Plan Review Notes
Plan Review Notes For Permit 15031312
Permit Number 15031312
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-28 16:34:56THE ELECTRICAL REVIEW FAILED AS INDICATED ON THE
 ATTACHED DOCUMENT. A COPY OF MY NOTES HAS BEEN EMAILED
 TO DESIGN PROFESSIONAL AS WELL.
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE
 REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH
 RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN
 CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE
 DIGITAL PLANS.
  
 PAGE E1.0.0 LEGEND & NOTES
 1. LIGHTING FIXTURE NOTES: CORRECT NOTE 1 TO INDICATE
 THE PROPER CODE SECTION ADDRESSING LUMINAIRE SUPPORT.
 2. GENERAL NOTES: CORRECT NOTE 10 TO COMPLY WITH
 CURRENT FBC REQUIREMENTS FOR FIRE SEALING AS NOTED.
 3. OUTDOOR & LANDSCAPE NOTES: CORRECT NOTE 4 TO INCLUDE
 THE REQUIREMENT OF NEC 406.8 (B)
 4. A NOTE REQUIRING COMPLIANCE WITH NEC 406.11
 TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS. IN ALL
 AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15 AND
 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER RESISTANT
 RECEPTACLES.
 5. YOU WILL NOTICE THAT ON EVERY FLOOR I HAVE MADE A
 NOTATION AS TO THE REQUIRED SERVICE OUTLET FOR THE
 INDIVIDUAL UNIT A/C EQUIPMENT IN A CLOSET IN THE COMMON
 CORRIDOR. AS A MATTER OF MY REVIEW, I HAVE MEASURED THE
 DISTANCES OF THE OUTLETS IN THE CORRIDORS AND THEY DO
 COMPLY WITH THIS REQUIREMENT BUT WILL THE BLDG. ALLOW
 THE INDIVIDUAL UNIT OWNERS TO USE THESE OUTLETS FOR
 THEIR PERSONAL USE? IF SO, A NOTE ADDRESSING THIS SHALL
 BE TO THE DRAWINGS, OTHERWISE AN ACCESSIBLE OUTLET
 POWERED FROM THE UNIT?S ELECTRICAL SERVICE SHALL BE
 INSTALLED INSIDE THE RESPECTIVE CLOSETS FOR THIS
 PURPOSE.
 6. FOR COMPLIANCE W/THE 2010 FBC-ENERGY CONSERVATION
 CODE, THERE ARE LIGHTING REQUIREMENTS THAT ARE NOT
 ADDRESSED ON THE PLANS. SUCH ARE THE GASKET REQUIREMENT
 FOR RECESSED LIGHTING, THE EFFICIENT LIGHTING
 REQUIREMENT, ETC.
  
 PAGE E2.1.1 OVERALL GROUND FLOOR PLAN
 1. IDENTIFY THE EXIT AND EXIT LIGHT IN THE GENERATOR
 ROOM
 2. MISSING THE EXIT LIGHT IN THE DOMESTIC PUMP ROOM.
 3. MISSING EXIT LIGHT FOR FIRE CONTROL ROOM
 4. MISSING EXIT LIGHT FOR TRASH ROOM
 5. MISSING EXIT LIGHT FOR VESTIBULE 116 B
 6. MISSING EXIT FOR STAIR 5 & STAIR 1
 7. MISSING EXIT LIGHT OUTSIDE OF MAINTENANCE OFFICE
 8. MISSING EXIT LIGHTS IN WORKROOM CLOUD AREA.
  
 THIS PAGE IS CO CLUTTERED THAT I MAY HAVE MISSED
 ADDITIONAL EXIT LIGHT REQUIREMENTS. PLEASE GO OVER THE
 DRAWING IN LAYERS TO SIMPLIFY EXIT LIGHT PLACEMENT.
  
 PAGE E2.2.1 OVERALL SECOND FLOOR PLAN
 1. INSTALL AN EXIT LIGHT AS MARKED TO ANNOUNCE STAIR #4
 FROM PARKING AREA.
  
 PAGE E2.3.1 OVERALL 3RD FLOOR & 5TH FLOOR PLAN
 1. BIKE STORAGE ROOM 304 MISSING O/S SENSOR (EXIT IS
 POORLY IDENTIFIED)
  
 PAGE E2.4.1 OVERALL 4TH FLOOR PLAN
 1. THE FOLLOWING ROOMS ARE MISSING THE REQUIRED O/S
 404, 405, 407, 413
  
 PAGE E2.5.1 OVERALL 5TH FLOOR PLAN
 1. BIKE STG. ROOM 504 IS MISSING THE O/S
  
 PAGE E2.6.1 OVERALL 6TH FLOOR PLAN
 1. THE FOLLOWING ROOMS ARE MISSING THE REQUIRED O/S:
 603, 604, 605, 607, 608, 609, 612, & 613
 2. FCU-2 IS MISSING THE REQUIRED LIGHTING PER NEC
 110.26(D)
 3. POOL EQUIPMENT ROOM SHALL INCLUDE THE EQUIPMENT
 BEING INSTALLED TO VERIFY PROPER CLEARANCES.
 4. NEC 680.22 (B) GFCI PROTECTIONS. OUTLETS SUPPLYING
 POOL PUMP MOTORS 15 OR 20 AMPERES, 125 VOLT OR 240
 VOLT, SINGLE PHASE, WHETHER BY RECEPTACLE OR DIRECT
 CONNECTION, SHALL BE PROVIDED WITH GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. IF THE
 POOL HEATERS ARE TO BE STAND-ALONE, MEANING THAT THEY
 DO NOT DEPEND ON THE POOL CIRCULATING PUMPS FOR WATER
 CIRCULATION, THEY TOO SHALL BE GFCI PROTECTED.
  
 PAGE E2.7.1 OVERALL 7TH FLOOR PLAN
 1. PER NOTES, POOL IS TO BE ON SEPARATE PERMIT THUS NO
 NOTES ADDRESSING POOL.
  
 PAGE E2.8.1 OVERALL TYPICAL 8TH ? 20TH FLOOR PLAN
 1. RELOCATE EXITS SIGNS SO AS NOT TO CONFUSE
 PEDESTRIANS INTO WRONG DOORWAY.
  
 PAGE E3.1.1, UNITS 301/501
 1. 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS OCCURS THROUGH THE
 UNITS IN MULTIPLE LOCATIONS.
 3. NEC 210.52 (A)(2) WALL SPACE. REQUIRES AN OUTLET ON
 EVERY WALL GREATER THAN 2?. SEE CLOUDS ON THE LIVING
 ROOM AND FOYER AND CORRECT ACCORDINGLY.
 4. NEC 210.52 (C)(3) PENINSULAR COUNTERTOP SPACES.
 REQUIRES AT LEAST ONE RECEPTACLE AT EACH PENINSULA
 COUNTERTOP. THIS IS A COMMON ISSUE OCCURRING IN MOST
 ALL KITCHEN PENINSULAS, SEE CLOUDS.
 5. NEC 210.63 HVAC EQUIPMENT OUTLET. REQUIRES THAT
 THERE BE A SERVICE OUTLET WITHIN 25? OF THE EQUIPMENT
 BEING SERVICED. YOU WILL NOTICE THIS FOR MOST EVERY
 UNIT, SINCE THE HVAC EQUIPMENT IS IN THE CORRIDOR
 OUTSIDE THE UNIT. SEE MY NOTE 5 OF THE LEGEND & NOTES
 PAGE.
 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE
  
 PAGE E3.1.1, UNITS 302/502
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS OCCURS THROUGH THE
 UNITS IN MULTIPLE LOCATIONS
 2. 210.52(C)(1) WALL COUNTERTOP SPACES. A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP SPACE
 THAT IS 12 IN. OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 24 IN. MEASURED HORIZONTALLY FROM A RECEPTACLE
 OUTLET IN THAT SPACE.
 3. NEC 210.63 HVAC EQUIPMENT OUTLET. REQUIRES THAT
 THERE BE A SERVICE OUTLET WITHIN 25? OF THE EQUIPMENT
 BEING SERVICED. YOU WILL NOTICE THIS FOR MOST EVERY
 UNIT, SINCE THE HVAC EQUIPMENT IS IN THE CORRIDOR
 OUTSIDE THE UNIT. SEE MY NOTE 5 OF THE LEGEND & NOTES
 PAGE.
 4. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING
  
 PAGE E3.1.1A UNITS 301/501 & 302/502 PANEL SCHEDULES
 1. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 2. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 3. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.2.1, UNITS 303-503 & 304-504
 1. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE.
 2. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 3. NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY
 4. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 5. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 6. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.3.1, UNITS 305-505
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE CLOUDED AREA IN
 KITCHEN
 3. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE. SEE CLOUDED
 AREA AND CORRECT ACCORDINGLY.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.3.1, UNITS 306-506
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE CLOUDED AREAS
 LABELED IN FOYER, KITCHEN & BEDROOM
 2. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE. . SEE CLOUDED
 AREA AND CORRECT ACCORDINGLY.
 3. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 5. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 6. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 7. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.4.1, UNIT 1 (TYP. 8 - 20 FLR.)
 1. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 2. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN
 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY.
 3. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 4. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 5. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 6. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 7. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 8. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.5.1, TYPICAL UNIT 2
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN
 EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE
 IS TO REMAIN FIXED AND THE PENINSULA AFFORDS A PLACE
 FOR AN OUTLET TO SOLVE THE DISTANCE FROM AN EDGE.
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.6.1, UNIT 3, (TYP. FOR 7 ? 19 FLR.)
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN
 EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE
 IS TO REMAIN FIXED AND THE PENINSULA AFFORDS A PLACE
 FOR AN OUTLET TO SOLVE THE DISTANCE FROM AN EDGE.
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
 10. YOU MAY WANT TO CHECK YOUR CALCULATOR, SEE SMALL
 APPLIANCE LOAD ANALYSIS UNIT 3.
  
 PAGE E3.6.1, UNIT 3, (TYP. FOR 7 ? 19 FLR.)
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN
 EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE
 IS TO REMAIN FIXED AND THE PENINSULA AFFORDS A PLACE
 FOR AN OUTLET TO SOLVE THE DISTANCE FROM AN EDGE.
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. UNIT 3 OF PAGE E3.6.1 IS OF THE SAME SIZE, YET THE
 A/C LOAD ON ONE IS 5400VA AND THE OTHER HAS 8000VA
 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD.
  
 PAGE E3.7.1, UNIT 4
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN
 EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE
 IS TO REMAIN FIXED
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 6. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 7. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 8. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 9. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 10. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 11. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 12. YOU MUST BE USING THE SAME CALCULATOR, SEE SMALL
 APPLIANCE LOAD ANALYSIS UNIT 4.
  
 PAGE E3.8.1, UNITS 5
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE CLOUD MASTER BEDROOM
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 10. JUST HAPPEN TO NOTICE THE BATHROOM COUNTER
 EXTENDING INTO THE PATH OF THE DOOR
 11. SEE CLOUD IN MASTER BATH COUNTER 805.05
  
 PAGE E3.9.1, UNITS 6, 7, 8, 9, 10, 12
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE FOYER
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E3.9.1A, TYPICAL UNIT 7, 9
 1. ACCORDING TO THE PAGE HEADING, THESE UNITS ARE
 SUPPOSED TO BE MIRRORED OF EACH OTHER, YET THERE ARE
 TWO PANEL SCHEDULES EACH WITH ITS RESPECTIVE LOAD
 ANALYSIS; BOTH OF WHICH ARE DIFFERENT. CORRECT THE LOAD
 ANALYSIS AND PANEL SCHEDULES OR REMOVE THE MIRROR
 REFERENCE.
 2. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 3. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE FOYER
 4. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 8. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 9. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E3.10.1, TYPICAL UNIT 11
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE DEN & FOYER
 2. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE.
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 10. THE SMOKE DETECTOR IN THE DEN IS NOT REQUIRED AS
 THIS IS NOT CONSIDERED A SLEEPING AREA; IF IT TO
 REMAIN, IT SHALL BE RELOCATED TO COMPLY WITH NFPA
 SECTION 29.8.3.4(6) WHICH REQUIRES THAT THE SMOKE
 DETECTOR NOT BE WITHIN 36? OF A BATHROOM WITH A SHOWER
 OR TUB. RELOCATE THIS UNIT ACCORDINGLY.
  
 PAGE E3.11.1, UNIT 11A, 7TH FLR
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL.
 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 3. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 4. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 5. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 6. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 7. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 8. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
 9. JUST HAPPEN TO NOTICE THE BATHROOM COUNTER EXTENDING
 INTO THE PATH OF THE DOOR
  
 PAGE E3.12.1, UNIT 13
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE MASTER BEDROOM
 & BEDROOM 2.
 2. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE FOYER.
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS.
 4. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH
 BASIN. SEE MASTER BATH.
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 8. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 9. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E3.13.1, UNIT 14
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE MASTER BEDROOM.
 3. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE FOYER.
 4. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS.
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E3.14.1, UNIT 15
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE LIVING ROOM,
 DINING ROOM & BEDROOM 2.
 3. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR
 MORE IN WIDTH. SEE DINING ROOM & WALL ADJACENT TO
 ELECTRIC PANEL
 4. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS.
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED
 TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT
 ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO
 LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF
 THE NEC AND WAS NOT ABLE TO FIND THEM
 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY
 CIRCUIT AND LATER ADDING A WASHER LOAD
 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E15.1, UNIT 15A, 7TH FLR
 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL
 BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. SEE LIVING & DINING
 ROOMS.
 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS.
 4. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN
 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY. THOUGH I
 DON?T SEE THE TERRACE DELINEATION, ROOM 715.12
 INDICATES A TERRACE. NO CLOUD DUE TO UNCERTAINTY OF
 TERRACE.
 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND &
 NOTES
 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS
 IN SHALL HAVE THE REQUIRED LIGHTING. SEE BEDROOM 2
 CLOSET.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 8. I REVIEWED YOUR LOAD CALCULATIONS FOR COMPLIANCE AND
 NOT ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED
 TO LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION
 OF THE NEC AND WAS NOT ABLE TO FIND THEM
 9. YOU ARE COUNTING A LAUNDRY CIRCUIT AND LATER ADDING
 A WASHER LOAD
 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A
 SMALLER LOAD USING THE STANDARD METHOD
  
 PAGE E4.1.1 PANEL SCHEDULES
 1. INCLUDE THE RETAIL MAIN
  
 PAGE E5.1.1 POWER RISER
 1. YOUR NOTES ON PAGE E5.2.1 DESCRIBE THESE CONDUCTORS
 AS HAVING THHN INSULATION. CORRECT THAT TO COMPLY WITH
 THE REQUIREMENTS OF NEC 300.5 B, STATING THAT THE
 INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE CONSIDERED
 A WET LOCATION AND THUS THWN IS REQUIRED.
  
 PAGE E6.3.1 ENLARGED ROOMS
 1. NEC 110.26 A1 REQUIRES A MINIMUM OF 3? CLEAR WORKING
 SPACE IN FRONT OF ELECTRICAL EQUIPMENT; ACCORDING TO
 THE DRAWINGS THERE SEEMS TO BE ENCROACHMENT OF THIS
 SPACE IN THE ELECTRICAL ROOMS OF LEVELS 7, 9, 11, 14,
 16, & 18. CHECK AND REVISE AS NECESSARY.
  
 PAGE E7.1.1 LIGHT FIXTURE SCHEDULES
 1. I HAVE NOT SEEN ANYWHERE ON THE DRAWINGS A NOTE AS
 TO THE COMPLIANCE WITH THE 2010 FBC-ENERGY CONSERVATION
 CODE.
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
  
 FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT:
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 PH: (561) 805-6743
 EMAIL: [email protected]
  
 FIRE ALARM REVIEW UNDER SEPARATE COVER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.