2015-04-11 11:17:011) SHT. P2.3 - 3RD FLOOR WASTE - SHOWS A 4 " HORIZONTAL
 RAINWATER LINE BY COL.#2 COLEECTING 1800 SQUARE FEET OF
 AREA. TABLE 1106.3 LIMITS THE SQUARE FOOTAGE OF A 4"
 LINE TO 1504 SQUARE FEET AT A 5" RAINFALL RATE.
 2) SHT. P2.2 SHOWS A 6" RAINWATER LINE THAT GOES
 NOWHERE. CLARIFY.
 3) SHT. P2.3 - SHOWS A 4" RAINWATER LINE PENETRATING
 WHAT APPEARS TO BE A RATED STAIR ENCLOSURE.
 PENETRATIONS INTO AND OPENINGS THROUGH ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAYS FOR FIRE DEPARTMENT COMMUNICATIONS,
 ETC. PER THE 2010 FBC SEC.1022.4.
  