Plan Review Notes
Plan Review Notes For Permit 15031312
Permit Number 15031312
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-05 17:13:32 
 1ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15031312
 5/29/15- 6/5/15
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH ASHRAE OR ACCA MANUAL N- SECTION
 503.2.1 FBC-10 ENERGY CONSERVATION
  
 2) PROVIDE ENERGY CALCULATIONS: SUBMIT TWO COPIES OF
 EITHER FORM 502 OR 506- 2010. SEE SECTION 103.2.1 AND
 TABLE 103.2.1 FBC-10 ENERGY CONSERVATION
  
 3) SUBMIT THE FOLLOWING LIST OF MANUFACTURER'S PRODUCT
 DATA SHEETS REQUIRED FOR A COMPLETE MECHANICAL REVIEW.
 PLEASE NOTE THAT ALL EQUIPMENT AND SYSTEM COMPONENTS
 INSTALLED IN BUILDING AREAS SUBJECT TO WIND PRESSURES
 AND WIND BORNE DEBRIS WILL REQUIRE ADDITIONAL SUBMITTAL
 OF VALID FLORIDA PRODUCT APPROVALS AND/OR MIAMI DADE
 NOTICES OF ACCEPTANCE:
 A) FIRE DAMPERS
 B) FIRE/SMOKE DAMPERS
 C) CO2 SENSORS
 D) PACKAGED FRESH AIR AC UNITS
 E) SPLIT SYSTEM AC UNITS (DUCTED AND DUCTLESS PER THE
 SCHEDULES: SHEETS M4-00, M4-01).
 F) RTU-1
 G) VENTILATION FANS AS LISTED IN THE SCHEDULE-
 (M4.01A).
 H) EXHAUST AND AIR INTAKE LOUVERS AND GRILLS
 I) AC ROOF STANDS AND CURBS
 J) POOL AND SPA HEATERS
 K) DRYER AND DRYER VENTS
 NOTE: ALL SUBMITTALS SHALL BE REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL OF RECORD.
  
 4) AS THE PLAN INDICATES EXTENSIVE VERTICAL REFRIGERANT
 PIPING RUNS FROM THE EQUIPMENT ON THE LOW FLOORS TO
 CONDENSING UNITS ON THE ROOF (SUCH AS THE FAN COIL
 UNITS ON THE 3RD AND 5TH FLOORS) DOCUMENTATION OF
 MAXIMUM PIPING RUNS PER EACH SYSTEM MANUFACTURER SHALL
 BE PROVIDED. PLEASE MODIFY THE SCHEDULES TO SHOW THE
 DATA OR PROVIDE A SEPARATE PIPING TABLE IN THE PLANS
 INDICATING THE TYPE OF PIPING, LENGTH OF THE PIPING
 RUN, AND THE TYPE AND AMOUNT OF REFRIGERANT IN EACH
 SYSTEM- TABLE 1103.1 FBC-10 MECH. ADDITIONALLY, THROUGH
 PENETRATION FIRE STOPPING DETAILS ARE REQUIRED FOR
 PIPES RUN THROUGH RATED WALLS AND CEILINGS- PLEASE NOTE
 SHAFT ENCLOSURES MAY BE REQUIRED SECTION 1107.2.2
 FBC-10 MECH.
  
 5) PROVIDE VENTILATION TABLES INDICATING THE REQUIRED
 MINIMUM VENTILATION RATES (O/A AND EXHAUST) FOR ALL
 OCCUPIED ROOMS AND SPACES, AND SYSTEM SIZING
 CALCULATIONS FOR ALL FANS LISTED IN THE SCHEDULE ON
 M4.01- TABLE 403.3 FBC-10 MECHANICAL, AND ASHRAE 62.1.
 CORRELATE THE REQUIRED O/A CFM'S WITH THE CFM AMOUNTS
 SHOWN ON THE AC EQUIPMENT SCHEDULES. PROVIDE
 CALCULATIONS INDICATING HOW O/A IS BEING ADEQUATELY
 PROVIDED FOR THE ELEVATOR CARS, ELEVATOR LOBBIES AND
 VESTIBULES THAT ARE BEING SUPPLIED BY DUCTLESS
 MINI-SPLIT SYSTEMS.
  
 6) PROVIDE SIZING CALCULATIONS FOR ALL COMPONENTS OF
 THE SMOKE CONTROL AND EXHAUST SYSTEMS INCLUDING
 STAIRWAY AND ELEVATOR PRESSURIZATION FANS, THE
 ROOF-MOUNTED SMOKE EXHAUST FAN SEF-1, AND THE ELEVATOR
 HOISTWAY RELIEF LOUVERED OPENINGS (SEE COMMENT 8 FOR
 FURTHER SMOKE CONTROL REQUIREMENTS). CALCULATIONS ARE
 ALSO REQUIRED FOR OTHER FANS LISTED IN THE SCHEDULE NOT
 RELATED TO THE SMOKE CONTROL.
  
 7) REFERENCE SHEET M4.07 AND M2.3.1- M2.6.1: THE SMOKE
 CONTROL SYSTEM DESCRIPTION AND SEQUENCE OF OPERATIONS
 OUTLINE ON M4.07 MAKES NO REFERENCES TO ZONE SYSTEMS
 FOR THE APARTMENTS AND CORRIDORS ON THE 3RD AND 5TH
 FLOORS, NOR ARE ANY SYSTEMS SHOWN FOR SMOKE CONTROL AND
 STAIRWAY/ELEVATOR PRESSURIZATIONS ON THESE FLOORS.
 PLEASE CLARIFY WHY STAIRWELL #3 IS INCLUDED IN THE
 PRESSURIZATION FAN FLOW DIAGRAM ON M4.07.
  
 8) M4.07 SEQUENCE OF OPERATIONS: PLEASE CLARIFY NOTE 2
 UNDER ZONES 2-14. WILL THE TYPICAL O/A FSD?S ON THE
 FLOOR OF THE SMOKE ZONE REMAIN OPEN OR CLOSED AT THE
 CORRIDOR, AND AT THE AC CLOSETS
  
 9) THE DESIGN PROFESSIONAL OF RECORD SHALL SUBMIT A
 RATIONAL ANALYSIS FOR THE PROPOSED SMOKE CONTROL SYSTEM
 IN COMPLIANCE WITH 513 FBC-10 MECHANICAL. PLEASE REVIEW
 AND COMPLY THE FOLLOWING SECTIONS:
  
 513.2 GENERAL DESIGN REQUIREMENTS.
 BUILDINGS, STRUCTURES, OR PARTS THEREOF REQUIRED BY
 THIS CODE TO HAVE A SMOKE CONTROL SYSTEM OR SYSTEMS
 SHALL HAVE SUCH SYSTEMS DESIGNED IN ACCORDANCE WITH THE
 APPLICABLE REQUIREMENTS OF SECTION 909 OF THE FLORIDA
 BUILDING CODE, BUILDING AND THE GENERALLY ACCEPTED AND
 WELL-ESTABLISHED PRINCIPLES OF ENGINEERING RELEVANT TO
 THE DESIGN. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE
 SUFFICIENT INFORMATION AND DETAIL TO DESCRIBE
 ADEQUATELY THE ELEMENTS OF THE DESIGN NECESSARY FOR THE
 PROPER IMPLEMENTATION OF THE SMOKE CONTROL SYSTEMS.
 THESE DOCUMENTS SHALL BE ACCOMPANIED WITH SUFFICIENT
 INFORMATION AND ANALYSIS TO DEMONSTRATE COMPLIANCE WITH
 THESE PROVISIONS
  
 513.3 SPECIAL INSPECTION AND TEST REQUIREMENTS.
 IN ADDITION TO THE ORDINARY INSPECTION AND TEST
 REQUIREMENTS WHICH BUILDINGS, STRUCTURES AND PARTS
 THEREOF ARE REQUIRED TO UNDERGO, SMOKE CONTROL SYSTEMS
 SUBJECT TO THE PROVISIONS OF SECTION 909 OF THE FLORIDA
 BUILDING CODE, BUILDING SHALL UNDERGO SPECIAL
 INSPECTIONS AND TESTS SUFFICIENT TO VERIFY THE PROPER
 COMMISSIONING OF THE SMOKE CONTROL DESIGN IN ITS FINAL
 INSTALLED CONDITION. THE DESIGN SUBMISSION ACCOMPANYING
 THE CONSTRUCTION DOCUMENTS SHALL CLEARLY DETAIL
 PROCEDURES AND METHODS TO BE USED AND THE ITEMS SUBJECT
 TO SUCH INSPECTIONS AND TESTS. SUCH COMMISSIONING SHALL
 BE IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING
 PRACTICE AND, WHERE POSSIBLE, BASED ON PUBLISHED
 STANDARDS FOR THE PARTICULAR TESTING INVOLVED. THE
 SPECIAL INSPECTIONS AND TESTS REQUIRED BY THIS SECTION
 SHALL BE CONDUCTED UNDER THE SAME TERMS AS FOUND IN
 SECTION 909.18 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 513.4 ANALYSIS.
 A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 513.4.1 THROUGH 513.4.6.
 513.4.1 STACK EFFECT.
 THE SYSTEM SHALL BE DESIGNED SUCH THAT THE MAXIMUM
 PROBABLE NORMAL OR REVERSE STACK EFFECTS WILL NOT
 ADVERSELY INTERFERE WITH THE SYSTEM?S CAPABILITIES. IN
 DETERMINING THE MAXIMUM PROBABLE STACK EFFECTS,
 ALTITUDE, ELEVATION, WEATHER HISTORY AND INTERIOR
 TEMPERATURES SHALL BE USED.
 513.4.2 TEMPERATURE EFFECT OF FIRE.
 BUOYANCY AND EXPANSION CAUSED BY THE DESIGN FIRE IN
 ACCORDANCE WITH SECTION 513.9 SHALL BE ANALYZED. THE
 SYSTEM SHALL BE DESIGNED SUCH THAT THESE EFFECTS DO NOT
 ADVERSELY INTERFERE WITH ITS CAPABILITIES.
 513.4.3 WIND EFFECT.
 THE DESIGN SHALL CONSIDER THE ADVERSE EFFECTS OF WIND.
 SUCH CONSIDERATION SHALL BE CONSISTENT WITH THE
 WIND-LOADING PROVISIONS OF THE FLORIDA BUILDING CODE,
 BUILDING.
 513.4.4 HVAC SYSTEMS.
 THE DESIGN SHALL CONSIDER THE EFFECTS OF THE HEATING,
 VENTILATING AND AIR-CONDITIONING (HVAC) SYSTEMS ON BOTH
 SMOKE AND FIRE TRANSPORT. THE ANALYSIS SHALL INCLUDE
 ALL PERMUTATIONS OF SYSTEMS? STATUS. THE DESIGN SHALL
 CONSIDER THE EFFECTS OF FIRE ON THE HVAC SYSTEMS.
 513.4.5 CLIMATE.
 THE DESIGN SHALL CONSIDER THE EFFECTS OF LOW
 TEMPERATURES ON SYSTEMS, PROPERTY AND OCCUPANTS. AIR
 INLETS AND EXHAUSTS SHALL BE LOCATED SO AS TO PREVENT
 SNOW OR ICE BLOCKAGE.
 513.4.6 DURATION OF OPERATION.
 ALL PORTIONS OF ACTIVE OR PASSIVE SMOKE CONTROL SYSTEMS
 SHALL BE CAPABLE OF CONTINUED OPERATION AFTER DETECTION
 OF THE FIRE EVENT FOR A PERIOD OF NOT LESS THAN EITHER
 20 MINUTES OR 1.5 TIMES THE CALCULATED EGRESS TIME,
 WHICHEVER IS LESS.
  
 9A) THE DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE AND
 DOCUMENTATION VERIFYING COMPLIANCE WITH SECTION 513.6.1
 MINIMUM PRESSURE DIFFERENCE ACROSS SMOKE BARRIERS, AND
 513.6.2 MAXIMUM PRESSURE DIFFERENCE ACROSS A SMOKE
 BARRIER BY REQUIRED DOOR-OPENING OR CLOSING FORCES.
  
 9B) THE DESIGN PROFESSIONAL SHALL REVIEW AND APPROVE
 ALL EQUIPMENT AND COMPONENTS OF THE SMOKE CONTROL
 SYSTEM INCLUDING FANS, DUCTS, AUTOMATIC FIRE AND SMOKE
 DAMPERS AND BALANCING DAMPERS PER SECTION 513.10 FBC-10
 MECHANICAL INCLUSIVE OF ALL SUB-SECTIONS.
  
 9C) THE DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE OF
 COMPLIANCE WITH SECTION 513.11 FOR TWO SOURCES OF POWER
 FOR THE SYSTEM INCLUDING A SECONDARY MEANS BY AN
 APPROVED STANDBY SOURCE, AND MAXIMUM AUTO TRANSFER TIME
 OF 60 SECONDS TO FULL STANDBY POWER FROM PRIMARY
 FAILURE TIME.
  
 10) PROVIDE EQUIPMENT SCHEDULES FOR THE FIRE AND
 FIRE/SMOKE DAMPERS INCLUDING MAKES AND MODELS, UL
 LISTINGS, FIRE-RESISTANCE HOURLY RATINGS, AND LIST
 THEIR PROPOSED INSTALLATION LOCATIONS IN THE BUILDING,
 AND HOW THEY WILL BE ACTUATE- BY FUSIBLE LINK OR
 CONNECTION TO THE SMOKE CONTROL SYSTEM ETC.
  
 11) PROVIDE TYPICAL INSTALLATION DETAILS FOR THE
 DAMPERS INCLUDING ACCESS PANEL LOCATIONS.
  
 12) PROVIDE UL TESTED AND APPROVED THROUGH-PENETRATION
 FIRE STOPPING ASSEMBLIES FOR THE REFRIGERANT PIPING,
 AND AC DUCTS PENETRATING THE VARIOUS RATED WALLS AND
 FLOOR CEILING ASSEMBLIES.
  
 13) SHEET M2-1.1: THE OUTSIDE AIR (O/A) INTAKE INLET
 FOR AC-F IN THE GROUND FLOOR GARAGE/STORAGE WALL IS
 WITHIN THE 10 FT. ALLOWABLE HORIZONTAL DISTANCE TO THE
 DRIVE AREA: PLEASE CORRECT PER SECTION 401.4 FBC-10
 MECH.
  
 14) M2.1.1- M2.6.1: GROUND FLOOR TO 6TH FLOOR GARAGES:
 PROVIDE A SEQUENCE OF OPERATION DIAGRAM FOR THE CO
 ACTUATED EXHAUST SYSTEMS. PROVIDE INSTALLATION DETAILS
 FOR THE SENSORS INCLUDING MOUNTING HEIGHT AFF, AND
 MAXIMUM SPACING. SUBMIT MANUFACTURER?S PRODUCT DATA
 SHEETS REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL
 OF RECORD- SEE SECTIONS 404.1 AND 404.2 FBC-10 MECH.
 PLEASE NOTE THAT CONTINUOUS VENTILATION IS REQUIRED
 UNLESS THE FANS WILL OPERATE AUTOMATICALLY UPON
 DETECTION OF A CONCENTRATION OF CARBON MONOXIDE OF 25
 PARTS PER MILLION.
  
 15) M2.1.1- M2.6.1- POSITIVE PRESSURE AND MINIMUM O/A
 VENTILATION MUST BE MAINTAINED FOR THE VARIOUS ELEVATOR
 LOBBIES, VESTIBULES, ETC. THAT ARE CONNECTING AT THE
 CENTER OF THE PARKING GARAGES PER SECTION 404.3. HOW
 WILL THIS BE ACCOMPLISHED? THE CURRENT PLAN DOES NOT
 INDICATE ANY O/A DUCTS BRINGING FRESH AIR INTO THESE
 SPACES.
  
 16) M2.1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY AND RETURN AIR SYSTEMS OF AC-D & AC-E (FITNESS
 CENTER)- SECTION 606.2.2. PLEASE NOTE THAT ALTHOUGH
 AREA SMOKE DETECTORS ARE SHOWN IN THE CENTER ON
 FA2.1.1, THERE ARE NO NOTES ON FA1.00 PERTAINING TO FAN
 SHUT DOWN OF THE UNITS.
  
 17) M2.1.1: RETURN AIR TRANSFERS FROM THE CONFERENCE
 AND WORK ROOMS INTO THE CORRIDORS ARE PROHIBITED PER
 SECTION 601.2. PROVIDE DUCTED RETURNS.
  
 18) M2.1.1: INDICATE THE CLEARANCE DISTANCES FOR THE
 GENERATOR EXHAUST OUTLET AND EF-1-4 TO THE SUPPLY FAN
 INLET SERVING THE SWITCHGEAR ROOM, TO THE PUMP ROOM AIR
 INLET OPENINGS, AND TO THE PUBLIC WALKWAY.
  
 19) M2.3.1 & M2.5.1: IN REFERENCE TO THE NOTE REGARDING
 THE 6"X4" DUCT PENETRATING THE RATED CORRIDOR, PROVIDE
 EVIDENCE THAT THE MATERIAL USED TO FILL THE ANNULAR
 SPACE AROUND THE DUCT PENETRATION MEETS THE ASTM E 119
 OR UL 263 FOR PREVENTION OF PASSAGE OF FLAME AND HOT
 GASES PER SECTION 713.3.1 FBC-10 BUILDING.
  
 20) M2.6.1: A) CLARIFY IF THE COMBUSTION AIR
 CALCULATIONS INCLUDE BOTH THE SPA AND POOL HEATERS, AND
 SUBMIT MANUFACTURER?S SPECIFICATIONS FOR EACH UNIT, THE
 INDUCTION FAN, AND VENT PIPING. B) PROVIDE ENLARGED
 FRONT AND PLAN VIEW DRAWINGS OF THE EQUIPMENT ROOM
 INDICATING CLEARANCE DISTANCES AROUND THE EQUIPMENT AND
 ASSOCIATED POOL AND GAS PIPING, CONTROLS ETC. FOR
 SERVICE ACCESS. C) PROVIDE A VENTING DIAGRAM PER
 MANUFACTURER?S RECOMMENDATIONS. THE DIAGRAM SHALL
 INDICATE THE TYPE AND SIZE OF VENT PIPING, LENGTH OF
 CONNECTORS, HEIGHT OF THE RISER, TOTAL RISE AND RUN OF
 THE FLUE, AND METHOD OF HANGING AND SUPPORT OF THE
 PIPING.- SEE SECTION 503.6, 504 FBC-10 FUEL. D) PROVIDE
 A FIRE DAMPER AND THROUGH PENETRATION FIRE STOPPING FOR
 THE VENT PIPE PENETRATING THE FIRE-RATED WALL. PLEASE
 NOTE ALL SUBMITTALS SHALL BE REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL OF RECORD.
  
 21) M2.6.1) A VESTIBULE PROVIDING A TWO DOORWAY
 SEPARATION IS REQUIRED FOR THE CONNECTION OF THE POOL
 AND SPA HEATER ROOM TO THE ADJACENT GARAGE- SECTION
 305.3.2 FBC-10 FUEL GAS. CORRECT THE PLANS OR PROVIDE
 DOCUMENTATION VERIFYING THE HEATERS HAVE IGNITION
 SOURCES ELEVATED HIGHER THAN18 INCHES ABOVE THE FLOOR-
 SECTION 305.3.
  
 22) M2.6.1: THE LOCATION OF THE COMBUSTION AIR INTAKES
 ADJACENT TO GARAGE PARKING SPACES IS NOT PERMITTED PER
 SECTION 304.12 FBC-10 FUEL GAS. PLEASE PROVIDE
 COMBUSTION AIR FROM THE OUTDOORS.
  
 23) M2.4.1 & M2.6.1: AUTOMATIC SHUT OFF DAMPERS ARE
 REQUIRED FOR THE O/A INTAKES FOR FCU-1 AND FCU-2 PER
 SECTION 503.2.4.4 FBC-10 ENERGY CONSERVATION.
  
 24) M2.7.1: CLARIFY THE PURPOSE OF THE INLINE CORROSIVE
 RESISTANT FAN IN THE CORRIDOR CLOSET AND HOW IT WILL BE
 ACTIVATED. SUBMIT REVIEWED AND APPROVED SPECIFICATIONS,
 AND PROVIDE A UL APPROVED THROUGH-PENETRATION FIRE
 STOPPING DETAIL AND DETAILS FOR HANGING AND SUPPORTING
 THE EXHAUST DUCT.
  
 25) ALL RESIDENTIAL UNITS 3RD 5TH, 7TH, & 8TH- 20TH: A)
 PROVIDE INSTALLATION DETAILS FOR THE AIR HANDLERS IN
 THE SHOWING REQUIRED CLEARANCES INSIDE THE CLOSET PER
 SECTION 603.1.3, AND PRIMARY AND SECONDARY CONDENSATE
 DISPOSAL DETAILS- SECTION 307.2.1 & 307.2.3 FBC-10
 MECH., AND CONNECTION OF THE SUPPLY AND RETURN PLENUMS.
 B) PROVIDE A DETAIL FOR SUPPORT OF THE REFRIGERANT
 PIPING IN THE CLOSETS AND INDICATE THE TYPE AND
 THICKNESS OF THE PIPING INSULATION- PLEASE NOTE THE
 PIPING INSULATION SHALL BE PLENUM-RATED AND APPROVED BY
 THE DESIGN PROFESSIONAL PER SECTION 602.2.1. C)
 REFERENCE FIRESTOPPING DETAIL PER PREVIOUS COMMENT #
 12. B) IN REFERENCE TO NOTE #5 SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE DRYER REVIEWED AND APPROVED.
  
 26) PROVIDE AN EQUIPMENT SCHEDULE FOR ALL THE VARIOUS
 EXTERIOR EXHAUST AND AIR INTAKE LOUVERS AND GRILLS.
 LIST THE MAKES AND MODELS, TYPES AND SIZES, AND INSTALL
 LOCATIONS.
  
 27) MECHANICAL ROOF: PROVIDE WIND LOAD ENGINEERED
 DETAILS FOR TIE-DOWN OF THE ALL THE EQUIPMENT AND
 COMPONENTS INDICATED ON THE PLAN: CONDENSERS, AND
 CONDENSER RACKS, PACKAGE UNITS AND CURBS, SUPPLY AND
 EXHAUST FANS AND CURBS, REFRIGERATION PIPING RACKS AND
 STANDS ETC. INCLUDE SECTION CUTS SHOWING ATTACHMENT
 DETAILS, AND REQUIRED ROOF CLEARANCES FOR THE RACKS,
 AND CURB HEIGHTS.
  
 28) INDICATE HOW THE REFRIGERATION PIPING AND PIPING
 INSULATIONS WILL BE PROTECTED FROM WEATHER AND UV
 DAMAGE.
  
  
 CHRISTOPHER COLE