 PROJECT: POTTER RESIDENCE
 PERMIT#: 15031260
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE ELECTRICAL SERVICE LOAD SUMMARY INDICATES A
 TOTAL CONNECTED LOAD OF 320AMPS AND YET THE RISER
 DIAGRAM INDICATES ONLY A 2/0 FEEDER TO A 200AMP MAIN
 RATED PANEL "A". REVISE THE RISER TO ACCOMMODATE THE
 TOTAL CONNECTED LOAD PROPOSED.
  
 2) REVISE THE RISER DIAGRAM TO INDICATE THE BONDING OF
 THE GAS PIPING AND THE INSTALLATION OF THE INTER-SYSTEM
 BONDING DEVICE. SEE NEC 250.94 AND 250.104(2)
  
 3) INDICATE THE LOCATION FOR THE SAUNA AND PANEL "C" ON
 THE FLOOR PLAN.WPB AMENDMENTS TO THE FBC 107.2.1
  
 4) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
  
 5) RECESSED LUMINARIES INSTALLED IN THE BUILDING
 THERMAL ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE
 BETWEEN CONDITIONED AND UNCONDITIONED SPACES. ALL
 RECESSED LUMINARIES SHALL BE IC-RATED AND LABELED AS
 MEETING ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA)
 PRESSURE DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944
 L/S) OF AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE
 CEILING CAVITY. ALL RECESSED LUMINARIES SHALL BE SEALED
 WITH A GASKET OR CAULK BETWEEN THE HOUSING AND INTERIOR
 WALL OR CEILING COVERING. FBC-E 502.3.8 RECESSED
 LIGHTING.
  
 6) VERIFY CARBON MONOXIDE DETECTORS ARE INSTALLED AS
 REQUIRED. EVERY SEPARATE BUILDING OR AN ADDITION TO AN
 EXISTING BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED AND HAVING A FOSSIL FUEL BURNING
 HEATER OR APPLIANCE, A FIRE PLACE, AN ATTACHED GARAGE,
 OR OTHER FEATURE, FIXTURE OR ELEMENT THAT EMITS CARBON
 MONOXIDE AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10'
 OF EACH ROOM USED FOR SLEEPING PURPOSES.
 FBC-RESIDENTIAL 315.1
  
 7) PROVIDE A 3WAY SWITCH AT THE BALCONY EGRESS DOORS
 FROM BATH 2 ON THE 2ND FL WPB AMENDMENTS TO THE FBC
 107.2.1
  
 8) VERIFY LUMINAIRES IN CLOTHES CLOSETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC
 410.16(A) AND (B).
  
 9) DOUBLE CHECK AND VERIFY GFI OUTLET SPACING AT THE
 KITCHEN COUNTERTOPS. THERE APPEARS TO BE A COUPLE OF
 OUTLETS MISSING BY THE REFRIGERATOR AND THE OVEN. NEC
 210.52(C)(1) WALL COUNTERTOP SPACES.
  
 10) VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 PLEASE PROVIDE A SEPARATE PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND
 SHOP DRAWINGS FOR ALL LOW VOLTAGE SPECIALTY SYSTEMS
 SUCH AS BUT NOT LIMITED TO THE FOLLOWING:
 DATA/COMMUNICATION, SECURITY, AND AUDIO/VIDEO.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  