Plan Review Notes
Plan Review Notes For Permit 15031312
Permit Number 15031312
Review Stop B
Sequence Number 3
Notes
Date Text
2015-12-12 09:31:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15031312
 ADD: 333 FERN ST.
 CONT: KAST CONSTRUCTION
 CONTACT :
 TEL: (561)689-2910
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: SEPT. DEC.12 /2015
 ACTION: BUILDING PROVISO
  
 1) PROVISO: ; THE CITY OF WEST PALM BEACH ART IN PUBLIC
 PLACES ORDINANCE.
 2-6 COMPLIED.
 7A-7I) COMPLIED.
  
 7J) PROVISO/ DELEGATE ENGINEER. ) HORIZONTAL TRELLIS
 FOUND ON THE SOUTH & WEST SIDES OF THE BUILDING SEE
 SECTION 6,8 & 9 PAGE A7.5.4. PLEASE SHOW WIND DESIGN
 AND ANCHORING DETAILS. FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
  
 7K-7P) COMPLIED.
  
 8-10) COMPLIED.
  
 11A-B) COMPLIED
  
 11C), COMPLIED/ PROVISO. THE LETTER FROM JOE CUSCHIERI
 P. E. ACOUSTICS AND VIBRATION CONSULTANT HAS SUBMITTED
 A RATIONAL ANALYSIS AS TO HOW THEY ARE ACHIEVING THE
 IIC AND STC RATINGS.
 ALL FLOORS (FLOOR SLABS ARE 8 INCH POST TENSION SLABS)
 , THE 3RD -16TH STORY. PLEASE PROVIDE COMPLIANCE WITH
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 PROVISO: DEFERRED SUBMITTALS. 107.3.4.2.
 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 11D) COMPLIED.
  
 12A-D) COMPLIED.
  
 12E) PROVISO: NOTE THERE IS NO KNOWING WHICH WAY A R2
 OCCUPANCY CAN TURN INTO EITHER AN APARTMENT BUILDINGS
 ARE AN R-2 AS WELL AS CONDOMINIUMS. IT ISN?T UNTIL C.O.
 THAT THE DOCUMENTS GO TO THE STATE FOR THE DECLARATION
 OF CONDOMINIUM. THIS NEXT CODE ISSUE WILL BE A PROVISO,
 THE PLANS BEING REVIEWED AS THIS IS TO BE A CONDOMINIUM
 AND UNDER FAIR HOUSING.
 PROVISO: NOTE THIS POOL DECK AND POOL ARE COVERED UNDER
 THE FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY
 REQUIRES ACCESS MUST BE PROVIDED TO THE POOL DECK AREA,
 NOT AN ACCESSIBLE ROUTE (RAMP OR LIFT) DOWN INTO THE
 WATER INTO THE POOL. ON THE OTHER HAND IF THE
 ASSOCIATION ELECTS TO ALLOW THE COMMUNITY ROOM, POOL,
 AND OR POOL DECK TO BE RENTED OUT FOR PARTIES THAT THE
 PUBLIC COULD USE, THEN THIS AREA WOULD BE REQUIRED TO
 MEET FLORIDA ACCESSIBILITY SECTION 1009 OF THE
 ACCESSIBILITY CODE POOL LIFTS.
  
 12F-G) COMPLIED.
  
 .
 13) COMPLIED.
  
 14A-D) COMPLIED.
  
 14E) PROVISO: THE PLANS INDICATE THE USE OF
 PRE-ENGINEERED A/C STANDS. WHEN FIGURING THE REQUIRED
 CLEARANCES IN HEIGHT REQUIRED BY TABLE FBC-B 1509.7,
 THE CLEARANCE IS FROM THE FINISHED ROOF HEIGHT, ABOVE
 THE LIGHTWEIGHT CONCRETE ROOF.
  
 15) COMPLIED,
  
 16) PROVISO:) PRODUCT APPROVALS: DEFERRED SUBMITTAL.
 ARCHITECT WILL REVIEW/ APPROVE/ STAMP EACH PRODUCT
 APPROVAL W/ SHOP DRAWING STAMP BEFORE SUBMISSION TO
 CITY BUILDING DEPARTMENT..
  
 17-18) COMPLIED.
  
 19)A7.5.3
 19A) PROVISO: NOTE: THE POOL TRELLIS STRUCTURE
 (PERGOLA) THIS DETAIL INDICATES IT IS GOING TO BE
 DESIGNED BY A SPECIALTY ENGINEER. BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT, THE PLANS WILL NEED TO BE
 REVIEWED BY THE ENGINEER OF RECORD. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 19B) COMPLIED.
  
 20) PAGE 136 A7.5.4. 20A) PROVISO: DETAIL # 5 RIGID
 ALUMINUM CANOPY WITH FABRIC WRAPPED WILL REQUIRE WIND
 DESIGN CRITERIA SEE OPTIONS FOUND UNDER FBC-B 3105.4 .
 ALSO: FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 21-23) COMPLIED.
  
 24 A-C) COMPLIED.
  
 24D) COMPLIED. FBC-B 403.4.6 SMOKE REMOVAL. SMOKE
 CONTROL SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 909. SEE MECHANICAL REVIEWERS COMMENTS.
  
 24E-G) COMPLIED.
  
 24H) PROVISO: FBC-B 403.5.3.1 STAIRWAY COMMUNICATION
 SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS
 SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED
 STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH
 FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
  
 24I) COMPLIED. FBC-B 403.5.4 SMOKEPROOF EXIT
 ENCLOSURES. EVERY REQUIRED EXIT STAIRWAY SERVING FLOORS
 MORE THAN 75 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF
 FIRE DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH
 SECTIONS 909.20 AND 1022.9. SEE MECHANICAL REVIEWER
 COMMENT 9A.
  
 24J) COMPLIED
  
 24K) COMPLIED.
  
 25) COMPLIED. IMPACT FEES PAID.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  