Plan Review Notes For Permit 15031274 |
Permit Number |
15031274 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-04 19:38:55 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. SEE FBC 2010 RESIDENTIAL 311.7.7.3; HANDRAIL TO | | COMPLY WITH THE REQUIREMENTS FOR GRIP SIZE. SHOW ALL | | DIMENSIONS. | | | | 2. THE DETAILS HAVE BEEN REDUCED AND ARE DIFFICULT TO | | READ. REFER TO ISSUED PERMIT FOR AN EXAMPLE OF | | LEGIBILITY, FBC 107. | | | | 3. THERE IS A NOTE ON THE PLAN WHICH STATES THAT THESE | | STAIRS ARE AN EXACT REPLACEMENT. DUE TO THE EXTENT OF | | REPAIR, THIS MAY NOT BE PERMITTED IF THE STAIR DOES NOT | | COMPLY WITH THE REQUIREMENTS OF FBC 2010 RESIDENTIAL | | 311. | | | | ELEMENTS WHICH DO NOT COMPLY WITH THE REQUIREMENTS FOR | | NEW STAIRS, IF ANY SUCH ITEMS EXIST, ARE TO BE NOTED ON | | THE PLAN AND CLOUDED OR OTHERWISE CLEARLY INDICATED FOR | | CONSIDERATION. | | | | 4. REMOVE THE STATEMENT IN "SCOPE OF WORK" WHICH STATES | | THAT "ALL RISERS ARE OPEN" AS THAT IS NOT PERMITTED AND | | DRAWING HAS ALREADY BEEN MODIFIED BY ENGINEER. | | | | 5. PROVIDE A REASONABLE VALUE FOR THE PERMIT (15010077) | | OR PROVIDE AN ITEMIZED ESTIMATE TO JUSTIFY $900 VALUE, | | FBC 109. | | | | | | | | |
|