Plan Review Notes
Plan Review Notes For Permit 15031115
Permit Number 15031115
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-03-30 15:26:58THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS
 RETURNED.
  
 2. DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS SIDE.
  
 THUMB-TURN LOCK, IRF USED, SHALL BE EQUIPPED WITH AN
 ?OPEN/LOCKED? INDICATOR WINDOW (SUCH AS ADAMS RITE 4089
 OR SIMILAR).
  
 3. THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS
  