Plan Review Notes
Plan Review Notes For Permit 15031312
Permit Number 15031312
Review Stop P
Sequence Number 2
Notes
Date Text
2015-09-10 12:50:25PLUMBING:
 1) SHT.A6.2.1 - IDENTIFIES THE UNITS AS 303/503 &
 304/504 IN THE BOTTOM RIGHT HAND CORNER OF THE PLAN BY
 THE DRAWING NUMBER BUT DETAILS #1 & #2 HAVE THE UNITS
 LABELED AS UNITS 302/502. CLARIFY
 2) SHT. A 6.3.1 - IDENTIFIES THE UNITS AS 305/505 &
 306/506 IN THE LOWER RIGHT HAND CORNER OF THE PLAN BY
 THE DRAWING NUMBER BUT DETAILS #1 & #2 HAVE THE UNITS
 LABELED AS 303/503. CLARIFY.
 3) SHT.A 6.10.1 - SHOW THE LENGTH OF THE WING WALL
 ADJACENT TO THE WATER CLOSET IN THE MASTER BATH. THE
 WING WALL SHALL NOT EXCEED 24 INCHES PER THE FHA
 GUIDELINES.
 4) SHT. A 6.11.1 -SHOW THE LENGTH OF THE WING WALL
 ADJACENT TO THE WATER CLOSET IN THE MASTER BATH. THE
 WING WALL SHALL NOT EXCEED 24 INCHES PER THE FHA
 GUIDELINES.
 5) SHT. A 6.15.1 - SHOW THE LENGTH OF THE SHOWER WALL
 ADJACENT TO THE WATER CLOSET IN THE MASTER BATH.THE
 MEASUREMENT SHALL BE TAKEN FROM THE FACE OF THE WALL
 BEHIND THE WATER CLOSET TO THE OFFSET. THIS CANNOT
 EXCEED 24 INCHES.
 6) SHT. P 2.1.1 - THE NOTE AT THE GENERATOR REFERS TO
 "P6-02" - WHAT IS THIS? THERE IS NO SUCH DRAWING IN THE
 PLAN. CLARIFY.
 7) SHT. P 4.1.8. - THERE IS A HORIZONTAL STORM DRAIN
 LINE FROM 2-4" DD'S ( 940 SQ. FT.& 950 SQ. FT.) ON THE
 7TH FLOOR DISCHARGING A TOTAL OF 1890 SQUARE FEET. THE
 HORIZONTAL LINE IS NOT SIZED BUT THIS LINE NEEDS TO BE
 A MINIMUM OF 5". THE MAXIMUM SQUARE FOOTAGE A 4"
 HORIZONTAL STORM DRAIN CAN CARRY AT A 5" DESIGN
 RAINFALL RATE IS 1504 SQUARE FEET. THIS SECTION NEEDS
 TO BE INCREASED TO A MINIMUM SIZE OF 5 INCH.
 8) SHT. P 5.1.2. - ELEVATOR SUMP DETAIL - A FULL OPEN
 GATE VALVE IS REQD. ON THE DOWNSTREM (DISCHARGE) SIDE
 OF THE CHECK VALVE PER 2010 FBC-PLUMBING SEC.712.2.
 9) SUBMIT SPECIFICATIONS FOR THE TANKLESS WATER HEATER.
 WPB AMEND. TO FBC SEC. 107.2.1.
 10) THE DETAIL FOR THE WATER HEATER & RELIEF VALVE
 DISCHARGE ON SHT.P5.1.2 MEETS CODE BUT THE RISERS ON
 SHT.P4.1.10 STILL SHOW THE RELIEF LINES & PAN DRAINS
 INTO THE SAME RISER. PLACE A NOTE ON P4.1.10 TO SEE
 SHT. P5.1.2 FOR RELIEF VALVE & PAN DRAIN DETAIL.
  
 SWIMMING POOL & SPA
 1) INDICATE ON THE PLAN HOW THE OCCUPANT LOAD OF 31
 PERSONS FOR THE POOL WAS CALCULATED.WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 2) THE POOL & SPA PLANS SHOW THE WASTE WATER
 DISCHARGING TO THE SANITARY SYSTEM. SEE SHEET #367,
 POOL 4 OF 4 & SHT.370 SPA 2. POOL WATER CANNOT
 DISCHARGE TO THE SANITARY OR TO THE STORM SYSTEM PER
 CITY ORDINANCE SEC.90-126 (5) AND SEC. 90-203 (A) ,
 90-204, 90-205 (1).
 3) THE MAXIMUM FILTRATION RATE IN GALLONS PER MINUTE
 PER SQUARE FOOT OF FILTER AREA SHALL BE 0.075 FOR
 CARTRIDGE FILTERS PER 2010 FBC SEC.424.1.6.5.5.
 INDICATE COMPLIANCE ON THE PLANS FOR BOTH THE POOL &
 SPA.
 4) SUBMIT VERIFICATION FROM THE PALM BEACH COUNTY
 HEALTH DEPARTMENT THAT AN APPLICATION FOR AN OPERATING
 PERMIT HAS BEEN SUBMITTED TO THEM FOR THIS POOL & SPA.
 5) PIPING AND INFLUENT, EFFLUENT AND BYPASS VALVES
 WHICH ALLOW ISOLATION OR REMOVAL OF THE HEATER FROM THE
 SYSTEM SHALL BE PROVIDED PER 2010 FBC SEC.424.1.6.5.14.
 SEE RETURN LINE ON THE POOL & SPA.
 6) THE CAPACITY OF THE COLLECTOR TANKS SHALL BE AT
 LEAST 1 MINUTE OF OF THE RECIRCULATED FLOW PER 2010 FBC
 SEC.424.1.6.5.10.5. PLEASE EXPLAIN THE METHOD OF
 ARRIVING AT THE REDUCED SIZE OF THE COLLECTOR TANKS FOR
 THE POOL & SPA..
 7) SIZE ALL THE PIPING TO AND FROM THE POOL HEATERS ON
 THE POOL AND SPA PIPING RISERS.WPB AMEND. TO FBC SEC.
 107.2.1.
 8) SUBMIT MSDS DOCUMENTS FOR THE POOL CHEMICALS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 9) INDICATE THE LOCATION OF THE CHEMICALS ON THE POOL,
 SPA AND BUILDING PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHT.370 (SPA 2) SHOWS 50 GAL. ACID & CHLORINE TANKS
 SHARED WITH POOL AND SHT. 367 (POOL 4) SHOWS 30 GAL.
 ACID & CHLORINE TANKS.ARE THESE TWO SEPARATE SETS OF
 TANKS OR SHARED AND WHAT IS THE PROPER CAPACITY?
 CLARIFY.
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATERS. THE HEATERS SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH 2010 FBC-FUEL GAS SEC. 301.3.
 12) SUBMIT MANUFACTURER'S SPECIFICATIONS OF RTHE MAIN
 DRAIN GRATES FOR THE POOL AND SPA.WPB AMEND. TO FBC
 SEC. 107.2.1, ANSI/APSP-7 SEC.4.5.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
 REVIEW NOT COMPLETE