Plan Review Notes For Permit 15031190 |
Permit Number |
15031190 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-30 10:28:38 | 1) SUBMIT A ROOF SCUPPER DETAIL FOR REVIEW.SHOW THE | | LENGTH & WIDTH & HEIGHT DIMENSIONS, THE SQUARE FOOTAGE | | THAT WOULD DRAINED BY EACH SCUPPER, AND THE HEAD OF THE | | SCUPPER PER TABLE 1106.7 OF THE 2010 FPC. SCUPPER | | DESIGN AND LOCATION SHALL COMPLY W/2010 FBC SEC. | | 1503.4.2.1. | | 2) SUBMIT A CLEAR AND LEGIBLE PLAN THAT SHOWS THE | | LOCATION OF THE ROOF DRAINS AND THE SCUPPERS. THE HAND | | DRAWN PLAN IS NOT LEGIBLE ENOUGH. WPB AMEND. TO 2010 | | FBC SEC. 107.2.1. | | 3) INDICATE ON THE PLAN IF THE SCUPPERS DISCHARGE TO A | | COLLECTOR BOX AND DOWNSPOUT. IF SO, SHOW THE LOCATION | | AND SIZES ON THE PLANS. DOWNSPOUTS SHALL COMPLY W/ 2010 | | FPC TABLES 1106.2 (1) OR 110602 (2). | | 4) SUBMIT A STORM DRAINAGE RISER FOR THE NEWLY ADDED 4" | | OVERFLOW DRAINS. SHOW THE SQUARE FOOTAGE DRAINED BY | | EACH DRAIN AND SHOW THE SIZES OF ALL VERTICAL AND | | HORIZONTAL PIPES. COMPLY WITH TABLE 1106.3 OF 2010 FPC. | | 5) CLEARLY IDENTIFY BY CLOUDING THE NEW 4" ROOF | | OVERFLOW DRAINS ON THE DRAWINGS FROM EMERALD | | ENGINEERING. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|