Plan Review Notes
Plan Review Notes For Permit 15031312
Permit Number 15031312
Review Stop E
Sequence Number 2
Notes
Date Text
2015-10-01 20:13:37PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF
 THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
  
 1. THESE BEING RENTAL UNITS, THE CORRIDOR OUTLETS ARE
 UNDER THE HOUSE LOAD AND THUS WILL NOT PLACE A BURDEN
 ON ANOTHER TENANT. (RENTAL OR PRIVATE OWNERSHIP OF
 THESE UNITS HAD NOT BEEN MADE KNOW BEFORE)
 2. NEC REQUIRES THAT YOU INCLUDE A LAUNDRY CIRCUIT IN
 THE LOAD CALCS. THE OTHER GENERAL PURPOSE OUTLETS WHICH
 MAY BE IN THE LAUNDRY ROOM/AREA FALL UNDER THE GENERAL
 LIGHTING LOADS. THERE IS NOTHING PROHIBITING YOU FROM
 DOING IT THE WAY YOU HAVE, IT IS JUST NOT NECESSARY.
 3. THERE APPEARS NOT TO BE ENOUGH LIGHT TO WORK INSIDE
 THE ELECTRICAL PANEL COMING FROM THE DOWN LIGHTS IN THE
 KITCHEN ISLAND, ON PG. E3.8.1, PG. E3.9.1, PG. E3.9.1A
 4. PG. E3.16 CLUB HOUSE: MISSING CONVENIENCE GFI
 OUTLETS AT ISLAND COUNTER.
 5. PG. E3.16 CLUB HOUSE: PER NEC 422.52 ELECTRIC
 DRINKING FOUNTAINS SHALL BE ON A GFI PROTECTED CIRCUIT.
 6. PG. E3.16 CLUB HOUSE: INDICATE WHICH SIDE THE PANEL
 WILL FACE. PER NEC 210.70(3) THERE HAS TO BE AMPLE
 LIGHTING ABOUT THE ELECTRICAL PANEL.
 7. PG. E3.16 CLUB HOUSE: I DON?T SEE THE MANDATORY
 ADDITIONAL CONTROLS (OCCUPANCY SENSORS) REQUIRED BY THE
 FBC-ENERGY FOR THIS AREA.
 8. (CHECK THE EXIT DOOR BY THE RESTROOMS FOR THE PROPER
 SWING IN THE PATH OF TRAVEL.)
 9. PG. E4.1.1 PANEL G HAS A CALCULATED LOAD OF 156 AMP
 WITHOUT TAKING 125% FOR THE CONTINUOUS LOADS INTO
 ACCOUNT; #4 THWN AL IS ONLY GOOD FOR 150 AMP.
 10. PG. E4.2.1 PANEL MEL HAS A LOAD OF 11.6 AMP NOT
 8.8.
 11. PG. E4.3.1 PANEL RL HAS A CONNECTED LOAD OF 820 AMP
 ACCORDING TO YOU NUMBERS, HAVE YOU CONSIDERED THE
 CONTINUOUS LOADS AS THE FEEDERS ARE EXACT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  