2015-04-02 09:29:31 | |
| BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15031194 |
| ADD: 777 S. FLAGLER DR. SUITE # 136 |
| CONT: JIM RAPP |
| TEL: (561)248-6411 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE |
| |
| 1ST REVIEW |
| DATE: THURS. APRIL 02/2015 |
| ACTION: DENIED |
| |
| 1) SHEET A2 OFFICE # 4 IS NEW AND HAS (2) INSWING |
| DOORS, THE NEW DOORS DO NOT PROVIDE IF THEY ARE 3'-0" |
| OR 2'-10" EACH. DEPENDING ON THE SIZE OF THE DOOR |
| COMPLIANCE WITH MAY OR MAY NOT BE ACHIEVED, 2010 |
| FBC-ACCESSIBILITY CODE 404.2.6 DOORS IN SERIES. |
| |
| 2) SHEET A2. NEW RESTROOM( NOT BATHROOM) IN THE OLD |
| SERVER LOCATION, IS NOT DIMENSIONED. IT APPEARS THIS |
| NEW RESTSROOM IS DESIGNED AS A ACCESSIBLE RESTROOM WITH |
| PEDISTALL SINK AND GRAB BARS, THE MINIMUM DIMENSION |
| WITH THE FIXTURES ON THE BACK WALL IS 7'-1" WITH THE |
| LAV CENTERED 15 INCHES FROM WALL LAV OVERALL DIMENSION |
| OF 19 INCHES IN WIDTH WILL GIVE COMPLIANCE OF 60 INCHES |
| CLEARANCE IN COMPLIANCE WITH FBC-ACCESSIBILITY CODE |
| 604.3.2. |
| |
| 3)SHEET A2. THE NEW RESTROOM AND PRIVATE OFFICE SHOWS |
| NEW GRAB BARS BEING INSTALLED ON THE BACK AND SIDE |
| WALLS. THE PLANS DO NOT PROVIDE ELEVATIONS WITH THE |
| REQUIRED DIMENSIONS FOR THE GRAB BARS NOR DOES THE |
| PLANS PROVIDE THE STRENGHT REQUIREMENTS FOR THE |
| BACKING. |
| 2010 FBC-ACCESSIBILITY CODE 604.5.1, 604.5.2 & 609.8 |
| STRUCTURAL STRENGHT. |
| |
| 4) SHEET A2.THE CONFERENCE ROOM TO THE RIGHT OF THE |
| PAGE SHOWS A KITCHEN IN THIS ROOM. NOTE WHEN A KITCHEN |
| IS IN A COMMERCIAL APPLICATION COMPLIANCE WITH 2010 |
| FBC-B F] 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. EACH |
| REQUIRED COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT |
| SYSTEM REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR |
| CHAPTER 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO |
| HAVE A TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN |
| ACCORDANCE WITH THIS CODE. |
| |
| 5) SHEET A2. BEHIND THE AREA OF ALTERATIONS IS A |
| CORRIDOR WITH (2) EXISTING DOORS THAT DO NOT COMPLY |
| WITH 2010 FBC-ACCESSIBILITY CODE 404.2.4. PLEASE EITHER |
| SHOW COMPLIANCE WITH THE CODE SECTION PROVIDED OR |
| PRODUCE A LETTER SHOWING THE CONTRACTOR HAS MET THE |
| COST ASSOCIATED WITH DISPROPORTIONATE COST. NOTE THE |
| ORDER OF EXPENDITURES ASSOCIATED IN ACCESSIBLE |
| UPGRADES, AND WHAT ITEMS CAN BE INCLUDED. 202.4.1 |
| DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |