Plan Review Notes
Plan Review Notes For Permit 15031260
Permit Number 15031260
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-04 18:28:51NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- PROPERTY IS LOCATED IN FLOOD ZONE A5. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE REQUIREMENTS OF SEC. R322 OF 2010
 FBC-RESIDENTIAL. SPECIFY FINISH FLOOR ELEVATION FOR
 MAIN HOUSE, GARAGE, CABANA AND ALL EQUIPMENT. NOTE:
 ELEVATIONS CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION.
  
 3- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON SHEET
 SP-1 DON'T CORRESPOND TO THE WORST CASE SCENARIO FOR
 EXPOSURE "D". REVISE AS REQUIRED. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND
 OFFICE SHOWING COMPLIANCE WITH SEC. R302.5 OF 2010
 FBC-RESIDENTIAL.
  
 5- GARAGE WALL SECTION ON SHEET A-3 AND WALL SECTION ON
 SHEET A-6 CALL FOR ROOF FLAT TILE TO BE FOAMED AND
 NAILED. SPECIFY TYPE AND NUMBER OF NAILS. SEC.
 107.2.1.2 CITY AMENDMENTS.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SECOND FLOOR DRAFSTOPPING SHOWING COMPLIANCE WITH SEC.,
 R302.12 OF 2010 FBC-RESIDENTIAL.
  
 7- GARAGE WALL SECTION ON SHEET A-3:
 A) PROVIDE FIREBLOCKING SPECS BETWEEN GARAGE AND SECOND
 FLOOR. SEC. R302.11 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE SPECIFICATIONS FOR CEILING MATERIALS AS
 REQUIRED BY TABLE R302.6 OF 2010 FBC-RESIDENTIAL.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SOFFIT CONSTRUCTION AT SECOND FLOOR AND AT THE BALCONY
 SHOWING COMPLIANCE WITH SEC. R703.1.3 OF 2010
 FBC-RESIDENTIAL. SPECIFY ALL FRAMING MEMBERS AND
 FASTENERS, WATER BARRIER, ETC.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF BALCONY CONCRETE PIERS. TABLE R301.5 OF
 2010 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 GUARDRAIL CONSTRUCTION SHOWING COMPLIANCE WITH THE LIVE
 LOAD OF TABLE R301.5 AND THE REQUIREMENTS OF SEC. R312
 OF 2010 FBC-RESIDENTIAL.
  
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SECOND FLOOR ASSEMBLY. SPECIFY FLOOR SHEATHING AND
 FINISH, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 G) SHOW CORRECT LOCATION OF ICYNENE. WALL SECTION SHOWS
 SOFFIT WITHOUT INSULATION. NEED TO SHOW THAT THERMAL
 ENVELOPE IS COVERED WITH ICYNENE FOR AN UNVENTED ATTIC.
 SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 H) SPECIFY INSULATION BETWEEN GARAGE AND SECOND FLOOR.
 COORDINATE WITH THE ENERGY CALCULATIONS. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF STUCCO OVER FRAME CONSTRUCTION SHOWING
 THICKNESS COMPLIANCE WITH TABLE R702.1(1) AND WATER
 RESISTANT BARRIER SEC. R703.6.3 OF 2010
 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF DECORATIVE ALUMINUM
 LOUVERS ON COVERED PORCH.
  
 10- ENTRY WALL SECTION ON SHEET A-4: SEE GARAGE WALL
 SECTION COMMENTS AND ADDRESS ITEMS THAT APPLY TO THIS
 SECTION. NOTE: SAME THING APPLIES TO WALL SECTION ON
 SHEET A-6.
  
 11- SHEET A-5:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FIREBLOCKING AS REQUIRED BY SEC. R302.11 AT STAIRS AND
 DROPPED CEILING SHOWN ON STAIR SECTION-1.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FABRICATION AND INSTALLATION OF HANDRAILS AND
 GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE LOAD OF
 TABLE R301.5 AND ALL THE REQUIREMENTS OF SEC. R311.7.7
 AND R312 OF 2010 FBC-RESIDENTIAL. SPECIFY MATERIALS AND
 FASTENERS.
  
 C) SCHEMATIC GUARDRAIL DETAIL. REVISE OPENING
 SPECIFICATIONS. IT'S NOT 4" SPHERE MIN. IT'S AN OPENING
 THAT DOESN'T ALLOW THE PASSAGE OF A 4" SPHERE. SEC.
 R312.3 OF 2010 FBC-RESIDENTIAL.
  
 D) WINDOW SAFEGUARD NOTE IS INCORRECT. SEE SEC. R612.2
 OF 2010 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE FLASHING REQUIREMENTS OF SEC.
 R703.8 OF 2010 FBC-RESIDENTIAL.
  
 12- SHEET A-6:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CABANA STEEL ALUMINUM COLUMNS. SPECIFY BOTTOM PLATE
 SIZE AND FASTENERS. SEC. R601.2 OF 2010
 FBC-RESIDENTIAL..
  
 B) PROVIDE WALL SECTION THRU THE SUMMER KITCHEN.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CEILING CONSTRUCTION. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 C) SPECIFICATIONS FOR THE ROOF SHEATHING SHOWN ON THE
 ROOF FRAMING PLAN DON'T MATCH THE SPECIFICATIONS SHOWN
 ON THE WALL SECTION . REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 13- SHEET S-2:
 A) PROVIDE WALL SECTION THRU REAR COVERED PORCH.
 SPECIFY CEILING CONSTRUCTION MATERIALS AND FASTENERS.
 SPECIFY CONNECTORS FOR TRUSSES THAT ARE RESTING ON THE
 WALL BETWEEN THE GARAGE AND COVERED PORCH. SEC. R301.1
 OF 2010 FBC-RESIDENTIAL.
  
 B) GIRDER TRUSS LOCATED BY THE STAIRS AND LIVING ROOM
 AREA: GIRDER TRUSS IS RESTING ON A WOOD COLUMN ON THE
 LEFT HAND SIDE, BUT THERE IS NOT INFORMATION FOR THE
 BEARING ON THE RIGHT HAND SIDE. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS, INCLUDING FOOTING IF
 REQUIRED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 C) SPECIFY ALL CONNECTORS FOR THE FLOOR TRUSSES,
 INCLUDING THE GIRDER TRUSSES. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 D) TYPICAL INTERMEDIATE SECTION. SHOW COMPLIANCE WITH
 FIREBLOCKING AS REQUIRED BY SEC. R302.11 OF 2010
 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 COLUMNS BETWEEN WINDOWS "F". SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 14- SHEET S-3: THERE ARE DIFFERENT SPECS FOR THE ROOF
 SHEATHING FASTENING. SEE SPECS ON TYPICAL ROOF SECTION,
 NAILING ZONE PLAN AND ROOF FRAMING PLAN. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 15- PROVIDE SEPARATE ENERGY CALCULATIONS FOR THE
 DETACHED CABANA. SEC. 103.2.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 16- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) CUSTOM MADE ENTRY DOOR ASSEMBLY. NEED TO PROVIDE
 COMPLETE ENGINEER PACKAGE FOR SITE SPECIFIC APPROVAL.
 MANUFACTURER TO CONTACT ROBERT BROWN (BUILDING
 OFFICIAL) AT (561)805-6652 OR AT [email protected] TO
 COORDINATE REQUIRED SUBMITTAL PACKAGE TO AVOID DELAYS
 OR CONFLICTS.
  
 B) ROOF TILE. NOA 12-0222.03 SUBMITTED DOESN'T
 CORRESPOND TO THE FLORIDA PRODUCT APPROVAL FL601-R9
 SUBMITTED. PROVIDE CORRECT NOA.
  
 C) ROOF TILE ADHESIVE THAT MEETS THE MINIMUM ROOF TILE
 ATTACHMENT RESISTANCE. TILE BOND ADHESIVE SUBMITTED
 DOESN'T MEET THE ROOF TILE ATTACHMENT RESISTANCE.
  
 D) FIXED WINDOW SIZE SPECIFIED FOR WINDOW "F". NOA
 11-1031.06 SUBMITTED DOESN'T COVER THAT SIZE.
  
 E) OUTSWING GLAZED DOORS WITH/WITHOUT SIDE-LITES. NOA
 13-0226.06 SUBMITTED DOESN'T CORRESPOND TO FLORIDA
 PRODUCT APPROVAL FL16217 SUBMITTED. PROVIDE EITHER THE
 MIAMI-DADE NOA OR COMPLETE FLORIDA PRODUCT APPROVAL
 PACKAGE. NOTE: BEFORE SUBMITTAL VERIFY THAT PRODUCT
 APPROVAL COVER SIZE OF DOOR ASSEMBLY SPECIFIED FOR DOOR
 #4.
  
 F) GARAGE DOOR. NEED PRODUCT APPROVAL THAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE ARCHITECT OF RECORD.
 AND PROVIDE LEGIBLE DRAWINGS.
  
 G) SLIDING GLASS DOORS SIZE AS SPECIFIED FOR DOOR #3.
 NOTE: SEE SIZE OF PANELS (3).
  
 H) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 I) ALUMINUM BAHAMA SHUTTERS AS SPECIFIED ON PLANS. AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 J) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR LIST FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO THE SPECIFIED CONNECTOR.
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 18- PROVIDE ICYNENE ICC CURRENT EVALUATION REPORT TO
 VERIFY COMPLIANCE WITH SEC. R316 OF 2010
 FBC-RESIDENTIAL. AND ARCHITECT OF RECORD TO REVIEW AND
 APPROVE IT PRIOR TO SUBMITTAL.
  
 19- SHEET S-1: FOOTING PROFILE SHOWN BETWEEN THE GARAGE
 AND OFFICE SIDE IS INCORRECT. THERE IS A 4" DROP ON THE
 FOOTING PROFILE. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 20- REVISE THE DESCRIPTION OF THE GEO-TECHNICAL
 ENGINEERING REPORT SUBMITTED. THIS IS A TWO STORY
 SINGLE FAMILY HOME NOT ONE. ALSO, TAKE INTO
 CONSIDERATION THAT IT'S CONCRETE BLOCK CONSTRUCTION.
 SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 21- DESIGNER OF RECORD TO REVIEW THE GEO-TECHNICAL
 ENGINEERING REPORT FOR FOUNDATION AND CONCRETE SLAB
 RECOMMENDATIONS (SEE SEC. 4.3.1 AND 4.3.2 OF REPORT
 SUBMITTED). DESIGNER OF RECORD TO REVISE PLANS AS
 RECOMMENDED OR ACKNOWLEDGE IN WRITING THAT NO CHANGES
 WILL BE REQUIRED FOR HIS DESIGN. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 22- ATTIC ACCESS LOCATED IN SECOND FLOOR BY THE LIVING
 AREA DOESN'T COMPLY WITH SEC. R807 OF 2010
 FBC-RESIDENTIAL. CLOSET IS TOO SMALL. ACCESS WILL BE
 BLOCKED BY THE CONTENT OF THE CLOSET. REVISE LOCATION
 AS REQUIRED.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]