2015-06-14 07:35:491)THE BREAK ROOM SINK ON THE FIRST FLOOR ( RM. 125A)
 SHALL COMPLY W/ FL. ACCESSIBILITY CODE SEC. 212 AND
 606.
 2)SUPPLY A KEYNOTE LEGEND ON THE PLANS FOR THE HEXAGON,
 CIRCLE, SQUARE AND DIAMOND SYMBOLS. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 3)THE SWIMMING POOL AND DECK ARE COVERED UNDER THE FAIR
 HOUSING ACT WHICH ONLY REQUIRES ACCESS TO THE POOL
 AREA. HOWEVER, IF THE CONDOMINIUM ASSOCIATION ELECTS
 THAT THE COMMUNITY ROOM, POOL AND POOL DECK TO BE
 RENTED OUT FOR PARTIES TO THE PUBLIC, THEN FULL
 COMPLIANCE WITH SEC. 1009 OF THE FL. ACCESSIBILITY CODE
 IS REQUIRED.
 4)INDICATE ON THE STORM DRAINAGE PLANS THE RAINFALL
 RATE THAT WAS USED FOR THE SIZING OF THE STORM DRAINAGE
 SYSTEM. THE RAINFALL RATE FOR THIS AREA IS 5 INCHES PER
 HOUR. FBC 1503.4, FPC FIGURE 1106.1.
 5)SHT. A7.5.2 -THE TOP OF THE ROOF DRAIN STRAINER SHALL
 EXTEND NO LESS THAN 4 INCHES ABOVE THE ROOF SURFACE
 IMMEDIATELY ADJACENT TO THE ROOF DRAIN PER 2010 FPC
 SEC.1105.1.
 6)SHEET P5.1.2- SUBMIT DETAILS FOR THE FIRESTOP SYSTEM
 FOR THE TUB DRAINS IN THE FLOOR SLABS. FBC 713.4.1.1.1,
 713.4.1.1.2.
 7)SHT. LS-0.2 - DETAIL 1 THE MINIMUM AND MAXIMUM
 HEIGHTS ARE INCORRECT FOR THE GRAB BAR BACKING FOR THE
 WATER CLOSETS.. THE BOTTOM OF THE REINFORCEMENT SHALL
 BE AT 32 INCHES MAXIMUM ABOVE THE FLOOR AND THE TOP OF
 THE REINFORCEMENT SHALL BE LOCATED 38 INCHES MINIMUM
 PER DETAIL # 3 OF THE FHA GUIDELINES.
 8)SHT. LS-0.2 - BATHTUB- BACK WALL - THE REINFORCEMENT
 SHALL BE LOCATED A MAXIMUM OF 6 INCHES FROM THE SIDE
 WALLS ON BOTH SIDES. FHA FIGURE # 4.
 9)SHT. LS-0.2 - THE TOP OF THE REINFORCEMENT ON THE
 BACK WALL OF THE TUB SHALL BE LOCATED A MINIMUM OF 38
 INCHES ABOVE THE FLOOR, NOT 38 INCHES MAXIMUM AS SHOWN.
 FHA FIGURE #4.
 10)SHT. LS-0.2- THE BOTTOM OF THE REINFORCEMENT AT THE
 FOOT OF THE TUB SHALL BE AT 32 INCHES MAXIMUM AND THE
 TOP SHALL BE AT 38 INCHES MINIMUM ABOVE THE FINISH
 FLOOR. FHA FIGURE #4. THE SAME APPLIES TO THE
 REINFORCEMENT AT THE HEAD OF THE TUB.
 11)SHT. LS-0.2 - THE REINFORCEMENT FOR THE FOR THE
 SHOWER SIDES SHALL BE LOCATED 32 INCHES MAXIMUM TO THE
 BOTTOM AND THE WIDTH OF THE REINFORCEMENT SHALL BE A
 MINIMUM OF 6 INCHES WIDE. FHA FIGURE #5.
 12)SHT.LS-0.2 - FHA GENERAL NOTES - ACCESSIBLE UNITS
 NOTE 4 (D) REFERS TO A LAVATORY DETAIL THIS SHEET.
 THERE IS NO DETAIL SHOWING THE DISTANCE OF LAVATORY TO
 A WALL. CLARIFY.
 13)SHT.A2.1.1 - PLAN NOTES #1- STATES SEE SHT.G1.1 FOR
 GENERAL NOTES AND SYMBOLS. THERE IS NO SUCH SHEET IN
 THE PLANS. CLARIFY.
 14)ON THE ENLARGED PLANS FOR THE UNITS, SHOW THE
 REQUIRED CLEAR FLOOR SPACE FOR THE FIXTURES PER THE FHA
 IN THE ACCESSIBLE BATHROOMS AND THE KITCHEN. IN
 ADDITION, SHOW WHICH BATHROOM COMPLIES WITH THE FHA AS
 THE ADAPTABLE BATHROOM FOR THE UNITS WITH MORE THAN ONE
 BATHROOM.
 15)INDICATE THE LENGTH OF THE SHOWERS ON THE PLANS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 16)SHOW THE REQUIRED 30 INCH BY 48 INCH CLEAR FLOOR
 SPACE ADJACENT TO THE SHOWER IN THE ADAPTABLE UNITS.
 FHA GUIDELINES REQ. #7.
 17) SHT.P2.1.1 -IDENTIFY THE SPECIFIC ELECTRICAL AND
 MECHANICAL DRAWINGS WHERE THE ADDITIONAL INFORMATION
 FOR THE GENERATOR IS LOCATED. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 18)SHT.P2.1.1 SHOWS A 4" FIRE HUB DRAIN IN THE
 STAIRWELLS. 2010 FBC SEC. 1022.4 LIMITS PENETRATIONS IN
 THE EXIT ENCLOSURE TO ITEMS THAT SERVING THE EXIT
 ENCLOSURE.
 19)SUBMIT A KEYNOTE LEGEND FOR THE SQUARES, CIRCLES AND
 DIAMONDS WITH NUMBERS LOCATED WITHIN THE SYMBOLS.
 20)THE ROOM IN WHICH THE POOL HEATERS ARE LOCATED SHALL
 COMPLY WITH THE 2010 FUEL GAS CODE SEC. 305.3.2.
 21)SUBMIT A WATER RISER FOR UNITS 303 & 503. ALTHOUGH
 THESE UNITS ARE A MIRROR OF UNITS 304 & 504, A WATER
 RISER IS REQUIRED PER THE CITY OF WPB ADMIN. AMEND. TO
 2010 FBC SEC. 107.3.5.1.3.
 22)A RELIEF VENT IS REQUIRED ON THE SOIL AND WASTE
 STACKS THAT ARE MORE THAN 10 BRANCH INTERVALS. THE
 RELIEF VENT SHALL BE PROVIDED AT EACH TENTH INTERVAL
 INSTALLED, BEGINNING WITH THE TOP FLOOR PER 2010 FPC
 SEC. 914.1, 914.2.
 23)SHT. P4.1.1. - SUBMIT THE LENGTH OF THE BRANCH VENT
 CONNECTING STACKS #2, #3, & #4 TO STACK # 46. BRANCH
 VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL BE
 INCREASED BY ONE NOMINAL SIZE FOR THE ENTIRE DEVELOPED
 LENGTH OF THE VENT PIPE PER 2010 FPC SEC. 916.4.1.THE
 SAME APPLIES TO THE BRANCH VENT CONNECTING STACKS #13.
 14, 15 & 16 AND STACKS #47, 48, 49, 50. IN ADDITION,
 ALSO LOOK AT SHT. P4.1.5.
 24)SHT. P4.1.1.1 - STACKS #29 & 13 - INDICATE ON THE
 RISER WHERE THE STACKS PENETRATES THE UPPER FLOORS.WPB
 ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1.
 25) SHT.P4.1.3. - RISERS 24, 25, 26 - THE NOTE STATES
 SEE SHT. P4.1.3 FOR CONTINUATION MATCH POINT D. THERE
 IS NO MATCH POINT "D" ON P4.1.3. CLARIFY.
 26)SHT.P4.1.3 ? STACK #48 AT THE 6TH FLOOR LEVEL- SHOWS
 A RISER COMING OFF THE HORIZONTAL DRAIN AND CONNECTING
 RIGHT BACK INTO THE STACK VENT. CLARIFY. THIS AREA WAS
 NOTED WITH A MARKUP.
 27)SHT.P4.1.5 - DOMESTIC WATER BOOSTER DETAIL SHOWS A 6
 INCH SUPPLY AND A 6 INCH DISCHARGE LINE AND THE WATER
 RISER SHOWS 5 INCH SUPPLY AND DISCHARGE. CLARIFY.
 28)SUBMIT INFORMATION AS TO HOW THE CONTROL OF THERMAL
 EXPANSION WILL BE ACCOMPLISHED IN ACCORDANCE WITH 2010
 FPC SEC.607.3, 607.3.2.
 29)SHT. P4.1.7 SHOWS A 4 INCH ROOF DRAIN COLLECTING
 1608 SQUARE FEET OF ROOF AREA. THE MAXIMUM SQUARE
 FOOTAGE THAT A HORIZONTAL 4 STORM DRAIN CAN CARRY AT
 1/8 INCH PER FOOT AT A 5 INCH RAINFALL RATE IS 1504
 SQUARE FEET PER TABLE 1106.3 OF 2010 FPC.
 30)SHT.P4.1.7. SHOWS A 5 INCH ROOF DRAIN COLLECTING
 2840 SQUARE FEET OF ROOF AREA. THE MAXIMUM SQUARE
 FOOTAGE THAT A HORIZONTAL 5" STORM DRAIN CAN CARRY AT
 1/8? PER FOOT AT A 5 INCH RAINFALL RATE IS 2672 SQUARE
 FEET.
 31)SHT. P4.1.9 - GAS RISER - SUPPLY THE LOW PRESSURE
 GAS INFORMATION FOR THE GENERATOR. THE RISER DIAGRAM
 SHOWS A PRESSURE REGULATOR AT THE GENERATOR.
 32)SHT.P4.1.9 - THE TOTAL SYSTEM LOAD INFO IS
 CONFUSING; THE GENERATOR LOAD IS INCLUDED IN THE TOTAL
 LOAD BUT THE PIPING IS SHOWN AS METALLIC PIPE BUT THE
 GENERATOR IS BEING SUPPLIED BY PE PIPE. CLARIFY.
 33)SHT. P4.1.10 - THE PLAN SHOWS THE T & P LINES
 CONNECTING INTO THE SAME LINE AS THE PAN DRAINS. THESE
 TWO SYSTEMS SHALL BE 2 INDEPENDENT AND SEPARATE SYSTEMS
 PER THE 2010 FPC SEC. 504.6(4).
 34)THE DISCHARGE PIPE FOR A TEMPERATURE & PRESSURE
 RELIEF VALVE SHALL COMPLY WITH 2010 FPC SEC. 504.6,
 1-13.
 35)SHT. P5.1.2 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE OIL GUARD PUMP SYSTEM.
 36)A WATER HAMMER ARRESTOR SHALL BE INSTALLED ON THE
 FLUSHING RING FOR THE TRASH CHUTE PER 2010 FPC SEC.
 604.9.
  