Date |
Text |
2015-09-28 15:40:26 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15031312 |
| ADD: 333 FERN ST. |
| CONT: KAST CONSTRUCTION |
| CONTACT : |
| TEL: (561)689-2910 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2ND REVIEW |
| DATE: MON. SEPT. 28 /2015 |
| ACTION: DENIED |
| |
| 1) PROVISO: ; THE CITY OF WEST PALM BEACH ART IN PUBLIC |
| PLACES ORDINANCE. |
| 2-6 COMPLIED. |
| 7A-7I) COMPLIED. |
| 7J) PROVISO/ DELEGATE ENGINEER. ) HORIZONTAL TRELLIS |
| FOUND ON THE SOUTH & WEST SIDES OF THE BUILDING SEE |
| SECTION 6,8 & 9 PAGE A7.5.4. PLEASE SHOW WIND DESIGN |
| AND ANCHORING DETAILS. FBC-B 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER |
| SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO |
| THE ENGINEER OF RECORD FOR REVIEW. |
| 7K-7M) COMPLIED. |
| 7N) 2ND REQUEST. RESPONSE INDICATES NOTE # 37 SHEET |
| 024-LS-1.0. NO SUCH NOTE. NOR ON SHEET 023-LS-01. |
| PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F] |
| 914.2 EQUIPMENT ROOM IDENTIFICATION. FIRE PROTECTION |
| EQUIPMENT SHALL BE IDENTIFIED IN AN APPROVED MANNER. |
| ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS, |
| SPRINKLER RISERS AND VALVES OR OTHER FIRE DETECTION, |
| SUPPRESSION OR CONTROL ELEMENTS SHALL BE IDENTIFIED FOR |
| THE USE OF THE FIRE DEPARTMENT. APPROVED SIGNS REQUIRED |
| TO IDENTIFY FIRE PROTECTION EQUIPMENT AND EQUIPMENT |
| LOCATION SHALL BE CONSTRUCTED OF DURABLE MATERIALS, |
| PERMANENTLY INSTALLED AND READILY VISIBLE |
| 70-7P) COMPLIED. |
| 8A-B) COMPLIED. |
| 9A) DISCREPANCY IN PLANS, SEMI-COMPLIED. THE RESPONSE |
| INDICATED THE DIMENSIONS WERE ADDED TO SHEETS |
| 077-A6.1.1 AND 078-A6.1.2 BUT THEY WERE NEVER CHANGED |
| ON SHEETS 038-A2.3.1 OR 039- A2.3.2. |
| DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED COMMON |
| AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE UNIT. |
| THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON THE |
| LATCH SIDE OF THE DOOR, PER FAIR HOUSING REQUIREMENT 3. |
| USABLE DOORS. GUIDELINE SECTION 100.205(C)(2) WOULD |
| APPLY TO DOORS THAT ARE A PART OF AN ACCESSIBLE ROUTE |
| IN THE PUBLIC AND COMMON USE AREAS OF MULTIFAMILY |
| DWELLINGS AND TO DOORS INTO AND WITHIN INDIVIDUAL |
| DWELLING UNITS. |
| (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS |
| AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS |
| THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT. |
| 9B) COMPLIED. |
| 10A-B) COMPLIED. |
| 10C) NEW COMMENT. PLEASE SEE MARK UP ON SHEET |
| 039-A2-3-2. THE COMMON CORRIDOR HAS PINCH POINTS IN THE |
| CORRIDOR NEXT TO THE COLUMN LINE WHERE 36 INCH MINIMUM |
| IS REQUIRED FOR THE CORRIDOR WIDTH BOTH BY FAIR HOUSING |
| AND THE 2010 FBC-B 1018.2 EXC. # 2. |
| 11A) DISCREPANCY IN PLANS, SEMI-COMPLIED. THE RESPONSE |
| INDICATED THE DIMENSIONS WERE ADDED TO SHEETS |
| 077-A6.1.1 AND 078-A6.1.2 BUT THEY WERE NEVER CHANGED |
| ON SHEETS 045-A2.5.2. |
| DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED COMMON |
| AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE UNIT. |
| THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON THE |
| LATCH SIDE OF THE DOOR, PER FAIR HOUSING REQUIREMENT 3. |
| USABLE DOORS. GUIDELINE SECTION 100.205(C)(2) WOULD |
| APPLY TO DOORS THAT ARE A PART OF AN ACCESSIBLE ROUTE |
| IN THE PUBLIC AND COMMON USE AREAS OF MULTIFAMILY |
| DWELLINGS AND TO DOORS INTO AND WITHIN INDIVIDUAL |
| DWELLING UNITS. |
| 11B) COMPLIED. |
| 11C), 11C)(1A), 11C(1B) 11C)(1C) THE LETTER FROM JOE |
| CUSCHIERI P. E. ACOUSTICS AND VIBRATION CONSULTANT WILL |
| NEED TO PROVIDE RATIONAL ANYLSIS AS TO HOW THEY ARE |
| ACHIEVING THE IIC AND STC RATINGS STATED WITHIN THE |
| LETTER. WE SEE MANY PRODUCTS THAT WERE TESTED IN |
| LAVATORIES ON A 6 INCH CONCRETE SLAB AND BARELY GET A |
| IIC RATING OF 51 WITH SOUND INSULATION. AT THE VARY END |
| OF THE LETTER THE STATEMENT FOR HARD FINISHES SUCH AS |
| WOOD OR MARBLE OR TILE MITIGATION FOR STRUCTURE BORNE |
| SOUND SUCH AS THE USE OF KINETIC SR FLOOR BOARD OR |
| EQUIVALENT SHOULD BE CONSIDERED TO MEET THE FBC |
| REQUIREMENT. |
| COMMENT FROM THE 1ST REVIEW. 11C) THIS COMMENT WILL BE |
| A COMMON COMMENT FOR ALL FLOORS (FLOOR SLABS ARE 8 INCH |
| POST TENSION SLABS) , THE 3RD -16TH STORY. PLEASE |
| PROVIDE COMPLIANCE WITH BLDG TYPE: TYPE I/ TYPE II |
| FLOOR INSULATION |
| |
| 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 11D) NEW COMMENT. PLEASE SEE MARK UP ON SHEET |
| 045-A2.5.2. THE COMMON CORRIDOR HAS PINCH POINTS IN THE |
| CORRIDOR NEXT TO THE COLUMN LINE WHERE 36 INCH MINIMUM |
| IS REQUIRED FOR THE CORRIDOR WIDTH BOTH BY FAIR HOUSING |
| AND THE 2010 FBC-B 1018.2 EXC. # 2. |
| |
| 12A) COMPLIED. |
| |
| 12B) POOL DECK AND THE MEANS OF EGRESS. PLEASE VERIFY |
| THE EGRESS DOORS THAT LEAD FROM THE POOL DECK TO THE |
| INTERIOR OF THE BUILDING HAVE CARD READERS ON BOTH |
| DOORS. PLEASE VERIFY THE CARD READERS ARE FOR ENTRY |
| ONTO THE POOL DECK. THAT IF YOU ARE ON THE POOL DECK |
| THE DOORS WILL AUTOMATICALLY UNLOCK. THIS CONFIGURATION |
| WILL ALSO LIMIT CHILDREN GAINING ACCESS TO THE POOL |
| DECK AND BE IN COMPLIANCE WITH 2010 FBC-B 424.1.3.1.9. |
| |
| 12C) COMPLIED. |
| |
| 12D) 2ND REQUEST. PLEASE SEE THE SHEET 119-A6.16.1 THE |
| TOTAL CORRIDOR WIDTH IS 4 FT. 7 ? INCHES WIDE. DOOR |
| 706F DOES NOT COMPLY WITH THE FAIR HOUSING GUIDE LINES |
| REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC AND COMMON |
| USE AREAS. ANSI A117.1 TABLE 404.2.4.1 MANEUVERING |
| CLEARANCES FOR MANUAL SWING DOORS. |
| |
| 12E) NOTE THERE IS NO KNOWING WHICH WAY A R2 OCCUPANCY |
| CAN TURN INTO. APARTMENT BUILDINGS ARE A R-2 AS WELL AS |
| CONDOMINIUMS. IT ISN?T UNTIL C.O. THAT THE DOCUMENTS GO |
| TO THE STATE FOR THE DECLARATION OF CONDOMINIUM. THIS |
| NEXT CODE ISSUE WILL BE A PROVISO, THE PLANS BEING |
| REVIEWED AS THIS IS TO BE A CONDOMINIUM AND UNDER FAIR |
| HOUSING. |
| PROVISO: NOTE THIS POOL DECK AND POOL ARE COVERED UNDER |
| THE FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY |
| REQUIRES ACCESS MUST BE PROVIDED TO THE POOL DECK AREA, |
| NOT AN ACCESSIBLE ROUTE (RAMP OR LIFT) DOWN INTO THE |
| WATER INTO THE POOL. ON THE OTHER HAND IF THE |
| ASSOCIATION ELECTS TO ALLOW THE COMMUNITY ROOM, POOL, |
| AND OR POOL DECK TO BE RENTED OUT FOR PARTIES THAT THE |
| PUBLIC COULD USE, THEN THIS AREA WOULD BE REQUIRED TO |
| MEET FLORIDA ACCESSIBILITY SECTION 1009 OF THE |
| ACCESSIBILITY CODE POOL LIFTS. |
| |
| 12F) 2ND REQUEST. ) THIS NOTE WILL BE A COMMON NOTE FOR |
| FLOORS 7-20TH FLOORS. THE DOOR SCHEDULE FOUND ON PAGE |
| 126 A.7.1.1 (DOOR SCHEDULE) IN THE REMARKS COLUMN THERE |
| ARE VARIOUS DOORS IN THE CORRIDOR(STORAGE & ELECTRICAL) |
| THAT STATE THAT A FIRE DAMPER IS TO BE INSTALLED IN THE |
| LOUVERED DOOR. PLEASE SHOW COMPLIANCE WITH: |
| |
| 2010 FBC-B 715.4.6 LABELED PROTECTIVE ASSEMBLIES. FIRE |
| DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED AGENCY. |
| THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL BE |
| PERMANENTLY AFFIXED TO THE DOOR OR FRAME INSTALLED |
| WITHIN THE LOUVERED DOOR. |
| |
| 716.5.2 FIRE BARRIERS. DUCTS AND AIR TRANSFER OPENINGS |
| OF FIRE BARRIERS SHALL BE PROTECTED WITH APPROVED FIRE |
| DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING. |
| |
| 12G) COMPLIED. |
| 13A) COMPLIED. SLIDING GLASS DOORS. |
| 13B) 2ND REQUEST. ) FOR ALL SLIDING GLASS DOORS THE |
| HARDWARE WILL ALSO NEED TO MEET THE ANSI 117.1 STANDARD |
| 404.2.7. RESPONSE INDICATES SEE SPECS, REQUIREMENT |
| INCLUDED IN SPEC. IF SPEC BOOKS ARE SUBMITTED WE STAMP |
| THEM VOID. WE ARE LOOKING FOR CODE COMPLIANCE ON THE |
| PLANS. WE DO NOT REVIEW SPEC BOOKS> |
| |
| 14A-D) COMPLIED. |
| |
| 14E) PROVISO: THE PLANS INDICATE THE USE OF |
| PRE-ENGINEERED A/C STANDS. WHEN FIGURING THE REQUIRED |
| CLEARANCES IN HEIGHT REQUIRED BY TABLE FBC-B 1509.7, |
| THE CLEARANCE IS FROM THE FINISHED ROOF HEIGHT, ABOVE |
| THE LIGHTWEIGHT CONCRETE ROOF. |
| |
| 15) COMPLIED, |
| |
| 16A-C) PRODUCT APPROVALS: DEFERRED SUBMITTAL. ARCHITECT |
| WILL APPROVE/ STAMP EACH PRODUCT APPROVAL AND SUBMIT. |
| |
| 17-18) COMPLIED. |
| |
| 19)A7.5.3 |
| 19A) PROVISO: ) NOTE: THE POOL TRELLIS STRUCTURE |
| (PERGOLA) THIS DETAIL INDICATES IT IS GOING TO BE |
| DESIGNED BY A SPECIALTY ENGINEER. BEFORE SUBMITTAL TO |
| THE BUILDING DEPARTMENT, THE PLANS WILL NEED TO BE |
| REVIEWED BY THE ENGINEER OF RECORD. FL 61G-15-30.006 |
| (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 19B) COMPLIED. |
| |
| |
| |
| 20) PAGE 136 A7.5.4. 20A) PROVISO: DETAIL # 5 RIGID |
| ALUMINUM CANOPY WITH FABRIC WRAPPED WILL REQUIRE WIND |
| DESIGN CRITERIA SEE OPTIONS FOUND UNDER FBC-B 3105.4 . |
| ALSO: FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| ENGINEER OF RECORD FOR REVIEW. |
| |
| 21-23) COMPLIED. |
| |
| 24 A-C) COMPLIED. |
| |
| 24D) 2ND REQUEST ) FBC-B 403.4.6 SMOKE REMOVAL. SMOKE |
| CONTROL SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| 909. SEE MECHANICAL REVIEWERS COMMENTS. |
| |
| 24E-G) COMPLIED. |
| |
| 24H) PROVISO: FBC-B 403.5.3.1 STAIRWAY COMMUNICATION |
| SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS |
| SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED |
| STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH |
| FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY |
| ARE LOCKED. |
| |
| 24I) 2ND REQUEST. ) FBC-B 403.5.4 SMOKEPROOF EXIT |
| ENCLOSURES. EVERY REQUIRED EXIT STAIRWAY SERVING FLOORS |
| MORE THAN 75 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF |
| FIRE DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH |
| SECTIONS 909.20 AND 1022.9. SEE MECHANICAL REVIEWER |
| COMMENT 9A. |
| |
| 24J) 2ND REQUEST, RESPONSE: ACKNOWLEDGED. FBC-B 1022.8 |
| FLOOR IDENTIFICATION SIGNS. / 1022.8.1 SIGNAGE |
| REQUIREMENTS. |
| |
| 24K) COMPLIED. |
| |
| 25) COMPLIED. IMPACT FEES PAID. |
| |
| 26) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |