2015-05-14 15:24:05NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SELECTED EQUIPMENT EXCEEDS THE CALCULATED TOTAL
 LOAD. NEED TO COMPLY WITH SEC. 403.6.1.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- EQUIPMENT LISTED ON THE MECHANICAL PLAN DOESN'T
 MATCH EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. NOTE: COORDINATE WITH ITEM #1 ABOVE WHEN
 THE EQUIPMENT IS REVISED.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  