2015-06-27 14:37:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1- REVISE BUILDING EXPOSURE AND ALL DESIGN PRESSURES. |
| 2- PROVIDE COMPLETE DETAILS & SPECIFICATIONS FOR THE |
| OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND |
| OFFICE. SEC. R302.5. |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR (NOTE: ALL |
| PRODUCT APPROVALS WILL BE RE-REVIEWED WHEN ALL DESIGN |
| PRESSURES ARE REVISED). |
| A) CUSTOM MADE ENTRY DOOR ASSEMBLY. NEED TO PROVIDE |
| COMPLETE ENGINEER PACKAGE FOR BUILDING OFFICIAL |
| REVIEW/APPROVAL. CONTACT ROBERT BROWN (BUILDING |
| OFFICIAL) AT [email protected]. |
| B) FIXED WINDOW SIZE SPECIFIED FOR WINDOW "F" ON THE |
| WINDOW SCHEDULE. NOA 11-1031.06 SUBMITTED DOESN'T COVER |
| THAT SIZE. |
| NOTE: WINDOW SCHEDULE CALLS FOR PGT WINDOWS. PRODUCT |
| APPROVALS SUBMITTED ARE FOR DIFFERENT MANUFACTURER. |
| REVISE AS REQUIRED. |
| C) OUTSWING GLAZED DOOR WITH SIDELITES: NEED TO PROVIDE |
| PRODUCT APPROVAL THAT COVERS SIZE FOR DOOR #4. |
| D) SLIDING GLASS DOORS WITH 3 PANELS SIZE AS SPECIFIED |
| FOR DOOR #3. |
| E) PRECAST LINTELS AS SPECIFIED ON PLANS. NOA |
| 13-0321.07 SUBMITTED IS FOR 4", 6" & 12" LINTELS. |
| 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS. |
| 5- GEO-TECHNICAL ENGINEERING REPORT SUBMITTED NEED THE |
| ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY |
| CHAPTER 471 F.S. |
| |
| NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE |
| REQUIRED DURING CONSTRUCTION. |