2015-09-10 12:50:25 | PLUMBING: |
| 1) SHT.A6.2.1 - IDENTIFIES THE UNITS AS 303/503 & |
| 304/504 IN THE BOTTOM RIGHT HAND CORNER OF THE PLAN BY |
| THE DRAWING NUMBER BUT DETAILS #1 & #2 HAVE THE UNITS |
| LABELED AS UNITS 302/502. CLARIFY |
| 2) SHT. A 6.3.1 - IDENTIFIES THE UNITS AS 305/505 & |
| 306/506 IN THE LOWER RIGHT HAND CORNER OF THE PLAN BY |
| THE DRAWING NUMBER BUT DETAILS #1 & #2 HAVE THE UNITS |
| LABELED AS 303/503. CLARIFY. |
| 3) SHT.A 6.10.1 - SHOW THE LENGTH OF THE WING WALL |
| ADJACENT TO THE WATER CLOSET IN THE MASTER BATH. THE |
| WING WALL SHALL NOT EXCEED 24 INCHES PER THE FHA |
| GUIDELINES. |
| 4) SHT. A 6.11.1 -SHOW THE LENGTH OF THE WING WALL |
| ADJACENT TO THE WATER CLOSET IN THE MASTER BATH. THE |
| WING WALL SHALL NOT EXCEED 24 INCHES PER THE FHA |
| GUIDELINES. |
| 5) SHT. A 6.15.1 - SHOW THE LENGTH OF THE SHOWER WALL |
| ADJACENT TO THE WATER CLOSET IN THE MASTER BATH.THE |
| MEASUREMENT SHALL BE TAKEN FROM THE FACE OF THE WALL |
| BEHIND THE WATER CLOSET TO THE OFFSET. THIS CANNOT |
| EXCEED 24 INCHES. |
| 6) SHT. P 2.1.1 - THE NOTE AT THE GENERATOR REFERS TO |
| "P6-02" - WHAT IS THIS? THERE IS NO SUCH DRAWING IN THE |
| PLAN. CLARIFY. |
| 7) SHT. P 4.1.8. - THERE IS A HORIZONTAL STORM DRAIN |
| LINE FROM 2-4" DD'S ( 940 SQ. FT.& 950 SQ. FT.) ON THE |
| 7TH FLOOR DISCHARGING A TOTAL OF 1890 SQUARE FEET. THE |
| HORIZONTAL LINE IS NOT SIZED BUT THIS LINE NEEDS TO BE |
| A MINIMUM OF 5". THE MAXIMUM SQUARE FOOTAGE A 4" |
| HORIZONTAL STORM DRAIN CAN CARRY AT A 5" DESIGN |
| RAINFALL RATE IS 1504 SQUARE FEET. THIS SECTION NEEDS |
| TO BE INCREASED TO A MINIMUM SIZE OF 5 INCH. |
| 8) SHT. P 5.1.2. - ELEVATOR SUMP DETAIL - A FULL OPEN |
| GATE VALVE IS REQD. ON THE DOWNSTREM (DISCHARGE) SIDE |
| OF THE CHECK VALVE PER 2010 FBC-PLUMBING SEC.712.2. |
| 9) SUBMIT SPECIFICATIONS FOR THE TANKLESS WATER HEATER. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 10) THE DETAIL FOR THE WATER HEATER & RELIEF VALVE |
| DISCHARGE ON SHT.P5.1.2 MEETS CODE BUT THE RISERS ON |
| SHT.P4.1.10 STILL SHOW THE RELIEF LINES & PAN DRAINS |
| INTO THE SAME RISER. PLACE A NOTE ON P4.1.10 TO SEE |
| SHT. P5.1.2 FOR RELIEF VALVE & PAN DRAIN DETAIL. |
| |
| SWIMMING POOL & SPA |
| 1) INDICATE ON THE PLAN HOW THE OCCUPANT LOAD OF 31 |
| PERSONS FOR THE POOL WAS CALCULATED.WPB AMEND. TO 2010 |
| FBC SEC. 107.2.1. |
| 2) THE POOL & SPA PLANS SHOW THE WASTE WATER |
| DISCHARGING TO THE SANITARY SYSTEM. SEE SHEET #367, |
| POOL 4 OF 4 & SHT.370 SPA 2. POOL WATER CANNOT |
| DISCHARGE TO THE SANITARY OR TO THE STORM SYSTEM PER |
| CITY ORDINANCE SEC.90-126 (5) AND SEC. 90-203 (A) , |
| 90-204, 90-205 (1). |
| 3) THE MAXIMUM FILTRATION RATE IN GALLONS PER MINUTE |
| PER SQUARE FOOT OF FILTER AREA SHALL BE 0.075 FOR |
| CARTRIDGE FILTERS PER 2010 FBC SEC.424.1.6.5.5. |
| INDICATE COMPLIANCE ON THE PLANS FOR BOTH THE POOL & |
| SPA. |
| 4) SUBMIT VERIFICATION FROM THE PALM BEACH COUNTY |
| HEALTH DEPARTMENT THAT AN APPLICATION FOR AN OPERATING |
| PERMIT HAS BEEN SUBMITTED TO THEM FOR THIS POOL & SPA. |
| 5) PIPING AND INFLUENT, EFFLUENT AND BYPASS VALVES |
| WHICH ALLOW ISOLATION OR REMOVAL OF THE HEATER FROM THE |
| SYSTEM SHALL BE PROVIDED PER 2010 FBC SEC.424.1.6.5.14. |
| SEE RETURN LINE ON THE POOL & SPA. |
| 6) THE CAPACITY OF THE COLLECTOR TANKS SHALL BE AT |
| LEAST 1 MINUTE OF OF THE RECIRCULATED FLOW PER 2010 FBC |
| SEC.424.1.6.5.10.5. PLEASE EXPLAIN THE METHOD OF |
| ARRIVING AT THE REDUCED SIZE OF THE COLLECTOR TANKS FOR |
| THE POOL & SPA.. |
| 7) SIZE ALL THE PIPING TO AND FROM THE POOL HEATERS ON |
| THE POOL AND SPA PIPING RISERS.WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 8) SUBMIT MSDS DOCUMENTS FOR THE POOL CHEMICALS.WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 9) INDICATE THE LOCATION OF THE CHEMICALS ON THE POOL, |
| SPA AND BUILDING PLANS.WPB AMEND. TO FBC SEC. 107.2.1. |
| 10) SHT.370 (SPA 2) SHOWS 50 GAL. ACID & CHLORINE TANKS |
| SHARED WITH POOL AND SHT. 367 (POOL 4) SHOWS 30 GAL. |
| ACID & CHLORINE TANKS.ARE THESE TWO SEPARATE SETS OF |
| TANKS OR SHARED AND WHAT IS THE PROPER CAPACITY? |
| CLARIFY. |
| 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| HEATERS. THE HEATERS SHALL BE LISTED AND LABELED IN |
| ACCORDANCE WITH 2010 FBC-FUEL GAS SEC. 301.3. |
| 12) SUBMIT MANUFACTURER'S SPECIFICATIONS OF RTHE MAIN |
| DRAIN GRATES FOR THE POOL AND SPA.WPB AMEND. TO FBC |
| SEC. 107.2.1, ANSI/APSP-7 SEC.4.5. |
| |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |