2015-04-17 13:38:18 | 4847 FRED GLADSTONE DRIVE | | PERMIT #15031053 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SHEET E-E501: SEVERAL STAIRS ON SEVERAL LEVELS INDICATE | | THE USE OF CARD READERS AND OCCUPANT SENSORS LOCATED | | WITHIN THE FIRE RATED EXIT ENCLOSURE. PER NFPA 101 | | SECTION 7.1.3.2.1, PENETRATIONS INTO, AND OPENINGS | | THROUGH, AN EXIT ENCLOSURE ASSEMBLY SHALL BE LIMITED TO | | DOOR ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND | | CORRIDORS, REQUIRED EXIT DOOR OPENINGS, ELECTRICAL | | CONDUIT SERVING THE EXIT ENCLOSURE, DUCTWORK AND | | EQUIPMENT NECESSARY FOR INDEPENDENT STAIR | | PRESSURIZATION, WATER OR STEAM PIPING NECESSARY FOR THE | | HEATING OR COOLING OF THE EXIT ENCLOSURE, SPRINKLER | | PIPING, STANDPIPES, AND PENETRATIONS FOR FIRE ALARM | | CIRCUITS, WHERE THE CIRCUITS ARE INSTALLED IN METAL | | CONDUIT AND THE PENETRATIONS ARE PROTECTED. | | | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|