Plan Review Notes For Permit 15031131 |
Permit Number |
15031131 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-25 15:57:11 | MASTER FOR RE-ROOFING AT SANDALWOOD LAKES, BUILDING | | REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- NEW SINGLE PLY ROOF SYSTEM FL11475-R5: NEED FASTENER | | WITHDRAWAL RESISTANCE TEST (TAS 105 OR ANSI/SPRI FX-1) | | AS REQUIRED BY NOTE #11 ON PAGE 2 OF 21 OF FLORIDA | | PRODUCT APPROVAL SUBMITTED. SEC. 1609 OF 2010 FBC. | | | | 2- RAS 117 CALCULATIONS SUBMITTED: | | A) ENGINEER TO REVISE THE CALCULATIONS BASED ON THE | | FASTENER WITHDRAWAL TEST RESULTS REQUIRED BY ITEM #1 | | ABOVE. SEC. 1609 OF 2010 FBC. | | | | B) ENGINEER TO UPDATE THE RAS 117 CALCULATIONS. THE | | CURRENT CODE IS THE 2010 FBC WHICH REFERENCES THE ASCE | | 7-10 NOT ASCE 7-05. REVISE AS REQUIRED AND SPECIFY THE | | ULTIMATE AND THE NOMINAL WIND SPEEDS. | | | | 3- PERMIT APPLICATION NEEDS THE OWNER'S NOTARIZED | | SIGNATURE OR OWNER'S NOTARIZED LETTER AUTHORIZING THE | | CONTRACTOR TO DO THE WORK. | | | | ****NOTE: NEW MASTER WILL BE REQUIRED AFTER JUNE 30TH | | 2015, WHEN NEW BUILDING CODE IS IN EFFECT**** | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|