2015-03-25 15:57:11MASTER FOR RE-ROOFING AT SANDALWOOD LAKES, BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- NEW SINGLE PLY ROOF SYSTEM FL11475-R5: NEED FASTENER
 WITHDRAWAL RESISTANCE TEST (TAS 105 OR ANSI/SPRI FX-1)
 AS REQUIRED BY NOTE #11 ON PAGE 2 OF 21 OF FLORIDA
 PRODUCT APPROVAL SUBMITTED. SEC. 1609 OF 2010 FBC.
  
 2- RAS 117 CALCULATIONS SUBMITTED:
 A) ENGINEER TO REVISE THE CALCULATIONS BASED ON THE
 FASTENER WITHDRAWAL TEST RESULTS REQUIRED BY ITEM #1
 ABOVE. SEC. 1609 OF 2010 FBC.
  
 B) ENGINEER TO UPDATE THE RAS 117 CALCULATIONS. THE
 CURRENT CODE IS THE 2010 FBC WHICH REFERENCES THE ASCE
 7-10 NOT ASCE 7-05. REVISE AS REQUIRED AND SPECIFY THE
 ULTIMATE AND THE NOMINAL WIND SPEEDS.
  
 3- PERMIT APPLICATION NEEDS THE OWNER'S NOTARIZED
 SIGNATURE OR OWNER'S NOTARIZED LETTER AUTHORIZING THE
 CONTRACTOR TO DO THE WORK.
  
 ****NOTE: NEW MASTER WILL BE REQUIRED AFTER JUNE 30TH
 2015, WHEN NEW BUILDING CODE IS IN EFFECT****
  
  