2015-04-29 15:38:36 | 333 FERN STREET |
| PERMIT #15031312 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| (2012 EDITION WITH FLORIDA AMENDMENTS.) |
| |
| |
| SHEET C-09: PER NFPA 24 SECTION 6.2.1, BACKFLOW |
| PREVENTER CONTROL VALVES SHALL BE INSTALLED IN A |
| FIRE-RATED ROOM ACCESSIBLE FROM THE EXTERIOR. |
| |
| SHEET LS-0.1: DEAD-END CORRIDORS IN STORAGE AND |
| APARTMENT OCCUPANCIES SHALL NOT EXCEED 20 FEET PER |
| TABLE 42.2.5 AND SECTION 30.2.5.4.2 RESPECTIVELY. |
| |
| SHEET LS-1.0: DEAD-ENDS EXCEED 20 FEET OF TRAVEL IN |
| OWNERS' STORAGE #133. |
| |
| SHEET LS-3.0: CORRIDOR HAS A DEAD-END MEASURING 40 |
| FEET. NEW APARTMENT DEAD-END CORRIDORS ARE LIMITED TO |
| 20 FEET PER NFPA 101 SECTION 30.2.5.4.2. |
| |
| SHEET LS-7.0: POOL CORRIDOR #706 CREATES A DEAD-END |
| EXCEEDING 20 FEET IN LENGTH. |
| |
| SHEET LS-7.0: ALL THREE SECONDARY EXITS FROM COMMON |
| ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT THE EXIT |
| ACCESS DOOR LEADING TO THE POOL DECK. |
| |
| SHEET A2.1.1: EXIT ACCESS CORRIDOR #115 APPEARS TO |
| ACTUALLY BE AN EXIT PASSAGEWAY. |
| |
| SHEET A7.1.1: TWO-HOUR TRASH CHUTE IS PROTECTED BY |
| 45-MINUTE FIRE RATED DOORS. |
| |
| SHEET FP2-1-1: THE PLANS INDICATE TWO FIRE MAINS |
| SUPPLYING THE FIRE PUMP; HOWEVER, THE THESE TWO MAINS |
| REDUCE TO ONE MAIN IMMEDIATELY INSIDE THE BUILDING. THE |
| MAINS NEED TO BE REMAIN SEPARATE UNTIL THEY REACH THE |
| FIRE PUMP ROOM. |
| |
| SHEET FA5-1-1: PROVIDE BI-DIRECTIONAL AMPLIFIER/TWO-WAY |
| RADIO COMMUNICATION ENHANCEMENT SYSTEMS COMPLYING WITH |
| NFPA 72. |
| |
| SITE: WHERE ARE THE CONSTRUCTION TRAILERS INTENDED TO |
| BE LOCATED? PER NFPA 241 SECTION 4.2.2: DETACHMENT |
| BETWEEN TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED |
| FIRE PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL |
| BE PROVIDED AS REQUIRED BY THE AUTHORITY HAVING |
| JURISDICTION. |
| |
| SITE: PER NFPA 241- STANDARD FOR SAFEGUARDING |
| CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, |
| SECTION 4.2: TEMPORARY OFFICES, TRAILERS, AND OTHER |
| FACILITIES OF COMBUSTIBLE CONSTRUCTION OR HOUSING |
| COMBUSTIBLE CONTENTS SHALL BE SEPARATED FROM ADJACENT |
| BUILDINGS, TRAILERS OR STRUCTURES IN ACCORDANCE WITH |
| TABLE 4.2.1. PER TABLE 4.2.1: |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| |
| NOTE: PER FFPC SECTION 11.9.4 AND FBC SECTION 911.1.5 - |
| THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND |
| SHALL CONTAIN THE FOLLOWING FEATURES: |
| 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| CONTROL UNIT. |
| 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR. |
| 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL. |
| 5. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION |
| SYSTEMS. |
| 6. THE FIRE-FIGHTER'S CONTROL PANEL REQUIRED BY SECTION |
| 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE |
| BUILDING. |
| 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| SIMULTANEOUSLY. |
| 8. SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY |
| PANELS. |
| 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS. |
| 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| ACCESS TO THE PUBLIC TELEPHONE SYSTEM. |
| 11. FIRE PUMP STATUS INDICATORS. |
| 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION |
| OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| BARRIERS AND SMOKE PARTITIONS. |
| 13. WORK TABLE. |
| 14. GENERATOR SUPERVISION DEVICES, MANUAL START AND |
| TRANSFER FEATURES. |
| 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| BY OTHER SECTIONS OF THIS CODE. |
| 16. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| A17.1. |
| 17. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| PROVIDED. |
| |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |