Plan Review Notes
Plan Review Notes For Permit 15031312
Permit Number 15031312
Review Stop SIGNATURE
Sequence Number 2
Notes
Date Text
2016-02-24 18:39:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. I WAS UNABLE TO LOCATE THE THRESHOLD INSPECTION PLAN
 IN THE PEDDS SUBMITTED, AND THE DRAWING INDEX DOES NOT
 INDICATE ON WHICH SHEET THIS CAN BE FOUND.
  
 PLEASE ADVISE; IS THIS ON ONE OF THE STRUCTURAL SHEETS?
 OR WAS AN ORIGINAL SUBMITTED WITH THE SHELL PERMIT?
  
 ALTERNATIVELY, THIS DOCUMENT CAN BE SENT VIA EMAIL WITH
 A DIGITAL SIGNATURE.
  
 2. AFTER THE THRESHOLD INSPECTION PLAN ISSUE IS
 RESOLVED, THE SIGNATURE REVIEW WILL BE PASSED WITH THE
 FOLLOWING NOTES:
  
 SEE 15030731 (SHELL PERMIT), ORIGINAL SIGNED AND SEALED
 SURVEY AND SOILS SUBMITTED
  
 PEDDS FOR FIRST SUBMITTAL DATED 4/2/2015 - OK
 PEDDS FOR FIRST RESUBMITTAL DATED 8/18/2015 - OK
 PEDDS FOR SECOND RESUB DATED 10/26/15 - OK
 PEDDS FOR THIRD RESUB DATED 1/21/16 - OK
 PEDDS FOR FOURTH RESUB DATED 2/10/16 - OK
  
 PROVISOS:
  
 SUBMIT SIGNATURE DOCUMENT OR ORIGINAL ACOUSTIC REPORT
 (PREPARED BY JOE CUSCHIERI, PE) OR SEND A DIGITALLY
 SIGNED REPORT VIA EMAIL.
  
 SUBMIT EITHER AN ORIGINAL "GS&P CODE COMPLIANCE LETTER
 06-09-15.PDF" IN HARD COPY FORM OR SEND THE LETTER,
 DIGITALLY SIGNED, VIA EMAIL.
  
 POOL/SPA PAGES HAVE BEEN VOIDED; SEPARATE PERMIT
 REQUIRED (NO REVIEWS DONE FOR POOL 1-4, SPA 1-3; NO
 PEDDS SUBMITTED)
  
 ACCESS CONTROL (SE1 THROUGH SE7) HAVE BEEN VOIDED;
 SEPARATE PERMIT REQUIRED (NOTE THAT DAVID FAERMAN, PE'S
 TITLE BLOCK IS NOT ON THE SHEETS. THE PEDDS SUBMITTED
 FOR SE1 - SE7 PREPARED BY DAVID FAERMAN, PE INCLUDE THE
 STATEMENT (ON THE "SIGNATURE DOCUMENT" PAGE):
 WARNING: THIS SIGNATURE DOCUMENT SIGNS NO FILES!!!!
  
  
2016-02-24 12:42:37PEDDS GIVEN TO SKENNEDY