Plan Review Notes For Permit 15031260 |
Permit Number |
15031260 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-29 12:15:18 | 1) SHOW THE LOCATION OF THE WASHING MACHINE AND LAUNDRY | | TRAY ON THE FLOOR PLAN.WPB AMEND. TO 2010 FBC SEC. | | 107.2.1. | | 2)THE SANITARY RISER DOES NOT CORRELATE WITH THE FLOOR | | PLAN FOR THE LOCATION OF FIXTURES.WPB AMEND. TO 2010 | | FBC SEC. 107.2.1. | | 3) SHT. E-2 HAS A SECTION OF THE SANITARY RISER THAT | | INCLUDES A WATER CLOSET, LAVATORY, FLOOR DRAIN, A SINK | | AND A LAVATORY BUT THERE IS NO SUCH AREA ON THE FLOOR | | PLAN. CLARIFY. | | 4) SHT. E-2 HAS A SANITARY RISER FOR A BATH #3 BUT | | THERE IS NO BATH #3. CLARIFY.WPB AMEND. TO 2010 FBC | | SEC. 107.2.1. | | 5) THE SECOND FLOOR SHOWS A BATH #1 BUT THE RISERS DO | | NOT SHOW A BATH #1. CLARIFY.WPB AMEND. TO 2010 FBC SEC. | | 107.2.1. | | 6) IDENTIFY THE CONNECTION POINTS ON THE FIRST FLOOR | | RISER WHERE THE SECOND FLOOR RISERS CONNECT TO THE | | STACKS.WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | 7) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER | | THE 2010 FBCR SEC.P3005.2.6. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|