RECEPTACLES INSTALLED IN WET LOCATIONS
 SHALL BE RATED WEATHER RESISTANT ?WR?. (TYPICAL FOR ALL
 OUTDOOR RECEPTACLES).
 2. RELOCATE THIS TOWARDS CORNER TO MAKE IT VISIBLE FROM
 BOTH DIRECTIONS AND TO POINT TOWARDS THE ACTUAL EXIT.
 PG. E2.8.1
 1. RELOCATE THIS TOWARDS CORNER TO MAKE IT VISIBLE FROM
 BOTH DIRECTIONS AND TO POINT TOWARDS THE ACTUAL EXIT.
 PG. E2.9.1
 1. ADDITIONAL NOTE TO BE ADDED #7: NEC 406.8(B) ALL 15
 AND 20 AMP 125 TO 250 VOLT NON-LOCKING RECEPTACLES
 INSTALLED IN WET LOCATIONS SHALL BE RATED WEATHER
 RESISTANT ?WR?. (TYPICAL FOR ALL OUTDOOR RECEPTACLES).
 PG. E2.10.1
 1. SHOW PANEL ?REL? ON RISER DIAGRAM AND PANEL
 SCHEDULES.
 PG. E4.1.1
 1. FOLLOWING THE LOADS FROM BOTH, SWITCHBOARDS 1 & 2,
 THERE ARE SEVERAL PANELS WHICH DO NOT APPEAR ON THE
 RISER DIAGRAM.
 PG. E4.3.1
 1. THE POWER SOURCE FOR PANEL ?RB? IS NOT IDENTIFIED,
 OR REFLECTED ON THE RISER DIAGRAM.
 PG. E5.1.1
 1. CIRCUIT DIRECTORY/PANEL SCHEDULE FOR PANEL ?RLB? IN
 NOT INDICATED AMONG THE PANEL SCHEDULES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH.
 PH. :(561) 805-6746