Plan Review Notes
Plan Review Notes For Permit 15031312
Permit Number 15031312
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-17 14:08:14BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15031312
 ADD: 333 FERN ST.
 CONT: KAST CONSTRUCTION
 CONTACT :
 TEL: (561)689-2910
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MAY 18 /2015
 ACTION: DENIED
  
 1) NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN
 PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2) THE PERMIT APPLIED VALUE IS STATED AS $28,665,000.00
 DOLLARS. THE CALCULATED VALUE IS $44,101,328.00 DOLLARS
 IN VALUE. USING THE FLOOR AREA SUMMARY FOUND ON 022
 SP1.1. PLEASE PROVIDE THE SQUARE FOOTAGE PER FLOOR.
 PLEASE BREAK OUT MIXED USE OCCUPANCIES PER FLOOR. FOR
 THE PARKING GARAGE PLEASE PROVIDE AREA BY LEVEL.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) PLEASE PROVIDE A SURVEY WITH THE PROPOSED OVERLAY OF
 THE BUILDING TO VERIFY THE ACTUAL DISTANCE FROM
 PROPERTY LINES. 2010 FBC-B TABLE 602.
 4) THE CURRENT SURVEY SUBMITTED INDICATES THIS PROPOSED
 STRUCTURE WILL BE LOCATED ON LOTS 11-15 OF BLOCK 10. A
 REPLAT WILL BE REQUIRED TO ELIMINATE THE BUILDING GOING
 PAST PROPERTY LINES. TABLE 602.
  
 5) NO ENERGY REPORT AND CALCULATIONS WERE SUBMITTED.
 PLEASE PROVIDE CODE COMPLIANCE WITH THE 2010 FBC-ENERGY
 103.2.1 CODE DEMONSTRATION FORMS, TABLE 103.2.1.
  
 6) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 6A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 6B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
 FORMS WERE SENT TO: : [email protected] AT
 05/09/2015 02:09 PM.
  
 6C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 6E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 6F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
  
 6G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 6H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 7) PAGE 024 LS-1.0, 032 A2.1.1 & 033 A2.1.2.
  
 7A) THESE PLANS INDICATE 5 STAIRWELLS WITH STAIRS 4 & 5
 HAVING THE EXIT DISCHARGE DIRECTLY AT THE EXTERIOR OF
 THE BUILDING. STAIR 1 EXITS THE VERTICAL ENCLOSURE
 TRAVEL THROUGH THE ELEVATOR LOBBY, MAIN LOBBY AND
 GALLERY BEFORE THE EXIT DISCHARGE IS ARRIVED AT. IN THE
 ELEVATOR LOBBY THERE ARE (2) COLUMNS AND SOME WALL TYPE
 THAT WOULD BLOCK THE VIEW OF THE MAIN ENTRANCE, MORE
 INFORMATION IS REQUIRED HOW THIS WILL QUALIFY UNDER THE
 EXCEPTIONS FOUND IN SECTION FBC-B 1027.1 IT APPEARS
 EXCEPTION 1 WOULD BE TAKEN?
  
 7B) THE OTHER STAIRWELL # 3 IT APPEARS IS ALSO TAKING
 THE SAME EXCEPTION FOUND IN 2010 FBC-B 1027.1 EXCEPTION
 # 1. THE 2007 FBC CODE COMMENTARY DOES IN PRINCIPLE
 AGREE, THERE IS LANGUAGE DOES LEAVE ROOM FOR QUESTION.
 THIS DOES NOT MEAN THE EXTERIOR EXIT DOOR MUST BE
 DIRECTLY IN FRONT OF THE DOOR AT THE BOTTOM OF THE
 STAIRWAY, BUT THE INTENT IS THAT IT SHOULD BE WITHIN
 THE GENERAL RANGE OF VISION. IT SHOULD NOT BE REQUIRED
 THAT A PERSON MUST TURN COMPLETELY AROUND OR GO AROUND
 A CORNER TO BE ABLE TO SEE THE WAY OUT.
  
 7C) STAIRWELL # 2 ROOM 139 IS SHOWN WITH A 2 HR.
 ENCLOSURE DOOR 139 1 ? HOUR OPENING PROTECTIVE. THE
 EXTENSION OF THE EXIT IS LABELED AS AN EXIT ACCESS
 CORRIDOR # 115. PLEASE NOTE THIS IS AN EXIT PASSAGE WAY
 AND NEEDS TO COMPLY WITH SECTION FBC-B 1023.6
 PENETRATIONS. THE MECHANICAL AND ELECTRICAL PLANS
 INDICATE AN INTAKE AIR LOUVER AN FAN WITH 2160 CFM TO
 PRESSURIZE THE EXIT PASSAGEWAY. NOTE NO ELECTRICAL RACE
 WAYS, CONDUITS, ETC. FROM THE FPL VAULT OR FROM THE
 SWITCHGEAR/ ELECTRICAL ROOM RUN THROUGH THIS EXIT
 PASSAGEWAY.
  
 7D) PLEASE NOTE THE EXIT PASSAGEWAY 115 THE TOP AND
 BOTTOM SLOPED AREAS MEET THE DEFINITION OF GRADE WITH A
 SLOPE OF 1:20 THE MIDDLE SECTION FROM LANDING MARKED AS
 12.75 FT. TO LANDING 12.08 FT. IS A DIFFERENCE OF 8
 INCHES X 20= 160 INCHES (13.3 FT. RAMP FBC-B 1010.2
 SLOPE) OF RUN REQUIRED NOT TO BE CONSIDERED A RAMP.
 THIS SECTION WILL NEED TO COMPLY WITH 2010 FBC-B 1010.8
 HANDRAILS.
  
 7E) THE PLANS INDICATE A SERIES OF LOUVERS AND WALL
 OPENINGS, THE OPENINGS DO NOT SHOW ANY PROTECTION NOR
 DOES THE LOUVERS WITH THE EXCEPTION OF LOUVER 17 SEE
 SHEET A7.4. THE FBC-B TABLE 705.8 BASES THE AMOUNT OF
 OPENINGS BASED ON THE SEPARATION DISTANCE. WHEN FACING
 PUBLIC RIGHT OF WAYS STREETS OR ALLIES AN ASSUMED
 PROPERTY LINE IS TAKEN FROM THE CENTER OF THE STREET OR
 ALLEY WAY OR IN THIS CASE 7?-0? FROM THE
 PROPERTY LINE, ALSO SEE FOOTNOTE (A) THE VALUES
 INDICATED ARE THE PERCENTAGE OF THE AREA OF THE
 EXTERIOR WALL, PER STORY.
  
 7F) TRASH TERMINATION ROOM # 117 HAS (2) DOORS A SWING
 DOOR LISTED AS 117 WHILE THE OVERHEAD DOOR DOES NOT
 HAVE A IDENTIFICATION TAG, NOR DOOR RATING AS REQUIRED
 BY 2010 FBC-B 70813.4.
  
 7G) THE DOOR 101 SEPARATING THE S2 STORAGE OCCUPANCY
 FROM THE BUSINESS OCCUPANCY IS MISSING THE DOOR RATING
 ON THE DOOR SCHEDULE, PAGE 126 A.7.1.1. 2010 FBC-B
 TABLE 715.4.
  
 7H) THIS NOTE IS COMMON FOR ALL FLOORS. IN REVIEWING
 THE VARIOUS DOORS IN EXIT ENCLOSURES FOR THERE FIRE
 RATINGS IN THE DOOR SCHEDULE LISTED ON PAGE 126 A7.1.1
 THERE IS A NOTE # 1 FOR HARDWARE SETS REFER TO
 SPECIFICATIONS. PLEASE NOTE SPECIFICATIONS ARE
 SOMETHING WE NORMALLY DO NOT REVIEW SINCE THEY CAN BE
 SEVERAL HUNDRED PAGES IN LENGTH. PLEASE PROVIDE A
 HARDWARE SCHEDULE THAT RELATES TO THE DOOR SCHEDULE SO
 CODE COMPLIANCE CAN BE REVIEWED. NORMALLY
 SPECIFICATIONS ARE STAMPED VOID NOT REVIEWED.
 7I) PLEASE PROVIDE THE 1ST FLOOR SQ. FOOTAGE VERSES THE
 OWNERS STORAGE LOCKER AREA TO SEE IF THIS AREA
 QUALIFIES AS AN MIXED USE OCCUPANCY REQUIRING
 SEPARATION. 2010 FBC-B 508.2.1.
 7J) HORIZONTAL TRELLIS FOUND ON THE SOUTH & WEST SIDES
 OF THE BUILDING SEE SECTION 6,8 & 9 PAGE A7.5.4. PLEASE
 SHOW WIND DESIGN AND ANCHORING DETAILS. FBC-B
 1609.6.4.4.1 COMPONENTS & CLADDING. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7K) NOTE!!! THE FPL VAULT TO BE BUILT TO THE AGREEMENT
 BETWEEN FPL AND PROPERTY OWNER.
 7L) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: F]
 914.1.1 EXTERIOR ACCESS TO SHAFTWAYS. OUTSIDE OPENINGS
 ACCESSIBLE TO THE FIRE DEPARTMENT AND THAT OPEN
 DIRECTLY ON A HOISTWAY OR SHAFTWAY COMMUNICATING
 BETWEEN TWO OR MORE FLOORS IN A BUILDING SHALL BE
 PLAINLY MARKED WITH THE WORD ?SHAFTWAY? IN RED LETTERS
 AT LEAST 6 INCHES (152 MM) HIGH ON A WHITE BACKGROUND.
 SUCH WARNING SIGNS SHALL BE PLACED SO AS TO BE READILY
 DISCERNIBLE FROM THE OUTSIDE OF THE BUILDING.
 7M) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: F
 914.1.2 INTERIOR ACCESS TO SHAFTWAYS. DOOR OR WINDOW
 OPENINGS TO A HOISTWAY OR SHAFTWAY FROM THE INTERIOR OF
 THE BUILDING SHALL BE PLAINLY MARKED WITH THE WORD
 ?SHAFTWAY? IN RED LETTERS AT LEAST 6 INCHES (152 MM)
 HIGH ON A WHITE BACKGROUND. SUCH WARNING SIGNS SHALL BE
 PLACED SO AS TO BE READILY DISCERNIBLE.
 7N) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F]
 914.2 EQUIPMENT ROOM IDENTIFICATION. FIRE PROTECTION
 EQUIPMENT SHALL BE IDENTIFIED IN AN APPROVED MANNER.
 ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS,
 SPRINKLER RISERS AND VALVES OR OTHER FIRE DETECTION,
 SUPPRESSION OR CONTROL ELEMENTS SHALL BE IDENTIFIED FOR
 THE USE OF THE FIRE DEPARTMENT. APPROVED SIGNS REQUIRED
 TO IDENTIFY FIRE PROTECTION EQUIPMENT AND EQUIPMENT
 LOCATION SHALL BE CONSTRUCTED OF DURABLE MATERIALS,
 PERMANENTLY INSTALLED AND READILY VISIBLE.
 7O) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F]
 915.1 GENERAL. [F] 915.1 GENERAL.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE
 PREVENTION CODE.
  
 7P) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B 916.1
 CARBON MONOXIDE PROTECTION. EVERY SEPARATE BUILDING OR
 AN ADDITION TO AN EXISTING BUILDING FOR WHICH A PERMIT
 FOR NEW CONSTRUCTION IS ISSUED AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR
 ELEMENT THAT EMITS CARBON MONOXIDE AS A BYPRODUCT OF
 COMBUSTION SHALL HAVE AN OPERATIONAL CARBON MONOXIDE
 ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES IN THE NEW BUILDING OR ADDITION, OR
 AT SUCH OTHER LOCATIONS AS REQUIRED BY THIS CODE.
  
 8) 2ND FLOOR, PAGE 025 LS-2-0, 035 A2-2-1,& A-2-2-2.
 8A) THE HANDICAPPED SPACE # 58 DOES NOT HAVE A 5?-0?
 CLEAR ACCESS AISLE NEXT TO IT, THERE IS A COLUMN IN THE
 WAY AT GRID LINE C.6 AND 1.5. NOTE THE COLUMN IS 3FT 3
 INCHES FROM THE ACCESSIBLE PARKING SPACE, EVEN THOUGH
 THE AISLE IS WIDER IF THE COLUMN IS AT A POINT WHERE
 THE DOOR CANNOT BE OPENED NOR A VANS ACCESSIBLE
 PLATFORM CANNOT BE LOWERED.
 8B) THERE IS (2) AREAS NOT CLEAR AS TO WHERE THE
 CEILING IS LOCATED OR IF THE BLOCK WALL GOES ALL THE
 WAY TO THE 3RD FLOOR. SEE FPL TRANSFORMER VAULT AND
 SWITCHGEAR/ ELECTRIC ROOM. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
 9) PAGE 026 LS-3.0, PAGE 038 A2.3.1 & PAGE 039 A2.3.2:
 9A) DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED
 COMMON AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE
 UNIT. THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON
 THE LATCH SIDE OF THE DOOR, PER FAIR HOUSING
 REQUIREMENT 3. USABLE DOORS. GUIDELINE SECTION
 100.205(C)(2) WOULD APPLY TO DOORS THAT ARE A PART OF
 AN ACCESSIBLE ROUTE IN THE PUBLIC AND COMMON USE AREAS
 OF MULTIFAMILY DWELLINGS AND TO DOORS INTO AND WITHIN
 INDIVIDUAL DWELLING UNITS.
 (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS
 AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS
 THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT.
 9B)NOTE THIS WILL BE A COMMON STATEMENT FOR ALL UNITS
 FOUND ON:
 PAGE 078 A6.1.2 UNIT 301 & 302
 PAGE 080 A6.2.2 UNIT 303 & 304
 PAGE 083 A6.3.2 UNIT 305 & 306
 PLEASE NOTE THE TENANT SEPARATION WALLS FOR THIS FLOOR
 INDICATE A 1 HOUR FIRE RATING BUT THE DOOR SCHEDULE FOR
 THE TYPICAL DWELLING UNIT DOORS SHOWS THE ENTRY DOOR AS
 WELL AS THE A/C CLOSET DOOR THAT IS WITHIN THE TENANT
 SEPARATION WALL BOTH SHOW 20 MIN. DOORS. FBC-B TABLE
 715.4 DOES ALLOW FOR 20 MIN. DOORS INTO CORRIDORS FOR A
 GENERAL RULE. SECTION 709.3 FIRE RESISTANCE RATINGS AS
 WELL IN EXCEPTION # 1 ALLOWS FOR CORRIDOR WALLS TO BE ?
 HR. RATED. EXCEPTION # 2 FOR DWELLING UNITS DOES NOT
 GIVE THE REDUCTION FOR TYPE I BUILDINGS, THE REDUCTION
 CAN ONLY TAKE PLACE IN TYPE IIB, IIIB AND VB.
 10) PAGE 027 LS 4.0, PAGE 041 A2.4.1 & PAGE 042 A2.4.2:
 NOTE: COMMENTS FOR THE 4TH FLOOR WILL ALSO STAND FOR
 THE 6TH FLOOR.
  
 10A) THE COMMON CMU WALL BETWEEN THE PARKING GARAGE AND
 OPEN AIR 3RD STORY DWELLING UNITS (CLEARSTORY) IS A 2
 HOUR FIRE RATED WALL. THE STRUCTURAL SHEETS SHOW
 DETAILS OF THIS WALL PAGE 171 S2.40 SHOWS A DETAIL #7
 FOUND ON S5-10. THIS DETAIL SHOW A REINFORCED CONCRETE
 POURED 8 INCH WALL TO COMPLY WITH FBC-B 1607.7.3
 VEHICLE BARRIER SYSTEMS. THERE ARE (2) POINTS OF
 LOADING TO CONSIDER, PLEASE PROVIDE HOW THE 2ND IS MET:
 THE SECOND LOADING CONDITION SHALL APPLY THE LOAD AT 2
 FEET, 3 INCHES (686 MM) ABOVE THE FLOOR OR RAMP
 SURFACE. THE MORE SEVERE LOAD CONDITION SHALL GOVERN
 THE DESIGN OF THE BARRIER.
 10B) THE 2ND COMMENT DEALS WITH AN ACCESSIBLE PARKING
 SPACE AND ACCESS AISLE NEXT TO STAIR # 3. THE FAIR
 HOUSING REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC AND
 COMMON USE AREAS. ANSI 117.1 GENERAL SITE AND BUILDING
 ELEMENTS. SECTION 503.3 ACCESS AISLES. WIDTH 503.3.1 60
 INCHES/ LENGTH 503.3.2 20 FT. LONG MINIMUM.
 11) PAGE 028 LS 5.0, PAGE 044 A2.5.1 & PAGE 045 A2.5.2:
 11A) DOORS 507.02 & 507.03 BOTH DOORS ARE CONSIDERED
 COMMON AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE
 UNIT. THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON
 THE LATCH SIDE OF THE DOOR, PER FAIR HOUSING
 REQUIREMENT 3. USABLE DOORS. GUIDELINE SECTION
 100.205(C)(2) WOULD APPLY TO DOORS THAT ARE A PART OF
 AN ACCESSIBLE ROUTE IN THE PUBLIC AND COMMON USE AREAS
 OF MULTIFAMILY DWELLINGS AND TO DOORS INTO AND WITHIN
 INDIVIDUAL DWELLING UNITS.
 (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS
 AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS
 THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT.
  
 11B)NOTE THIS WILL BE A COMMON STATEMENT FOR ALL UNITS
 FOUND ON:
 PAGE 078 A6.1.2 UNIT 501 & 502
 PAGE 080 A6.2.2 UNIT5303 & 504
 PAGE 083 A6.3.2 UNIT 505 & 506
 PLEASE NOTE THE TENANT SEPARATION WALLS FOR THIS FLOOR
 INDICATE A 1 HOUR FIRE RATING BUT THE DOOR SCHEDULE FOR
 THE TYPICAL DWELLING UNIT DOORS SHOWS THE ENTRY DOOR AS
 WELL AS THE A/C CLOSET DOOR THAT IS WITHIN THE TENANT
 SEPARATION WALL BOTH SHOW 20 MIN. DOORS. FBC-B TABLE
 715.4 DOES ALLOW FOR 20 MIN. DOORS INTO CORRIDORS FOR A
 GENERAL RULE. SECTION 709.3 FIRE RESISTANCE RATINGS AS
 WELL IN EXCEPTION # 1 ALLOWS FOR CORRIDOR WALLS TO BE ?
 HR. RATED. EXCEPTION # 2 FOR DWELLING UNITS DOES NOT
 GIVE THE REDUCTION FOR TYPE I BUILDINGS, THE REDUCTION
 CAN ONLY TAKE PLACE IN TYPE IIB, IIIB AND VB.
  
 11C) THIS COMMENT WILL BE A COMMON COMMENT FOR ALL
 FLOORS,(FLOOR SLABS ARE 8 INCH POST TENSION SLABS) THE
 3RD -16TH STORY. PLEASE PROVIDE COMPLIANCE WITH BLDG
 TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
  
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 12) PAGE 030 LS 7.0, PAGE 050 A2.7.1 & PAGE 051 A2.7.2:
 12A) COMMON ROOM 701.01 APPROXIMATELY 1286 SQ. FT./ 15=
 85 OCCUPANTS, THIS ROOM WILL REQUIRE 2 EXITS. NOTE ONE
 EXIT IS THROUGH THE ELEVATOR LOBBY (700) TO STAIR 701.
 THE LIFE SAFETY SHEET DOES NOT SHOW EXITING FOR THIS
 ROOM. 708.14.1 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE
 MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER
 PROVISIONS WITHIN THIS CODE. IN REALITY STAIRWELL 701
 CANNOT BE USED FOR THIS FLOOR AS DEPICTED!
 12B) THE POOL DECK AND POOL SURFACE AREA TOTAL OCCUPANT
 LOAD EQUAL A TOTAL OF 121 OCCUPANTS. PLEASE PROVIDE THE
 (2) MEANS OF EGRESS WITHOUT GOING THROUGH THE ELEVATOR
 LOBBY. IN REALITY STAIRWELL 701 CANNOT BE USED FOR THIS
 FLOOR AS DEPICTED!
 12C) EXIT ROUTE # 07 WEST TRAVELS THROUGH THE ELEVATOR
 LOBBY. . 708.14.1 ELEVATOR LOBBIES SHALL HAVE AT LEAST
 ONE MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER
 PROVISIONS WITHIN THIS CODE. IN REALITY STAIRWELL 701
 CANNOT BE USED FOR THIS FLOOR AS DEPICTED!
 12D) DOOR 706F DOES NOT COMPLY WITH THE FAIR HOUSING
 GUIDE LINES REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC
 AND COMMON USE AREAS. ANSI A117.1 TABLE 404.2.4.1
 MANEUVERING CLEARANCES FOR MANUAL SWING DOORS.
 12E) NOTE THIS POOL DECK AND POOL ARE COVERED UNDER THE
 FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY REQUIRES
 ACCESS MUST BE PROVIDED TO THE POOL DECK AREA, NOT AN
 ACCESSIBLE ROUTE(RAMP OR LIFT) DOWN INTO THE WATER INTO
 THE POOL. ON THE OTHER HAND IF THE ASSOCIATION ELECTS
 TO ALLOW THE COMMUNITY ROOM, POOL, AND OR POOL DECK TO
 BE RENTED OUT FOR PARTIES THAT THE PUBLIC COULD USE,
 THEN THIS AREA WOULD BE REQUIRED TO MEET FLORIDA
 ACCESSIBILITY SECTION 1009 OF THE ACCESSIBILITY CODE
 POOL LIFTS.
 12F) THIS NOTE WILL BE A COMMON NOTE FOR FLOORS 7-20TH
 FLOORS. THE DOOR SCHEDULE FOUND ON PAGE 126 A.7.1.1
 (DOOR SCHEDULE) IN THE REMARKS COLUMN THERE ARE VARIOUS
 DOORS IN THE CORRIDOR THAT STATE THAT A FIRE DAMPER IS
 TO BE INSTALLED IN THE LOUVERED DOOR. PLEASE SHOW
 COMPLIANCE WITH:
  
 2010 FBC-B 715.4.6 LABELED PROTECTIVE ASSEMBLIES. FIRE
 DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED AGENCY.
 THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL BE
 PERMANENTLY AFFIXED TO THE DOOR OR FRAME INSTALLED
 WITHIN THE LOUVERED DOOR.
  
 716.5.2 FIRE BARRIERS. DUCTS AND AIR TRANSFER OPENINGS
 OF FIRE BARRIERS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING.
  
 12G) PAGE 023 LS-0.1 LIST THE REQUIRED FIRE SEPARATION
 DISTANCE FOR THE REQUIRED HOURLY RATING AND AMOUNT OF
 ALLOWABLE OPENINGS. SHEET A2-7.2 THE EAST PROPERTY LINE
 WALL IS APPROX. 13 FEET AWAY FROM THE OPENINGS, FBC-B
 TABLE 705.8 ALLOWS 45% UNPROTECTED SPRINKLERED, PLEASE
 PROVIDE THE PERCENTAGE OF ALLOWABLE OPENING TAKEN PER
 FLOOR LEVEL.
 13) PAGE 031 LS 8.0, PAGE 053 A2.8.1 & PAGE 054 A2.8.2.
 8TH-20TH FLOORS COMMON TO ALL FLOORS.
 13A) THIS PAGE SHOWS SLIDING GLASS DOOR (SGD 6) IN UNIT
 815 BEDROOM # 02, THE DOOR SCHEDULE (129 A7.3.1)
 INDICATES THIS SLIDING GLASS DOOR IS A 6FT. 4 IN. IS
 THIS A ROUGH OPENING SIZE OR OUTSIDE DOOR JAMB OPENING,
 NOT CLEAR. IN THE FAIR HOUSING GUIDE THE EXTERIOR
 SLIDING GLASS DOORS WILL NEED TO MEET REQUIREMENT # 4
 (2)
 A MINIMUM CLEAR WIDTH OF 32 INCHES IS PROVIDED.
  
 13B) FOR ALL SLIDING GLASS DOORS THE HARDWARE WILL ALSO
 NEED TO MEET THE ANSI 117.1 STANDARD 404.2.7.
  
 14) PAGE 056 A.2.9.1:
  
 14A) ROOF NOTE # 3 :
 THE NO LESS THAN R-10 IN ANY LOCATION LIKE ROOF DRAINS
 STILL HAS TO HAVE A MINIMUM OF R-19 INSULATION. SEE THE
 2010 FBC-ENERGY CODE 506.2.1 UNDER TOTAL BUILDING
 PERFORMANCE METHOD.
 SEE BOAF INFORMAL INTERPRETATION # 5438
  
 DATE: TUE NOV 13 2007
 REPORT #: 5438
 CODE: BUILDING
 SECTION: 404.1.A
 QUESTION:
 IS IT THE INTENT OF THE CODE "....THE INSULATION SHALL
 HAVE A R-VALUE OF AT LEAST R-19, SPACE PERMITTING." TO
 MEAN THE MINIMUM R-VALUE OF ROOF INSULATION TO BE R-19
 AT LOWEST POINTS AT DRAINS? ALL ROOFERS WHO WE HAVE
 SPOKEN TO, INTERPRETED THIS CODE AS MINIMUM AVERAGE
 R-19, NOT MINIMUM R-19 AND HAVE DONE MOST ROOFING JOB
 ACCORDINGLY. THANK YOU
 ANSWER: A MINIMUM LEVEL OF INSULATION REQUIRED IS THAT,
 A MINIMUM, NOT AN AVERAGE. HOWEVER, PROVIDED THE
 MINIMUM R-19 VALUE HAS BEEN MET, A REASONABLE AVERAGING
 PROCEDURE CAN BE USED BY ROOF AREA FOR CALCULATIONS OF
 THE VALUE.
 COMMENTARY: THIS QUESTION ACTUALLY REFERS TO SECTION
 13-404.1 (A) PRESCRIPTIVE REQUIREMENTS SPECIFIC TO
 METHOD A. THIS SECTION MANDATES COMPLIANCE WITH FLA/COM
 METHOD A, HOWEVER GIVES A PRESCRIPTIVE REQUIREMENT OF
 AN R-19 FOR MULTIFAMILY RESIDENTIAL ROOF/CEILING
 ASSEMBLY. AS SPACE PERMITS, MAY RELATE TO THE AREA OF
 THE EAVES WHERE THE R- 19 INSULATION WOULD HAVE TO BE
 COMPRESSED TO FIT IN THE SPACE AVAILABLE. HOWEVER, THE
 PETITIONER ALLUDES TO THE ROOFER INSTALLING THE
 INSULATION. THERE ARE NO SPACE CONSTRAINTS FOR
 INSULATION APPLIED TO A ROOF DECK; IT SHOULD BE R-19
 MINIMUM. IF THE BUILT-UP ROOF IS SLOPING TO A DRAIN IN
 A MANNER WHERE SOME PARTS OF THE ROOF HAVE MORE THAN
 R-19 AND SOME HAVE LESS, THEN THE RESIDENT WHOSE
 APARTMENT/CONDO IS UNDER THE ROOF SECTION WITH LESS
 THAN R- 19 WOULD BE PENALIZED WITH HIGHER HEAT LOADS
 AND HIGHER ENERGY COSTS THAN THEIR NEIGHBOR.
  
 14B) ROOF NOTE # 6 REFERENCES THE USE OF CHEN-CURB OR
 EQUAL FOR PIPE OR TUBE ROOF PENETRATIONS. THE PRODUCT
 SPECIFIED HAS TO BE SPECIFIC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 14C) ROOF DRAINAGE CALCULATIONS DO NOT PROVIDE THE RATE
 OF RAINFALL PER HR. THE CHARTS WERE DESIGN FOR.
 P] 1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE SLOPED TO
 DRAIN OVER ROOF EDGES, DESIGN AND INSTALLATION OF ROOF
 DRAINAGE SYSTEMS SHALL COMPLY WITH SECTION 1503 AND THE
 FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11.
  
 14D) THE QUESTION IS THE TOP OF ROOF DRAINS IS SHOWN AS
 MINUS INCHES FROM THE TOP OF ROOF, FOR EXAMPLE BOTH
 AREAS OF THE ROOF DESIGNATED AS N & P BOTH SHOW A -7
 INCHES T.O.D. OR -7 INCHES FROM THE TOP OF THE HIGHEST
 ROOF DECK WHERE THE DECK ADJOINS TO THE PARAPET WALL.
 DETAIL 5/ A7.5.1 SHOWS THE EMERGENCY OVERFLOW SET AN
 ADDITIONAL 2 INCHES ABOVE THE 7 INCHES TOP OF DRAIN OR
 9 INCHES OF DEPTH OF WATER BEFORE WATER CAN START TO
 OVERFLOW THE EMERGENCY ROOF SCUPPERS. IN ROOF ZONE P,
 THIS IS APPROXIMATELY 42,553 LBS. OF WATER WEIGHT.
  
 FBC-B 1503.4.2.1 WHEN LOOKING AT THIS SECTION THE
 INTENT IS WHEN THE ROOF IS SLOPED TO A SCUPPER THE, THE
 SCUPPER SHALL BE PLACED LEVEL (1503.4.2) TO THE ROOF
 DECK. THE EMERGENCY OVERFLOW SCUPPERS ARE TO BE PLACED
 2 -4 INCHES ABOVE THE SCUPPER. THIS IS A COMMON MISTAKE
 WHEN APPLYING 1503.4.1 SECONDARY DRAINAGE REQUIRED. IF
 THE ROOF DRAINS ARE TO BE THE PRIMARY DRAIN THEN
 SHOULDN?T THE EMERGENCY OVERFLOW SCUPPERS BE PLACED 2
 TO 4 INCHES ABOVE THE DRAIN? IF USING A SECONDARY ROOF
 DRAIN THAT IS HOW IT WOULD BE SET UP 2 TO 4 INCHES
 ABOVE THE ROOF DRAIN.
  
 14E) THE PLANS INDICATE THE USE OF PRE-ENGINEERED A/C
 STANDS. WHEN FIGURING THE REQUIRED CLEARANCES IN HEIGHT
 REQUIRED BY TABLE FBC-B 1509.7, THE CLEARANCE IS FROM
 THE FINISHED ROOF HEIGHT, ABOVE THE LIGHTWEIGHT
 CONCRETE ROOF.
  
 15) THIS IS MORE OF A CONCERN FOR THE FIRE DEPARTMENT
 AS TO HOW THE FIRE DEPARTMENT WILL BE ABLE TO GAIN
 ENTRY WHEN THE TILT GATES TO THE GARAGE ARE DOWN? WILL
 THE GARAGE TILT GATES BE ON EMERGENCY POWER CIRCUITRY?
 IN THE EVENT OF GATE FAILING TO OPEN HOW WILL EGRESS TO
 MAINTAINED ? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED?
  
 16) PAGES 126 A7-1-1, 127 A7-2-1, 129 A7-3-1, 130
 A7-3-2, 131 A7-3-3 & 132 A7-4-1. ALL OF THESE SHEETS
 DEAL WITH THE EXTERIOR OF THE BUILDING AND WITH
 COMPONENTS & CLADDING.
  
 16A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 16B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 16C) IF EITHER THE CONTRACTOR OR DESIGNER OF RECORD
 WISH TO DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT
 ISSUANCE PLEASE INFORM SO IN WRITING.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION. 107.3.4.3
 CERTIFICATIONS BY CONTRACTORS AUTHORIZED UNDER THE
 PROVISIONS OF SECTION 489.115 FLORIDA STATUTES, SHALL
 BE CONSIDERED EQUIVALENT TO SEALED PLANS AND
 SPECIFICATIONS BY A PERSON LICENSED UNDER CHAPTER 471,
 FLORIDA STATUTES, OR CHAPTER 481 FLORIDA STATUTES, BY
 LOCAL ENFORCEMENT AGENCIES FOR PLANS REVIEW FOR
 PERMITTING PURPOSES RELATING TO COMPLIANCE WITH THE
 WIND-RESISTANCE PROVISIONS OF THE CODE OR ALTERNATE
 METHODOLOGIES APPROVED BY THE FLORIDA BUILDING
 COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS. LOCAL
 ENFORCEMENT AGENCIES MAY RELY UPON SUCH CERTIFICATION
 BY CONTRACTORS THAT THE PLANS AND SPECIFICATIONS
 SUBMITTED CONFORM TO THE REQUIREMENTS OF THE CODE FOR
 WIND RESISTANCE. UPON GOOD CAUSE SHOWN, LOCAL
 GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT OR
 REJECT PLANS SEALED BY PERSONS LICENSED UNDER CHAPTERS
 471,481 OR 489, FLORIDA STATUTES.
  
 17) PAGES 163 S1.13 AND 164 S1.14. NOTE # 1 ON THESE
 SHEETS INDICATE THE PRESSURES WERE CALCULATED USING THE
 CALCULATED BY CODE ANALYTICAL METHODS. THIS TERM
 ANALYTICAL METHOD DOES NOT SHOW UP IN THE CODE WHEN A
 WORD SEARCH IS COMPLETED. IT WOULD APPEAR THAT A WIND
 TUNNEL TEST WAS COMPLETED AS ALLOWED BY FBC-B 1609.1.1
 EXCEPTION 6. WIND TUNNEL TEST ARE TO BE IN ACCORDANCE
 WITH CHAPTER 31 OF ASCE 7. PLEASE PROVIDE THE SIGNED
 AND SEALED WIND TUNNEL TEST OR PROVIDE HOW THESE
 PRESSURES WERE DERIVED.
  
 18) PAGE 165 THE FOUNDATION PLAN SHOWS ALL PILE CAP
 DIRECTLY ON THE PROPERTY LINE. A REVISION MAY BE
 REQUIRED. THE SOILS REPORT INDICATES THAT THIS SITE HAS
 LOOSE SOILS AND BECAUSE OF THE CLOSENESS OF OTHER
 BUILDINGS AROUND THE SITE, VIBROFLOTATION WAS NOT
 RECOMMENDED AND AUGERED CAST PILES CAST IN PLACE SHOULD
 BE USED TO SUPPORT THE STRUCTURE. THE SOILS REPORT WENT
 IN DEPTH OF HOW THE UTILITIES IN THE ALLEY WOULD NEED
 TO BE SUPPORTED AND HOW TO COMPLETE THIS TASK.
  
 LAST WEEK (MAY 12/2015) IN A MEETING WITH MATT STILL
 THE PROJECT MANAGER , MATT SPOKE ABOUT THE POSSIBLE USE
 OF SHEET PILING AROUND THE PERIMETER OF THE PROJECT.
 THIS WILL HAVE THE SAME EFFECT AS VIBROFLOTATION AS TO
 DAMAGE TO STRUCTURES IN THE VICINITY OF THE PROJECT. A
 RESOLUTION ON THIS MATTER WILL NEED TO TAKE PLACE IF
 SHEET PILE ARE GOING TO BE INSTALLED AROUND THE
 PERIMETER, THIS WILL AFFECT THE PLACEMENT OF THE PILE
 AND PILE CAPS.
  
 19) PAGE A7.5.3 ;
 19A) NOTE: THE POOL TRELLIS STRUCTURE (PERGOLA) THIS
 DETAIL INDICATES IT IS GOING TO BE DESIGNED BY A
 SPECIALTY ENGINEER. BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT, THE PLANS WILL NEED TO BE REVIEWED BY THE
 ENGINEER OF RECORD. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 19B) THE POOL TRELLIS STRUCTURE (PERGOLA) THIS
 STRUCTURE INDICATES THE USE OF A PLEXIGLASS RAIN GUARD.
 PLEASE PROVIDE HOW THE PLEXIGLASS RAIN GUARD WILL MEET
 THE FIRE RESISTANCE RATINGS REQUIRED BY FBC-B TABLE 601
 AND FBC-B TABLE 1505.1.ALSO SEE FBC-B 2610 2610.4. WILL
 THERE BE FIRE SPRINKLERS BENEATH THIS STRUCTURE.
  
 20) PAGE 136 A7.5.4.
 20A) DETAIL # 5 RIGID ALUMINUM CANOPY WITH FABRIC
 WRAPPED WILL REQUIRE WIND DESIGN CRITERIA SEE OPTIONS
 FOUND UNDER FBC-B 3105.4 . ALSO: FL 61G-15-30.006 (3)
 THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 20B) DETAIL # 5 RIGID ALUMINUM CANOPY WITH FABRIC
 WRAPPED WILL NEED TO MEET THE REQUIREMENTS OF 3105.3.1
 FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL
 MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA
 701.
  
 21) PAGE 137 A7.5.5 DETAIL # 10 THE BALCONY EDGE
 ALUMINUM RAILING DOES NOT HAVE THE DESIGN CRITERIA THAT
 WILL BE REQUIRED TO MANUFACTURER, THE BALCONY RAIL WILL
 NEED TO MEET THE FOLLOWING :
 FBC-B 1607.7.1.1 CONCENTRATED LOAD & . 1607.7.1.2
 COMPONENTS.
  
 22) PAGE 139 A9.1.1 STAIRWELL NUMBER 1 DOES NOT SHOW
 THE STANDPIPE IN THE STAIRWELL NOR ARE THERE ANY NOTES
 ONE IS REQUIRED. FBC-B 905.3.1. THIS COMMENT STAND FOR
 ALL STAIRWELLS. PLEASE NOTE THE ONLY PENETRATIONS
 ALLOWED IN THE STAIRWELL ARE TOUGHS THAT COMPLY WITH:
  
 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 23) PAGE 153 A11.2:
 23A) DETAIL # 1 THE TRASH TERMINATION ROOM, SHOW A
 STAINLESS STEEL ROLLING FIRE DOOR WITH 165 DEGREE
 FUSIBLE LINK, THE PLANS DO NOT INDICATE WHAT THE FIRE
 DOOR IS RATED TOO? FBC-B TABLE 715.4.
  
 23B) THE THROUGH THE FLOOR FIRE PROOFING DETAIL
 INDICATE THE USE OF MINERAL WOOL INSULATION PLEASE
 PROVIDE A LISTED ASSEMBLY FOR A 2?-0? DIAMETER STEEL
 TRASH CHUTE, NOT FOUND ON THE UL ASSEMBLY SHEET. FBC-B
 713.4.1.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION
 713.4.1.1.1 OR 713.4.1.1.2.
  
 23C) THROUGH PENETRATION OF FLOOR SLAB FOR TUB DRAIN IF
 TRAP IS WITHIN THE FLOOR ASSEMBLY IS NOT PROVIDED ON
 THE UL ASSEMBLY SHEETS NOR P5.1.2. THROUGH PENETRATIONS
 OF FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH SECTION 713.4.1.1.1 OR 713.4.1.1.2.
 24) PLEASE PROVIDE WHERE THE FOLLOWING REQUIREMENTS FOR
 HIGH RISE CONSTRUCTION CAN BE FOUND:
 24A)FBC-B 403.3.2 WATER SUPPLY TO REQUIRED FIRE PUMPS.
 REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO
 A MINIMUM OF TWO WATER MAINS LOCATED IN DIFFERENT
 STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED
 BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE
 PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN
 THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY
 THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO
 OPERATE.
  
 24B) FBC-B [F] 403.4.3 EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM.
 AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 24C) FBC-B [F] 403.4.4 EMERGENCY RESPONDER RADIO
 COVERAGE.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 24D) FBC-B 403.4.6 SMOKE REMOVAL. SMOKE CONTROL SHALL
 BE PROVIDED IN ACCORDANCE WITH SECTION 909.
  
  
 24E) FBC-B [F] 403.4.7 STANDBY POWER.
 A STANDBY POWER SYSTEM COMPLYING WITH CHAPTER 27 SHALL
 BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN
 SECTION 403.4.7.2.
  
 24F) FBC-B [F] 403.4.7.2 STANDBY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS:
 1. POWER AND LIGHTING FOR THE FIRE COMMAND CENTER
 REQUIRED BY SECTION 403.4.5;
 2. VENTILATION AND AUTOMATIC FIRE DETECTION EQUIPMENT
 FOR SMOKEPROOF ENCLOSURES; AND
 3. STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN
 ACCORDANCE WITH SECTIONS 1006.2.4, 3003, 3007 AND 3008.
  
 24G) [F] 403.4.8 EMERGENCY POWER SYSTEMS. AN EMERGENCY
 POWER SYSTEM COMPLYING WITH CHAPTER 27 SHALL BE
 PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED IN SECTION
 403.4.8.1.
 [F] 403.4.8.1 EMERGENCY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS:
 1. EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION REQUIRED
 BY CHAPTER 10;
 2. ELEVATOR CAR LIGHTING;
 3. EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS;
 4. AUTOMATIC FIRE DETECTION SYSTEMS;
 5. FIRE ALARM SYSTEMS; AND
 6. ELECTRICALLY POWERED FIRE PUMPS.
  
  
 24H) FBC-B 403.5.3.1 STAIRWAY COMMUNICATION SYSTEM.
 A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM
 CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION
 SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN
 EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY ARE
 LOCKED.
  
 24I) FBC-B 403.5.4 SMOKEPROOF EXIT ENCLOSURES. EVERY
 REQUIRED EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET
 (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS SHALL COMPLY WITH SECTIONS 909.20 AND
 1022.9.
 24J) FBC-B 1022.8 FLOOR IDENTIFICATION SIGNS. /
 1022.8.1 SIGNAGE REQUIREMENTS.
  
 24K) FBC-B 403.5.5 LUMINOUS EGRESS PATH MARKINGS.
 LUMINOUS EGRESS PATH MARKINGS SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 1024.1-5.
 1024.4 SELF-LUMINOUS AND PHOTOLUMINESCENT. LUMINOUS
 EGRESS PATH MARKINGS SHALL BE PERMITTED TO BE MADE OF
 ANY MATERIAL, INCLUDING PAINT, PROVIDED THAT AN
 ELECTRICAL CHARGE IS NOT REQUIRED TO MAINTAIN THE
 REQUIRED LUMINANCE. SUCH MATERIALS SHALL INCLUDE, BUT
 ARE NOT LIMITED TO, SELF-LUMINOUS MATERIALS AND
 PHOTOLUMINESCENT MATERIALS. MATERIALS SHALL COMPLY WITH
 EITHER:
 1. UL 1994; OR
 2. ASTM E 2072, EXCEPT THAT THE CHARGING SOURCE SHALL
 BE 1 FOOTCANDLE (11 LUX) OF FLUORESCENT ILLUMINATION
 FOR 60 MINUTES, AND THE MINIMUM LUMINANCE SHALL BE 30
 MILLICANDELAS PER SQUARE METER AT 10 MINUTES AND 5
 MILLICANDELAS PER SQUARE METER AFTER 90 MINUTES.
  
 1024.5 ILLUMINATION.EXIT ENCLOSURES WHERE
 PHOTOLUMINESCENT EXIT PATH MARKINGS ARE INSTALLED SHALL
 BE PROVIDED WITH THE MINIMUM MEANS OF EGRESS
 ILLUMINATION REQUIRED BY SECTION 1006 FOR AT LEAST 60
 MINUTES PRIOR TO PERIODS WHEN THE BUILDING IS OCCUPIED.
  
 25) [F] 3311.1 WHERE REQUIRED. IN BUILDINGS REQUIRED TO
 HAVE STANDPIPES BY SECTION 905.3.1, NOT LESS THAN ONE
 STANDPIPE SHALL BE PROVIDED FOR USE DURING
 CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED WHEN
 THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40 FEET
 (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF FIRE
 DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE
 PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT
 ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
  
 26) [F] 3312.1 COMPLETION BEFORE OCCUPANCY.
 IN BUILDINGS WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 REQUIRED BY THIS CODE, IT SHALL BE UNLAWFUL TO OCCUPY
 ANY PORTION OF A BUILDING OR STRUCTURE UNTIL THE
 AUTOMATIC SPRINKLER SYSTEM INSTALLATION HAS BEEN TESTED
 AND APPROVED, EXCEPT AS PROVIDED IN SECTION 111.3.
  
 27) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 28) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 29) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 30) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  