Plan Review Notes For Permit 15031190 |
Permit Number |
15031190 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-11 11:17:01 | 1) SHT. P2.3 - 3RD FLOOR WASTE - SHOWS A 4 " HORIZONTAL | | RAINWATER LINE BY COL.#2 COLEECTING 1800 SQUARE FEET OF | | AREA. TABLE 1106.3 LIMITS THE SQUARE FOOTAGE OF A 4" | | LINE TO 1504 SQUARE FEET AT A 5" RAINFALL RATE. | | 2) SHT. P2.2 SHOWS A 6" RAINWATER LINE THAT GOES | | NOWHERE. CLARIFY. | | 3) SHT. P2.3 - SHOWS A 4" RAINWATER LINE PENETRATING | | WHAT APPEARS TO BE A RATED STAIR ENCLOSURE. | | PENETRATIONS INTO AND OPENINGS THROUGH ARE PROHIBITED | | EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK | | NECESSARY FOR FOR INDEPENDENT VENTILATION OR | | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, | | ELECTRICAL RACEWAYS FOR FIRE DEPARTMENT COMMUNICATIONS, | | ETC. PER THE 2010 FBC SEC.1022.4. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|