Date |
Text |
2015-06-19 17:01:42 | NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO. |
| BELOW COMMENTS MAY BE ADDRESSED AFTER PERMIT IS ISSUED. |
| REVISION FEES WILL APPLY. |
| |
| |
| |
| ORIGINAL COMMENT: |
| 1- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON SHEET |
| SP-1 DON'T CORRESPOND TO THE WORST CASE SCENARIO FOR |
| EXPOSURE "D". REVISE AS REQUIRED. SEC. R301.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| THE BUILDING EXPOSURE WAS CHANGED TO "C". THE BUILDING |
| EXPOSURE FOR THIS BUILDING IS "D". ORIGINAL PLANS HAD |
| THE CORRECT BUILDING EXPOSURE "D". IT WAS THE DESIGN |
| PRESSURES THAT WERE INCORRECT. THAT'S WHY I DIDN'T ASK |
| TO CHANGE THE BUILDING EXPOSURE. ONLY THE DESIGN |
| PRESSURES. RESPONSE LETTER FROM THE ARCHITECT ONLY |
| TAKES INTO CONSIDERATION A WIND EXPOSURE FROM THE EAST |
| SIDE. NEED TO TAKE INTO CONSIDERATION EACH WIND |
| DIRECTION. SEE SEC. R301.2.1.4. (I MET WITH ROBERT |
| BROWN, BUILDING OFFICIAL, FOR SECOND OPINION ON |
| BUILDING EXPOSURE FOR THIS BUILDING. HE AGREES ON |
| EXPOSURE "D". PROPERTY APPRAISAL AERIAL VIEWS WILL BE |
| E-MAILED TO ARCHITECT TO ILLUSTRATE BUILDING EXPOSURE). |
| |
| 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND |
| OFFICE. SEC. R302.5 OF 2010 FBC-RESIDENTIAL. (COMPLETE |
| ASSEMBLY MAY BE SUBMITTED LATER FOR BUILDING OFFICIAL |
| REVIEW AND APPROVAL) |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR (NOTE: ALL PRODUCT APPROVALS WILL BE |
| RE-REVIEWED WHEN DESIGN PRESSURES ARE CHANGED FOR |
| EXPOSURE "D"): |
| A) CUSTOM MADE ENTRY DOOR ASSEMBLY. NEED TO PROVIDE |
| COMPLETE ENGINEER PACKAGE FOR SITE SPECIFIC APPROVAL. |
| MANUFACTURER TO CONTACT ROBERT BROWN (BUILDING |
| OFFICIAL) AT (561)805-6652 OR AT [email protected] TO |
| COORDINATE REQUIRED SUBMITTAL PACKAGE TO AVOID DELAYS |
| OR CONFLICTS. |
| |
| B) FIXED WINDOW SIZE SPECIFIED FOR WINDOW "F" ON THE |
| WINDOW SCHEDULE. NOA 11-1031.06 SUBMITTED DOESN'T COVER |
| THAT SIZE. |
| NOTE: WINDOW SCHEDULE CALLS FOR PGT WINDOWS. PRODUCT |
| APPROVALS SUBMITTED ARE FOR DIFFERENT MANUFACTURER. |
| REVISE AS REQUIRED. |
| |
| C) OUTSWING GLAZED DOOR WITH SIDELITES: NEED TO PROVIDE |
| PRODUCT APPROVAL THAT COVERS SIZE FOR DOOR #4. |
| |
| D) SLIDING GLASS DOORS WITH 3 PANELS SIZE AS SPECIFIED |
| FOR DOOR #3. |
| |
| E) PRECAST LINTELS AS SPECIFIED ON PLANS. NOA |
| 13-0321.07 SUBMITTED IS FOR 4", 6" & 12" LINTELS. THIS |
| IS NOT WHAT'S SPECIFIED ON PLANS. |
| |
| 4- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE |
| PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 5- GEO-TECHNICAL ENGINEERING REPORT SUBMITTED NEED THE |
| ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY |
| CHAPTER 471 F.S. |
| |
| NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE |
| REQUIRED DURING CONSTRUCTION. |
| |
| ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| |