2015-03-30 15:26:58 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF |
| THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE |
| AND COMPLIANCE. |
| |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS |
| RETURNED. |
| |
| 2. DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM |
| THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, |
| TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| THE EGRESS SIDE. |
| |
| THUMB-TURN LOCK, IRF USED, SHALL BE EQUIPPED WITH AN |
| ?OPEN/LOCKED? INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 |
| OR SIMILAR). |
| |
| 3. THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF |
| THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE |
| INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND |
| ALL OTHER APPLICABLE CODES OR STANDARDS |
| |