2015-04-29 12:15:181) SHOW THE LOCATION OF THE WASHING MACHINE AND LAUNDRY
 TRAY ON THE FLOOR PLAN.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2)THE SANITARY RISER DOES NOT CORRELATE WITH THE FLOOR
 PLAN FOR THE LOCATION OF FIXTURES.WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 3) SHT. E-2 HAS A SECTION OF THE SANITARY RISER THAT
 INCLUDES A WATER CLOSET, LAVATORY, FLOOR DRAIN, A SINK
 AND A LAVATORY BUT THERE IS NO SUCH AREA ON THE FLOOR
 PLAN. CLARIFY.
 4) SHT. E-2 HAS A SANITARY RISER FOR A BATH #3 BUT
 THERE IS NO BATH #3. CLARIFY.WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 5) THE SECOND FLOOR SHOWS A BATH #1 BUT THE RISERS DO
 NOT SHOW A BATH #1. CLARIFY.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 6) IDENTIFY THE CONNECTION POINTS ON THE FIRST FLOOR
 RISER WHERE THE SECOND FLOOR RISERS CONNECT TO THE
 STACKS.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 7) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER
 THE 2010 FBCR SEC.P3005.2.6.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR