Date |
Text |
2015-04-03 12:05:25 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| 1) SHEET T INDICATES INCORRECT FIRE CODE REFERENCES. |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2009 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2010 EDITION. |
| |
| 2) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF |
| THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE |
| AND COMPLIANCE. |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| |