Plan Review Notes
Plan Review Notes For Permit 15031190
Permit Number 15031190
Review Stop P
Sequence Number 1
Notes
Date Text
2015-03-30 10:28:381) SUBMIT A ROOF SCUPPER DETAIL FOR REVIEW.SHOW THE
 LENGTH & WIDTH & HEIGHT DIMENSIONS, THE SQUARE FOOTAGE
 THAT WOULD DRAINED BY EACH SCUPPER, AND THE HEAD OF THE
 SCUPPER PER TABLE 1106.7 OF THE 2010 FPC. SCUPPER
 DESIGN AND LOCATION SHALL COMPLY W/2010 FBC SEC.
 1503.4.2.1.
 2) SUBMIT A CLEAR AND LEGIBLE PLAN THAT SHOWS THE
 LOCATION OF THE ROOF DRAINS AND THE SCUPPERS. THE HAND
 DRAWN PLAN IS NOT LEGIBLE ENOUGH. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 3) INDICATE ON THE PLAN IF THE SCUPPERS DISCHARGE TO A
 COLLECTOR BOX AND DOWNSPOUT. IF SO, SHOW THE LOCATION
 AND SIZES ON THE PLANS. DOWNSPOUTS SHALL COMPLY W/ 2010
 FPC TABLES 1106.2 (1) OR 110602 (2).
 4) SUBMIT A STORM DRAINAGE RISER FOR THE NEWLY ADDED 4"
 OVERFLOW DRAINS. SHOW THE SQUARE FOOTAGE DRAINED BY
 EACH DRAIN AND SHOW THE SIZES OF ALL VERTICAL AND
 HORIZONTAL PIPES. COMPLY WITH TABLE 1106.3 OF 2010 FPC.
 5) CLEARLY IDENTIFY BY CLOUDING THE NEW 4" ROOF
 OVERFLOW DRAINS ON THE DRAWINGS FROM EMERALD
 ENGINEERING. WPB AMEND. TO 2010 FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  