2015-05-17 14:08:14 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15031312 |
| ADD: 333 FERN ST. |
| CONT: KAST CONSTRUCTION |
| CONTACT : |
| TEL: (561)689-2910 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: MAY 18 /2015 |
| ACTION: DENIED |
| |
| 1) NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN |
| PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY |
| REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE |
| PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE |
| TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| GREATER THAN $500,000. PER CITY OF WEST PALM BEACH |
| ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE |
| OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| |
| 2) THE PERMIT APPLIED VALUE IS STATED AS $28,665,000.00 |
| DOLLARS. THE CALCULATED VALUE IS $44,101,328.00 DOLLARS |
| IN VALUE. USING THE FLOOR AREA SUMMARY FOUND ON 022 |
| SP1.1. PLEASE PROVIDE THE SQUARE FOOTAGE PER FLOOR. |
| PLEASE BREAK OUT MIXED USE OCCUPANCIES PER FLOOR. FOR |
| THE PARKING GARAGE PLEASE PROVIDE AREA BY LEVEL. |
| |
| W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 3) PLEASE PROVIDE A SURVEY WITH THE PROPOSED OVERLAY OF |
| THE BUILDING TO VERIFY THE ACTUAL DISTANCE FROM |
| PROPERTY LINES. 2010 FBC-B TABLE 602. |
| 4) THE CURRENT SURVEY SUBMITTED INDICATES THIS PROPOSED |
| STRUCTURE WILL BE LOCATED ON LOTS 11-15 OF BLOCK 10. A |
| REPLAT WILL BE REQUIRED TO ELIMINATE THE BUILDING GOING |
| PAST PROPERTY LINES. TABLE 602. |
| |
| 5) NO ENERGY REPORT AND CALCULATIONS WERE SUBMITTED. |
| PLEASE PROVIDE CODE COMPLIANCE WITH THE 2010 FBC-ENERGY |
| 103.2.1 CODE DEMONSTRATION FORMS, TABLE 103.2.1. |
| |
| 6) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| 6A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING |
| AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 6B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| FORMS WERE SENT TO: : [email protected] AT |
| 05/09/2015 02:09 PM. |
| |
| 6C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 6D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 6E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| [email protected] |
| |
| 6F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| INSPECTORS. |
| |
| |
| 6G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 6H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| WALLS AND CEILINGS. |
| |
| 7) PAGE 024 LS-1.0, 032 A2.1.1 & 033 A2.1.2. |
| |
| 7A) THESE PLANS INDICATE 5 STAIRWELLS WITH STAIRS 4 & 5 |
| HAVING THE EXIT DISCHARGE DIRECTLY AT THE EXTERIOR OF |
| THE BUILDING. STAIR 1 EXITS THE VERTICAL ENCLOSURE |
| TRAVEL THROUGH THE ELEVATOR LOBBY, MAIN LOBBY AND |
| GALLERY BEFORE THE EXIT DISCHARGE IS ARRIVED AT. IN THE |
| ELEVATOR LOBBY THERE ARE (2) COLUMNS AND SOME WALL TYPE |
| THAT WOULD BLOCK THE VIEW OF THE MAIN ENTRANCE, MORE |
| INFORMATION IS REQUIRED HOW THIS WILL QUALIFY UNDER THE |
| EXCEPTIONS FOUND IN SECTION FBC-B 1027.1 IT APPEARS |
| EXCEPTION 1 WOULD BE TAKEN? |
| |
| 7B) THE OTHER STAIRWELL # 3 IT APPEARS IS ALSO TAKING |
| THE SAME EXCEPTION FOUND IN 2010 FBC-B 1027.1 EXCEPTION |
| # 1. THE 2007 FBC CODE COMMENTARY DOES IN PRINCIPLE |
| AGREE, THERE IS LANGUAGE DOES LEAVE ROOM FOR QUESTION. |
| THIS DOES NOT MEAN THE EXTERIOR EXIT DOOR MUST BE |
| DIRECTLY IN FRONT OF THE DOOR AT THE BOTTOM OF THE |
| STAIRWAY, BUT THE INTENT IS THAT IT SHOULD BE WITHIN |
| THE GENERAL RANGE OF VISION. IT SHOULD NOT BE REQUIRED |
| THAT A PERSON MUST TURN COMPLETELY AROUND OR GO AROUND |
| A CORNER TO BE ABLE TO SEE THE WAY OUT. |
| |
| 7C) STAIRWELL # 2 ROOM 139 IS SHOWN WITH A 2 HR. |
| ENCLOSURE DOOR 139 1 ? HOUR OPENING PROTECTIVE. THE |
| EXTENSION OF THE EXIT IS LABELED AS AN EXIT ACCESS |
| CORRIDOR # 115. PLEASE NOTE THIS IS AN EXIT PASSAGE WAY |
| AND NEEDS TO COMPLY WITH SECTION FBC-B 1023.6 |
| PENETRATIONS. THE MECHANICAL AND ELECTRICAL PLANS |
| INDICATE AN INTAKE AIR LOUVER AN FAN WITH 2160 CFM TO |
| PRESSURIZE THE EXIT PASSAGEWAY. NOTE NO ELECTRICAL RACE |
| WAYS, CONDUITS, ETC. FROM THE FPL VAULT OR FROM THE |
| SWITCHGEAR/ ELECTRICAL ROOM RUN THROUGH THIS EXIT |
| PASSAGEWAY. |
| |
| 7D) PLEASE NOTE THE EXIT PASSAGEWAY 115 THE TOP AND |
| BOTTOM SLOPED AREAS MEET THE DEFINITION OF GRADE WITH A |
| SLOPE OF 1:20 THE MIDDLE SECTION FROM LANDING MARKED AS |
| 12.75 FT. TO LANDING 12.08 FT. IS A DIFFERENCE OF 8 |
| INCHES X 20= 160 INCHES (13.3 FT. RAMP FBC-B 1010.2 |
| SLOPE) OF RUN REQUIRED NOT TO BE CONSIDERED A RAMP. |
| THIS SECTION WILL NEED TO COMPLY WITH 2010 FBC-B 1010.8 |
| HANDRAILS. |
| |
| 7E) THE PLANS INDICATE A SERIES OF LOUVERS AND WALL |
| OPENINGS, THE OPENINGS DO NOT SHOW ANY PROTECTION NOR |
| DOES THE LOUVERS WITH THE EXCEPTION OF LOUVER 17 SEE |
| SHEET A7.4. THE FBC-B TABLE 705.8 BASES THE AMOUNT OF |
| OPENINGS BASED ON THE SEPARATION DISTANCE. WHEN FACING |
| PUBLIC RIGHT OF WAYS STREETS OR ALLIES AN ASSUMED |
| PROPERTY LINE IS TAKEN FROM THE CENTER OF THE STREET OR |
| ALLEY WAY OR IN THIS CASE 7?-0? FROM THE |
| PROPERTY LINE, ALSO SEE FOOTNOTE (A) THE VALUES |
| INDICATED ARE THE PERCENTAGE OF THE AREA OF THE |
| EXTERIOR WALL, PER STORY. |
| |
| 7F) TRASH TERMINATION ROOM # 117 HAS (2) DOORS A SWING |
| DOOR LISTED AS 117 WHILE THE OVERHEAD DOOR DOES NOT |
| HAVE A IDENTIFICATION TAG, NOR DOOR RATING AS REQUIRED |
| BY 2010 FBC-B 70813.4. |
| |
| 7G) THE DOOR 101 SEPARATING THE S2 STORAGE OCCUPANCY |
| FROM THE BUSINESS OCCUPANCY IS MISSING THE DOOR RATING |
| ON THE DOOR SCHEDULE, PAGE 126 A.7.1.1. 2010 FBC-B |
| TABLE 715.4. |
| |
| 7H) THIS NOTE IS COMMON FOR ALL FLOORS. IN REVIEWING |
| THE VARIOUS DOORS IN EXIT ENCLOSURES FOR THERE FIRE |
| RATINGS IN THE DOOR SCHEDULE LISTED ON PAGE 126 A7.1.1 |
| THERE IS A NOTE # 1 FOR HARDWARE SETS REFER TO |
| SPECIFICATIONS. PLEASE NOTE SPECIFICATIONS ARE |
| SOMETHING WE NORMALLY DO NOT REVIEW SINCE THEY CAN BE |
| SEVERAL HUNDRED PAGES IN LENGTH. PLEASE PROVIDE A |
| HARDWARE SCHEDULE THAT RELATES TO THE DOOR SCHEDULE SO |
| CODE COMPLIANCE CAN BE REVIEWED. NORMALLY |
| SPECIFICATIONS ARE STAMPED VOID NOT REVIEWED. |
| 7I) PLEASE PROVIDE THE 1ST FLOOR SQ. FOOTAGE VERSES THE |
| OWNERS STORAGE LOCKER AREA TO SEE IF THIS AREA |
| QUALIFIES AS AN MIXED USE OCCUPANCY REQUIRING |
| SEPARATION. 2010 FBC-B 508.2.1. |
| 7J) HORIZONTAL TRELLIS FOUND ON THE SOUTH & WEST SIDES |
| OF THE BUILDING SEE SECTION 6,8 & 9 PAGE A7.5.4. PLEASE |
| SHOW WIND DESIGN AND ANCHORING DETAILS. FBC-B |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FL 61G-15-30.006 |
| (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 7K) NOTE!!! THE FPL VAULT TO BE BUILT TO THE AGREEMENT |
| BETWEEN FPL AND PROPERTY OWNER. |
| 7L) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: F] |
| 914.1.1 EXTERIOR ACCESS TO SHAFTWAYS. OUTSIDE OPENINGS |
| ACCESSIBLE TO THE FIRE DEPARTMENT AND THAT OPEN |
| DIRECTLY ON A HOISTWAY OR SHAFTWAY COMMUNICATING |
| BETWEEN TWO OR MORE FLOORS IN A BUILDING SHALL BE |
| PLAINLY MARKED WITH THE WORD ?SHAFTWAY? IN RED LETTERS |
| AT LEAST 6 INCHES (152 MM) HIGH ON A WHITE BACKGROUND. |
| SUCH WARNING SIGNS SHALL BE PLACED SO AS TO BE READILY |
| DISCERNIBLE FROM THE OUTSIDE OF THE BUILDING. |
| 7M) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: F |
| 914.1.2 INTERIOR ACCESS TO SHAFTWAYS. DOOR OR WINDOW |
| OPENINGS TO A HOISTWAY OR SHAFTWAY FROM THE INTERIOR OF |
| THE BUILDING SHALL BE PLAINLY MARKED WITH THE WORD |
| ?SHAFTWAY? IN RED LETTERS AT LEAST 6 INCHES (152 MM) |
| HIGH ON A WHITE BACKGROUND. SUCH WARNING SIGNS SHALL BE |
| PLACED SO AS TO BE READILY DISCERNIBLE. |
| 7N) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F] |
| 914.2 EQUIPMENT ROOM IDENTIFICATION. FIRE PROTECTION |
| EQUIPMENT SHALL BE IDENTIFIED IN AN APPROVED MANNER. |
| ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS, |
| SPRINKLER RISERS AND VALVES OR OTHER FIRE DETECTION, |
| SUPPRESSION OR CONTROL ELEMENTS SHALL BE IDENTIFIED FOR |
| THE USE OF THE FIRE DEPARTMENT. APPROVED SIGNS REQUIRED |
| TO IDENTIFY FIRE PROTECTION EQUIPMENT AND EQUIPMENT |
| LOCATION SHALL BE CONSTRUCTED OF DURABLE MATERIALS, |
| PERMANENTLY INSTALLED AND READILY VISIBLE. |
| 7O) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F] |
| 915.1 GENERAL. [F] 915.1 GENERAL. |
| EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE |
| PREVENTION CODE. |
| |
| 7P) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B 916.1 |
| CARBON MONOXIDE PROTECTION. EVERY SEPARATE BUILDING OR |
| AN ADDITION TO AN EXISTING BUILDING FOR WHICH A PERMIT |
| FOR NEW CONSTRUCTION IS ISSUED AND HAVING A |
| FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR |
| ELEMENT THAT EMITS CARBON MONOXIDE AS A BYPRODUCT OF |
| COMBUSTION SHALL HAVE AN OPERATIONAL CARBON MONOXIDE |
| ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR |
| SLEEPING PURPOSES IN THE NEW BUILDING OR ADDITION, OR |
| AT SUCH OTHER LOCATIONS AS REQUIRED BY THIS CODE. |
| |
| 8) 2ND FLOOR, PAGE 025 LS-2-0, 035 A2-2-1,& A-2-2-2. |
| 8A) THE HANDICAPPED SPACE # 58 DOES NOT HAVE A 5?-0? |
| CLEAR ACCESS AISLE NEXT TO IT, THERE IS A COLUMN IN THE |
| WAY AT GRID LINE C.6 AND 1.5. NOTE THE COLUMN IS 3FT 3 |
| INCHES FROM THE ACCESSIBLE PARKING SPACE, EVEN THOUGH |
| THE AISLE IS WIDER IF THE COLUMN IS AT A POINT WHERE |
| THE DOOR CANNOT BE OPENED NOR A VANS ACCESSIBLE |
| PLATFORM CANNOT BE LOWERED. |
| 8B) THERE IS (2) AREAS NOT CLEAR AS TO WHERE THE |
| CEILING IS LOCATED OR IF THE BLOCK WALL GOES ALL THE |
| WAY TO THE 3RD FLOOR. SEE FPL TRANSFORMER VAULT AND |
| SWITCHGEAR/ ELECTRIC ROOM. 107.2.1.3 ADDITIONAL |
| INFORMATION REQUIRED. |
| 9) PAGE 026 LS-3.0, PAGE 038 A2.3.1 & PAGE 039 A2.3.2: |
| 9A) DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED |
| COMMON AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE |
| UNIT. THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON |
| THE LATCH SIDE OF THE DOOR, PER FAIR HOUSING |
| REQUIREMENT 3. USABLE DOORS. GUIDELINE SECTION |
| 100.205(C)(2) WOULD APPLY TO DOORS THAT ARE A PART OF |
| AN ACCESSIBLE ROUTE IN THE PUBLIC AND COMMON USE AREAS |
| OF MULTIFAMILY DWELLINGS AND TO DOORS INTO AND WITHIN |
| INDIVIDUAL DWELLING UNITS. |
| (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS |
| AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS |
| THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT. |
| 9B)NOTE THIS WILL BE A COMMON STATEMENT FOR ALL UNITS |
| FOUND ON: |
| PAGE 078 A6.1.2 UNIT 301 & 302 |
| PAGE 080 A6.2.2 UNIT 303 & 304 |
| PAGE 083 A6.3.2 UNIT 305 & 306 |
| PLEASE NOTE THE TENANT SEPARATION WALLS FOR THIS FLOOR |
| INDICATE A 1 HOUR FIRE RATING BUT THE DOOR SCHEDULE FOR |
| THE TYPICAL DWELLING UNIT DOORS SHOWS THE ENTRY DOOR AS |
| WELL AS THE A/C CLOSET DOOR THAT IS WITHIN THE TENANT |
| SEPARATION WALL BOTH SHOW 20 MIN. DOORS. FBC-B TABLE |
| 715.4 DOES ALLOW FOR 20 MIN. DOORS INTO CORRIDORS FOR A |
| GENERAL RULE. SECTION 709.3 FIRE RESISTANCE RATINGS AS |
| WELL IN EXCEPTION # 1 ALLOWS FOR CORRIDOR WALLS TO BE ? |
| HR. RATED. EXCEPTION # 2 FOR DWELLING UNITS DOES NOT |
| GIVE THE REDUCTION FOR TYPE I BUILDINGS, THE REDUCTION |
| CAN ONLY TAKE PLACE IN TYPE IIB, IIIB AND VB. |
| 10) PAGE 027 LS 4.0, PAGE 041 A2.4.1 & PAGE 042 A2.4.2: |
| NOTE: COMMENTS FOR THE 4TH FLOOR WILL ALSO STAND FOR |
| THE 6TH FLOOR. |
| |
| 10A) THE COMMON CMU WALL BETWEEN THE PARKING GARAGE AND |
| OPEN AIR 3RD STORY DWELLING UNITS (CLEARSTORY) IS A 2 |
| HOUR FIRE RATED WALL. THE STRUCTURAL SHEETS SHOW |
| DETAILS OF THIS WALL PAGE 171 S2.40 SHOWS A DETAIL #7 |
| FOUND ON S5-10. THIS DETAIL SHOW A REINFORCED CONCRETE |
| POURED 8 INCH WALL TO COMPLY WITH FBC-B 1607.7.3 |
| VEHICLE BARRIER SYSTEMS. THERE ARE (2) POINTS OF |
| LOADING TO CONSIDER, PLEASE PROVIDE HOW THE 2ND IS MET: |
| THE SECOND LOADING CONDITION SHALL APPLY THE LOAD AT 2 |
| FEET, 3 INCHES (686 MM) ABOVE THE FLOOR OR RAMP |
| SURFACE. THE MORE SEVERE LOAD CONDITION SHALL GOVERN |
| THE DESIGN OF THE BARRIER. |
| 10B) THE 2ND COMMENT DEALS WITH AN ACCESSIBLE PARKING |
| SPACE AND ACCESS AISLE NEXT TO STAIR # 3. THE FAIR |
| HOUSING REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC AND |
| COMMON USE AREAS. ANSI 117.1 GENERAL SITE AND BUILDING |
| ELEMENTS. SECTION 503.3 ACCESS AISLES. WIDTH 503.3.1 60 |
| INCHES/ LENGTH 503.3.2 20 FT. LONG MINIMUM. |
| 11) PAGE 028 LS 5.0, PAGE 044 A2.5.1 & PAGE 045 A2.5.2: |
| 11A) DOORS 507.02 & 507.03 BOTH DOORS ARE CONSIDERED |
| COMMON AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE |
| UNIT. THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON |
| THE LATCH SIDE OF THE DOOR, PER FAIR HOUSING |
| REQUIREMENT 3. USABLE DOORS. GUIDELINE SECTION |
| 100.205(C)(2) WOULD APPLY TO DOORS THAT ARE A PART OF |
| AN ACCESSIBLE ROUTE IN THE PUBLIC AND COMMON USE AREAS |
| OF MULTIFAMILY DWELLINGS AND TO DOORS INTO AND WITHIN |
| INDIVIDUAL DWELLING UNITS. |
| (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS |
| AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS |
| THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT. |
| |
| 11B)NOTE THIS WILL BE A COMMON STATEMENT FOR ALL UNITS |
| FOUND ON: |
| PAGE 078 A6.1.2 UNIT 501 & 502 |
| PAGE 080 A6.2.2 UNIT5303 & 504 |
| PAGE 083 A6.3.2 UNIT 505 & 506 |
| PLEASE NOTE THE TENANT SEPARATION WALLS FOR THIS FLOOR |
| INDICATE A 1 HOUR FIRE RATING BUT THE DOOR SCHEDULE FOR |
| THE TYPICAL DWELLING UNIT DOORS SHOWS THE ENTRY DOOR AS |
| WELL AS THE A/C CLOSET DOOR THAT IS WITHIN THE TENANT |
| SEPARATION WALL BOTH SHOW 20 MIN. DOORS. FBC-B TABLE |
| 715.4 DOES ALLOW FOR 20 MIN. DOORS INTO CORRIDORS FOR A |
| GENERAL RULE. SECTION 709.3 FIRE RESISTANCE RATINGS AS |
| WELL IN EXCEPTION # 1 ALLOWS FOR CORRIDOR WALLS TO BE ? |
| HR. RATED. EXCEPTION # 2 FOR DWELLING UNITS DOES NOT |
| GIVE THE REDUCTION FOR TYPE I BUILDINGS, THE REDUCTION |
| CAN ONLY TAKE PLACE IN TYPE IIB, IIIB AND VB. |
| |
| 11C) THIS COMMENT WILL BE A COMMON COMMENT FOR ALL |
| FLOORS,(FLOOR SLABS ARE 8 INCH POST TENSION SLABS) THE |
| 3RD -16TH STORY. PLEASE PROVIDE COMPLIANCE WITH BLDG |
| TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| |
| 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 703.4 NONCOMBUSTIBILITY TESTS. |
| |
| THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| |
| 703.4.1 ELEMENTARY MATERIALS. |
| MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| IN ACCORDANCE WITH ASTM E 136. |
| |
| 703.4.2 COMPOSITE MATERIALS. |
| MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723 SHALL BE ACCEPTABLE AS |
| NONCOMBUSTIBLE MATERIALS. |
| |
| 12) PAGE 030 LS 7.0, PAGE 050 A2.7.1 & PAGE 051 A2.7.2: |
| 12A) COMMON ROOM 701.01 APPROXIMATELY 1286 SQ. FT./ 15= |
| 85 OCCUPANTS, THIS ROOM WILL REQUIRE 2 EXITS. NOTE ONE |
| EXIT IS THROUGH THE ELEVATOR LOBBY (700) TO STAIR 701. |
| THE LIFE SAFETY SHEET DOES NOT SHOW EXITING FOR THIS |
| ROOM. 708.14.1 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE |
| MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER |
| PROVISIONS WITHIN THIS CODE. IN REALITY STAIRWELL 701 |
| CANNOT BE USED FOR THIS FLOOR AS DEPICTED! |
| 12B) THE POOL DECK AND POOL SURFACE AREA TOTAL OCCUPANT |
| LOAD EQUAL A TOTAL OF 121 OCCUPANTS. PLEASE PROVIDE THE |
| (2) MEANS OF EGRESS WITHOUT GOING THROUGH THE ELEVATOR |
| LOBBY. IN REALITY STAIRWELL 701 CANNOT BE USED FOR THIS |
| FLOOR AS DEPICTED! |
| 12C) EXIT ROUTE # 07 WEST TRAVELS THROUGH THE ELEVATOR |
| LOBBY. . 708.14.1 ELEVATOR LOBBIES SHALL HAVE AT LEAST |
| ONE MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER |
| PROVISIONS WITHIN THIS CODE. IN REALITY STAIRWELL 701 |
| CANNOT BE USED FOR THIS FLOOR AS DEPICTED! |
| 12D) DOOR 706F DOES NOT COMPLY WITH THE FAIR HOUSING |
| GUIDE LINES REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC |
| AND COMMON USE AREAS. ANSI A117.1 TABLE 404.2.4.1 |
| MANEUVERING CLEARANCES FOR MANUAL SWING DOORS. |
| 12E) NOTE THIS POOL DECK AND POOL ARE COVERED UNDER THE |
| FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY REQUIRES |
| ACCESS MUST BE PROVIDED TO THE POOL DECK AREA, NOT AN |
| ACCESSIBLE ROUTE(RAMP OR LIFT) DOWN INTO THE WATER INTO |
| THE POOL. ON THE OTHER HAND IF THE ASSOCIATION ELECTS |
| TO ALLOW THE COMMUNITY ROOM, POOL, AND OR POOL DECK TO |
| BE RENTED OUT FOR PARTIES THAT THE PUBLIC COULD USE, |
| THEN THIS AREA WOULD BE REQUIRED TO MEET FLORIDA |
| ACCESSIBILITY SECTION 1009 OF THE ACCESSIBILITY CODE |
| POOL LIFTS. |
| 12F) THIS NOTE WILL BE A COMMON NOTE FOR FLOORS 7-20TH |
| FLOORS. THE DOOR SCHEDULE FOUND ON PAGE 126 A.7.1.1 |
| (DOOR SCHEDULE) IN THE REMARKS COLUMN THERE ARE VARIOUS |
| DOORS IN THE CORRIDOR THAT STATE THAT A FIRE DAMPER IS |
| TO BE INSTALLED IN THE LOUVERED DOOR. PLEASE SHOW |
| COMPLIANCE WITH: |
| |
| 2010 FBC-B 715.4.6 LABELED PROTECTIVE ASSEMBLIES. FIRE |
| DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED AGENCY. |
| THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL BE |
| PERMANENTLY AFFIXED TO THE DOOR OR FRAME INSTALLED |
| WITHIN THE LOUVERED DOOR. |
| |
| 716.5.2 FIRE BARRIERS. DUCTS AND AIR TRANSFER OPENINGS |
| OF FIRE BARRIERS SHALL BE PROTECTED WITH APPROVED FIRE |
| DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING. |
| |
| 12G) PAGE 023 LS-0.1 LIST THE REQUIRED FIRE SEPARATION |
| DISTANCE FOR THE REQUIRED HOURLY RATING AND AMOUNT OF |
| ALLOWABLE OPENINGS. SHEET A2-7.2 THE EAST PROPERTY LINE |
| WALL IS APPROX. 13 FEET AWAY FROM THE OPENINGS, FBC-B |
| TABLE 705.8 ALLOWS 45% UNPROTECTED SPRINKLERED, PLEASE |
| PROVIDE THE PERCENTAGE OF ALLOWABLE OPENING TAKEN PER |
| FLOOR LEVEL. |
| 13) PAGE 031 LS 8.0, PAGE 053 A2.8.1 & PAGE 054 A2.8.2. |
| 8TH-20TH FLOORS COMMON TO ALL FLOORS. |
| 13A) THIS PAGE SHOWS SLIDING GLASS DOOR (SGD 6) IN UNIT |
| 815 BEDROOM # 02, THE DOOR SCHEDULE (129 A7.3.1) |
| INDICATES THIS SLIDING GLASS DOOR IS A 6FT. 4 IN. IS |
| THIS A ROUGH OPENING SIZE OR OUTSIDE DOOR JAMB OPENING, |
| NOT CLEAR. IN THE FAIR HOUSING GUIDE THE EXTERIOR |
| SLIDING GLASS DOORS WILL NEED TO MEET REQUIREMENT # 4 |
| (2) |
| A MINIMUM CLEAR WIDTH OF 32 INCHES IS PROVIDED. |
| |
| 13B) FOR ALL SLIDING GLASS DOORS THE HARDWARE WILL ALSO |
| NEED TO MEET THE ANSI 117.1 STANDARD 404.2.7. |
| |
| 14) PAGE 056 A.2.9.1: |
| |
| 14A) ROOF NOTE # 3 : |
| THE NO LESS THAN R-10 IN ANY LOCATION LIKE ROOF DRAINS |
| STILL HAS TO HAVE A MINIMUM OF R-19 INSULATION. SEE THE |
| 2010 FBC-ENERGY CODE 506.2.1 UNDER TOTAL BUILDING |
| PERFORMANCE METHOD. |
| SEE BOAF INFORMAL INTERPRETATION # 5438 |
| |
| DATE: TUE NOV 13 2007 |
| REPORT #: 5438 |
| CODE: BUILDING |
| SECTION: 404.1.A |
| QUESTION: |
| IS IT THE INTENT OF THE CODE "....THE INSULATION SHALL |
| HAVE A R-VALUE OF AT LEAST R-19, SPACE PERMITTING." TO |
| MEAN THE MINIMUM R-VALUE OF ROOF INSULATION TO BE R-19 |
| AT LOWEST POINTS AT DRAINS? ALL ROOFERS WHO WE HAVE |
| SPOKEN TO, INTERPRETED THIS CODE AS MINIMUM AVERAGE |
| R-19, NOT MINIMUM R-19 AND HAVE DONE MOST ROOFING JOB |
| ACCORDINGLY. THANK YOU |
| ANSWER: A MINIMUM LEVEL OF INSULATION REQUIRED IS THAT, |
| A MINIMUM, NOT AN AVERAGE. HOWEVER, PROVIDED THE |
| MINIMUM R-19 VALUE HAS BEEN MET, A REASONABLE AVERAGING |
| PROCEDURE CAN BE USED BY ROOF AREA FOR CALCULATIONS OF |
| THE VALUE. |
| COMMENTARY: THIS QUESTION ACTUALLY REFERS TO SECTION |
| 13-404.1 (A) PRESCRIPTIVE REQUIREMENTS SPECIFIC TO |
| METHOD A. THIS SECTION MANDATES COMPLIANCE WITH FLA/COM |
| METHOD A, HOWEVER GIVES A PRESCRIPTIVE REQUIREMENT OF |
| AN R-19 FOR MULTIFAMILY RESIDENTIAL ROOF/CEILING |
| ASSEMBLY. AS SPACE PERMITS, MAY RELATE TO THE AREA OF |
| THE EAVES WHERE THE R- 19 INSULATION WOULD HAVE TO BE |
| COMPRESSED TO FIT IN THE SPACE AVAILABLE. HOWEVER, THE |
| PETITIONER ALLUDES TO THE ROOFER INSTALLING THE |
| INSULATION. THERE ARE NO SPACE CONSTRAINTS FOR |
| INSULATION APPLIED TO A ROOF DECK; IT SHOULD BE R-19 |
| MINIMUM. IF THE BUILT-UP ROOF IS SLOPING TO A DRAIN IN |
| A MANNER WHERE SOME PARTS OF THE ROOF HAVE MORE THAN |
| R-19 AND SOME HAVE LESS, THEN THE RESIDENT WHOSE |
| APARTMENT/CONDO IS UNDER THE ROOF SECTION WITH LESS |
| THAN R- 19 WOULD BE PENALIZED WITH HIGHER HEAT LOADS |
| AND HIGHER ENERGY COSTS THAN THEIR NEIGHBOR. |
| |
| 14B) ROOF NOTE # 6 REFERENCES THE USE OF CHEN-CURB OR |
| EQUAL FOR PIPE OR TUBE ROOF PENETRATIONS. THE PRODUCT |
| SPECIFIED HAS TO BE SPECIFIC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. SUCH INFORMATION SHALL BE |
| SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 14C) ROOF DRAINAGE CALCULATIONS DO NOT PROVIDE THE RATE |
| OF RAINFALL PER HR. THE CHARTS WERE DESIGN FOR. |
| P] 1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE SLOPED TO |
| DRAIN OVER ROOF EDGES, DESIGN AND INSTALLATION OF ROOF |
| DRAINAGE SYSTEMS SHALL COMPLY WITH SECTION 1503 AND THE |
| FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. |
| |
| 14D) THE QUESTION IS THE TOP OF ROOF DRAINS IS SHOWN AS |
| MINUS INCHES FROM THE TOP OF ROOF, FOR EXAMPLE BOTH |
| AREAS OF THE ROOF DESIGNATED AS N & P BOTH SHOW A -7 |
| INCHES T.O.D. OR -7 INCHES FROM THE TOP OF THE HIGHEST |
| ROOF DECK WHERE THE DECK ADJOINS TO THE PARAPET WALL. |
| DETAIL 5/ A7.5.1 SHOWS THE EMERGENCY OVERFLOW SET AN |
| ADDITIONAL 2 INCHES ABOVE THE 7 INCHES TOP OF DRAIN OR |
| 9 INCHES OF DEPTH OF WATER BEFORE WATER CAN START TO |
| OVERFLOW THE EMERGENCY ROOF SCUPPERS. IN ROOF ZONE P, |
| THIS IS APPROXIMATELY 42,553 LBS. OF WATER WEIGHT. |
| |
| FBC-B 1503.4.2.1 WHEN LOOKING AT THIS SECTION THE |
| INTENT IS WHEN THE ROOF IS SLOPED TO A SCUPPER THE, THE |
| SCUPPER SHALL BE PLACED LEVEL (1503.4.2) TO THE ROOF |
| DECK. THE EMERGENCY OVERFLOW SCUPPERS ARE TO BE PLACED |
| 2 -4 INCHES ABOVE THE SCUPPER. THIS IS A COMMON MISTAKE |
| WHEN APPLYING 1503.4.1 SECONDARY DRAINAGE REQUIRED. IF |
| THE ROOF DRAINS ARE TO BE THE PRIMARY DRAIN THEN |
| SHOULDN?T THE EMERGENCY OVERFLOW SCUPPERS BE PLACED 2 |
| TO 4 INCHES ABOVE THE DRAIN? IF USING A SECONDARY ROOF |
| DRAIN THAT IS HOW IT WOULD BE SET UP 2 TO 4 INCHES |
| ABOVE THE ROOF DRAIN. |
| |
| 14E) THE PLANS INDICATE THE USE OF PRE-ENGINEERED A/C |
| STANDS. WHEN FIGURING THE REQUIRED CLEARANCES IN HEIGHT |
| REQUIRED BY TABLE FBC-B 1509.7, THE CLEARANCE IS FROM |
| THE FINISHED ROOF HEIGHT, ABOVE THE LIGHTWEIGHT |
| CONCRETE ROOF. |
| |
| 15) THIS IS MORE OF A CONCERN FOR THE FIRE DEPARTMENT |
| AS TO HOW THE FIRE DEPARTMENT WILL BE ABLE TO GAIN |
| ENTRY WHEN THE TILT GATES TO THE GARAGE ARE DOWN? WILL |
| THE GARAGE TILT GATES BE ON EMERGENCY POWER CIRCUITRY? |
| IN THE EVENT OF GATE FAILING TO OPEN HOW WILL EGRESS TO |
| MAINTAINED ? 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED? |
| |
| 16) PAGES 126 A7-1-1, 127 A7-2-1, 129 A7-3-1, 130 |
| A7-3-2, 131 A7-3-3 & 132 A7-4-1. ALL OF THESE SHEETS |
| DEAL WITH THE EXTERIOR OF THE BUILDING AND WITH |
| COMPONENTS & CLADDING. |
| |
| 16A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 16B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC |
| |
| 16C) IF EITHER THE CONTRACTOR OR DESIGNER OF RECORD |
| WISH TO DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT |
| ISSUANCE PLEASE INFORM SO IN WRITING. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION. 107.3.4.3 |
| CERTIFICATIONS BY CONTRACTORS AUTHORIZED UNDER THE |
| PROVISIONS OF SECTION 489.115 FLORIDA STATUTES, SHALL |
| BE CONSIDERED EQUIVALENT TO SEALED PLANS AND |
| SPECIFICATIONS BY A PERSON LICENSED UNDER CHAPTER 471, |
| FLORIDA STATUTES, OR CHAPTER 481 FLORIDA STATUTES, BY |
| LOCAL ENFORCEMENT AGENCIES FOR PLANS REVIEW FOR |
| PERMITTING PURPOSES RELATING TO COMPLIANCE WITH THE |
| WIND-RESISTANCE PROVISIONS OF THE CODE OR ALTERNATE |
| METHODOLOGIES APPROVED BY THE FLORIDA BUILDING |
| COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS. LOCAL |
| ENFORCEMENT AGENCIES MAY RELY UPON SUCH CERTIFICATION |
| BY CONTRACTORS THAT THE PLANS AND SPECIFICATIONS |
| SUBMITTED CONFORM TO THE REQUIREMENTS OF THE CODE FOR |
| WIND RESISTANCE. UPON GOOD CAUSE SHOWN, LOCAL |
| GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT OR |
| REJECT PLANS SEALED BY PERSONS LICENSED UNDER CHAPTERS |
| 471,481 OR 489, FLORIDA STATUTES. |
| |
| 17) PAGES 163 S1.13 AND 164 S1.14. NOTE # 1 ON THESE |
| SHEETS INDICATE THE PRESSURES WERE CALCULATED USING THE |
| CALCULATED BY CODE ANALYTICAL METHODS. THIS TERM |
| ANALYTICAL METHOD DOES NOT SHOW UP IN THE CODE WHEN A |
| WORD SEARCH IS COMPLETED. IT WOULD APPEAR THAT A WIND |
| TUNNEL TEST WAS COMPLETED AS ALLOWED BY FBC-B 1609.1.1 |
| EXCEPTION 6. WIND TUNNEL TEST ARE TO BE IN ACCORDANCE |
| WITH CHAPTER 31 OF ASCE 7. PLEASE PROVIDE THE SIGNED |
| AND SEALED WIND TUNNEL TEST OR PROVIDE HOW THESE |
| PRESSURES WERE DERIVED. |
| |
| 18) PAGE 165 THE FOUNDATION PLAN SHOWS ALL PILE CAP |
| DIRECTLY ON THE PROPERTY LINE. A REVISION MAY BE |
| REQUIRED. THE SOILS REPORT INDICATES THAT THIS SITE HAS |
| LOOSE SOILS AND BECAUSE OF THE CLOSENESS OF OTHER |
| BUILDINGS AROUND THE SITE, VIBROFLOTATION WAS NOT |
| RECOMMENDED AND AUGERED CAST PILES CAST IN PLACE SHOULD |
| BE USED TO SUPPORT THE STRUCTURE. THE SOILS REPORT WENT |
| IN DEPTH OF HOW THE UTILITIES IN THE ALLEY WOULD NEED |
| TO BE SUPPORTED AND HOW TO COMPLETE THIS TASK. |
| |
| LAST WEEK (MAY 12/2015) IN A MEETING WITH MATT STILL |
| THE PROJECT MANAGER , MATT SPOKE ABOUT THE POSSIBLE USE |
| OF SHEET PILING AROUND THE PERIMETER OF THE PROJECT. |
| THIS WILL HAVE THE SAME EFFECT AS VIBROFLOTATION AS TO |
| DAMAGE TO STRUCTURES IN THE VICINITY OF THE PROJECT. A |
| RESOLUTION ON THIS MATTER WILL NEED TO TAKE PLACE IF |
| SHEET PILE ARE GOING TO BE INSTALLED AROUND THE |
| PERIMETER, THIS WILL AFFECT THE PLACEMENT OF THE PILE |
| AND PILE CAPS. |
| |
| 19) PAGE A7.5.3 ; |
| 19A) NOTE: THE POOL TRELLIS STRUCTURE (PERGOLA) THIS |
| DETAIL INDICATES IT IS GOING TO BE DESIGNED BY A |
| SPECIALTY ENGINEER. BEFORE SUBMITTAL TO THE BUILDING |
| DEPARTMENT, THE PLANS WILL NEED TO BE REVIEWED BY THE |
| ENGINEER OF RECORD. FL 61G-15-30.006 (3) THE DELEGATED |
| ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| |
| 19B) THE POOL TRELLIS STRUCTURE (PERGOLA) THIS |
| STRUCTURE INDICATES THE USE OF A PLEXIGLASS RAIN GUARD. |
| PLEASE PROVIDE HOW THE PLEXIGLASS RAIN GUARD WILL MEET |
| THE FIRE RESISTANCE RATINGS REQUIRED BY FBC-B TABLE 601 |
| AND FBC-B TABLE 1505.1.ALSO SEE FBC-B 2610 2610.4. WILL |
| THERE BE FIRE SPRINKLERS BENEATH THIS STRUCTURE. |
| |
| 20) PAGE 136 A7.5.4. |
| 20A) DETAIL # 5 RIGID ALUMINUM CANOPY WITH FABRIC |
| WRAPPED WILL REQUIRE WIND DESIGN CRITERIA SEE OPTIONS |
| FOUND UNDER FBC-B 3105.4 . ALSO: FL 61G-15-30.006 (3) |
| THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 20B) DETAIL # 5 RIGID ALUMINUM CANOPY WITH FABRIC |
| WRAPPED WILL NEED TO MEET THE REQUIREMENTS OF 3105.3.1 |
| FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL |
| MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA |
| 701. |
| |
| 21) PAGE 137 A7.5.5 DETAIL # 10 THE BALCONY EDGE |
| ALUMINUM RAILING DOES NOT HAVE THE DESIGN CRITERIA THAT |
| WILL BE REQUIRED TO MANUFACTURER, THE BALCONY RAIL WILL |
| NEED TO MEET THE FOLLOWING : |
| FBC-B 1607.7.1.1 CONCENTRATED LOAD & . 1607.7.1.2 |
| COMPONENTS. |
| |
| 22) PAGE 139 A9.1.1 STAIRWELL NUMBER 1 DOES NOT SHOW |
| THE STANDPIPE IN THE STAIRWELL NOR ARE THERE ANY NOTES |
| ONE IS REQUIRED. FBC-B 905.3.1. THIS COMMENT STAND FOR |
| ALL STAIRWELLS. PLEASE NOTE THE ONLY PENETRATIONS |
| ALLOWED IN THE STAIRWELL ARE TOUGHS THAT COMPLY WITH: |
| |
| FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND |
| OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED |
| EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK |
| NECESSARY FOR INDEPENDENT VENTILATION OR |
| PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT |
| ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL |
| BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| |
| 23) PAGE 153 A11.2: |
| 23A) DETAIL # 1 THE TRASH TERMINATION ROOM, SHOW A |
| STAINLESS STEEL ROLLING FIRE DOOR WITH 165 DEGREE |
| FUSIBLE LINK, THE PLANS DO NOT INDICATE WHAT THE FIRE |
| DOOR IS RATED TOO? FBC-B TABLE 715.4. |
| |
| 23B) THE THROUGH THE FLOOR FIRE PROOFING DETAIL |
| INDICATE THE USE OF MINERAL WOOL INSULATION PLEASE |
| PROVIDE A LISTED ASSEMBLY FOR A 2?-0? DIAMETER STEEL |
| TRASH CHUTE, NOT FOUND ON THE UL ASSEMBLY SHEET. FBC-B |
| 713.4.1.1 THROUGH PENETRATIONS. |
| THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED |
| HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION |
| 713.4.1.1.1 OR 713.4.1.1.2. |
| |
| 23C) THROUGH PENETRATION OF FLOOR SLAB FOR TUB DRAIN IF |
| TRAP IS WITHIN THE FLOOR ASSEMBLY IS NOT PROVIDED ON |
| THE UL ASSEMBLY SHEETS NOR P5.1.2. THROUGH PENETRATIONS |
| OF FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL |
| COMPLY WITH SECTION 713.4.1.1.1 OR 713.4.1.1.2. |
| 24) PLEASE PROVIDE WHERE THE FOLLOWING REQUIREMENTS FOR |
| HIGH RISE CONSTRUCTION CAN BE FOUND: |
| 24A)FBC-B 403.3.2 WATER SUPPLY TO REQUIRED FIRE PUMPS. |
| REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO |
| A MINIMUM OF TWO WATER MAINS LOCATED IN DIFFERENT |
| STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED |
| BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE |
| PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN |
| THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY |
| THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO |
| OPERATE. |
| |
| 24B) FBC-B [F] 403.4.3 EMERGENCY VOICE/ALARM |
| COMMUNICATION SYSTEM. |
| AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2. |
| |
| 24C) FBC-B [F] 403.4.4 EMERGENCY RESPONDER RADIO |
| COVERAGE. |
| EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| |
| 24D) FBC-B 403.4.6 SMOKE REMOVAL. SMOKE CONTROL SHALL |
| BE PROVIDED IN ACCORDANCE WITH SECTION 909. |
| |
| |
| 24E) FBC-B [F] 403.4.7 STANDBY POWER. |
| A STANDBY POWER SYSTEM COMPLYING WITH CHAPTER 27 SHALL |
| BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN |
| SECTION 403.4.7.2. |
| |
| 24F) FBC-B [F] 403.4.7.2 STANDBY POWER LOADS. |
| THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: |
| 1. POWER AND LIGHTING FOR THE FIRE COMMAND CENTER |
| REQUIRED BY SECTION 403.4.5; |
| 2. VENTILATION AND AUTOMATIC FIRE DETECTION EQUIPMENT |
| FOR SMOKEPROOF ENCLOSURES; AND |
| 3. STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN |
| ACCORDANCE WITH SECTIONS 1006.2.4, 3003, 3007 AND 3008. |
| |
| 24G) [F] 403.4.8 EMERGENCY POWER SYSTEMS. AN EMERGENCY |
| POWER SYSTEM COMPLYING WITH CHAPTER 27 SHALL BE |
| PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED IN SECTION |
| 403.4.8.1. |
| [F] 403.4.8.1 EMERGENCY POWER LOADS. |
| THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS: |
| 1. EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION REQUIRED |
| BY CHAPTER 10; |
| 2. ELEVATOR CAR LIGHTING; |
| 3. EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; |
| 4. AUTOMATIC FIRE DETECTION SYSTEMS; |
| 5. FIRE ALARM SYSTEMS; AND |
| 6. ELECTRICALLY POWERED FIRE PUMPS. |
| |
| |
| 24H) FBC-B 403.5.3.1 STAIRWAY COMMUNICATION SYSTEM. |
| A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM |
| CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION |
| SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN |
| EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY ARE |
| LOCKED. |
| |
| 24I) FBC-B 403.5.4 SMOKEPROOF EXIT ENCLOSURES. EVERY |
| REQUIRED EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET |
| (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT |
| VEHICLE ACCESS SHALL COMPLY WITH SECTIONS 909.20 AND |
| 1022.9. |
| 24J) FBC-B 1022.8 FLOOR IDENTIFICATION SIGNS. / |
| 1022.8.1 SIGNAGE REQUIREMENTS. |
| |
| 24K) FBC-B 403.5.5 LUMINOUS EGRESS PATH MARKINGS. |
| LUMINOUS EGRESS PATH MARKINGS SHALL BE PROVIDED IN |
| ACCORDANCE WITH SECTION 1024.1-5. |
| 1024.4 SELF-LUMINOUS AND PHOTOLUMINESCENT. LUMINOUS |
| EGRESS PATH MARKINGS SHALL BE PERMITTED TO BE MADE OF |
| ANY MATERIAL, INCLUDING PAINT, PROVIDED THAT AN |
| ELECTRICAL CHARGE IS NOT REQUIRED TO MAINTAIN THE |
| REQUIRED LUMINANCE. SUCH MATERIALS SHALL INCLUDE, BUT |
| ARE NOT LIMITED TO, SELF-LUMINOUS MATERIALS AND |
| PHOTOLUMINESCENT MATERIALS. MATERIALS SHALL COMPLY WITH |
| EITHER: |
| 1. UL 1994; OR |
| 2. ASTM E 2072, EXCEPT THAT THE CHARGING SOURCE SHALL |
| BE 1 FOOTCANDLE (11 LUX) OF FLUORESCENT ILLUMINATION |
| FOR 60 MINUTES, AND THE MINIMUM LUMINANCE SHALL BE 30 |
| MILLICANDELAS PER SQUARE METER AT 10 MINUTES AND 5 |
| MILLICANDELAS PER SQUARE METER AFTER 90 MINUTES. |
| |
| 1024.5 ILLUMINATION.EXIT ENCLOSURES WHERE |
| PHOTOLUMINESCENT EXIT PATH MARKINGS ARE INSTALLED SHALL |
| BE PROVIDED WITH THE MINIMUM MEANS OF EGRESS |
| ILLUMINATION REQUIRED BY SECTION 1006 FOR AT LEAST 60 |
| MINUTES PRIOR TO PERIODS WHEN THE BUILDING IS OCCUPIED. |
| |
| 25) [F] 3311.1 WHERE REQUIRED. IN BUILDINGS REQUIRED TO |
| HAVE STANDPIPES BY SECTION 905.3.1, NOT LESS THAN ONE |
| STANDPIPE SHALL BE PROVIDED FOR USE DURING |
| CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED WHEN |
| THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40 FEET |
| (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF FIRE |
| DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE |
| PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT |
| ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH |
| STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES |
| TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF |
| CONSTRUCTION HAVING SECURED DECKING OR FLOORING. |
| |
| 26) [F] 3312.1 COMPLETION BEFORE OCCUPANCY. |
| IN BUILDINGS WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| REQUIRED BY THIS CODE, IT SHALL BE UNLAWFUL TO OCCUPY |
| ANY PORTION OF A BUILDING OR STRUCTURE UNTIL THE |
| AUTOMATIC SPRINKLER SYSTEM INSTALLATION HAS BEEN TESTED |
| AND APPROVED, EXCEPT AS PROVIDED IN SECTION 111.3. |
| |
| 27) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 28) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| SECTION 113 OF THIS CHAPTER. |
| |
| |
| 29) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 30) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |