Plan Review Notes For Permit 15031131 |
Permit Number |
15031131 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-08 13:23:05 | MASTER FOR RE-ROOFING AT SANDALWOOD LAKES, SECOND | | BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1-RAS 117 CALCULATIONS SUBMITTED: | | A) ENGINEER TO REVISE THE CALCULATIONS BASED ON THE | | FASTENER WITHDRAWAL TEST RESULTS (TAS 105 TEST). SEC. | | 1609 FBC-2010. | | REPEAT COMMENT. NOT ADDRESSED. | | | | B) ENGINEER TO UPDATE THE RAS 117 CALCULATIONS. THE | | CURRENT CODE IS THE 2010 FBC WHICH REFERENCES THE ASCE | | 7-10 NOT ASCE 7-05. REVISE AS REQUIRED AND SPECIFY THE | | ULTIMATE AND THE NOMINAL WIND SPEEDS. | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | | | ****NOTE: NEW MASTER WILL BE REQUIRED ON JUNE 30TH | | 2015, WHEN NEW BUILDING CODE IS IN EFFECT**** | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|