Plan Review Notes
Plan Review Notes For Permit 15031131
Permit Number 15031131
Review Stop B
Sequence Number 2
Notes
Date Text
2015-04-08 13:23:05MASTER FOR RE-ROOFING AT SANDALWOOD LAKES, SECOND
 BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1-RAS 117 CALCULATIONS SUBMITTED:
 A) ENGINEER TO REVISE THE CALCULATIONS BASED ON THE
 FASTENER WITHDRAWAL TEST RESULTS (TAS 105 TEST). SEC.
 1609 FBC-2010.
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) ENGINEER TO UPDATE THE RAS 117 CALCULATIONS. THE
 CURRENT CODE IS THE 2010 FBC WHICH REFERENCES THE ASCE
 7-10 NOT ASCE 7-05. REVISE AS REQUIRED AND SPECIFY THE
 ULTIMATE AND THE NOMINAL WIND SPEEDS.
 REPEAT COMMENT. NOT ADDRESSED.
  
  
  
 ****NOTE: NEW MASTER WILL BE REQUIRED ON JUNE 30TH
 2015, WHEN NEW BUILDING CODE IS IN EFFECT****
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved