2015-03-31 14:32:03333 FERN STREET
 PERMIT #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
  
 SHEET C-09: PER NFPA 24 SECTION 6.2.1, BACKFLOW
 PREVENTER CONTROL VALVES SHALL BE INSTALLED IN A
 FIRE-RATED ROOM ACCESSIBLE FROM THE EXTERIOR.
  
 SHEET LS-0.1: DEAD-END CORRIDORS IN STORAGE AND
 APARTMENT OCCUPANCIES SHALL NOT EXCEED 20 FEET PER
 TABLE 42.2.5 AND SECTION 30.2.5.4.2 RESPECTIVELY.
  
 SHEET LS-1.0: DEAD-ENDS EXCEED 20 FEET OF TRAVEL IN
 OWNERS' STORAGE #133.
  
 SHEET LS-3.0: CORRIDOR HAS A DEAD-END MEASURING 40
 FEET. NEW APARTMENT DEAD-END CORRIDORS ARE LIMITED TO
 20 FEET PER NFPA 101 SECTION 30.2.5.4.2.
  
 SHEET LS-7.0: POOL CORRIDOR #706 CREATES A DEAD-END
 EXCEEDING 20 FEET IN LENGTH.
  
 SHEET LS-7.0: ALL THREE SECONDARY EXITS FROM COMMON
 ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT THE EXIT
 ACCESS DOOR LEADING TO THE POOL DECK.
  
 SHEET A2.1.1: EXIT ACCESS CORRIDOR #115 APPEARS TO
 ACTUALLY BE AN EXIT PASSAGEWAY.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  