Plan Review Notes
Plan Review Notes For Permit 15030974
Permit Number 15030974
Review Stop M
Sequence Number 2
Notes
Date Text
2015-07-13 13:51:22 
  
 ***NOTE: CONTRACTOR MAY SUBMIT COMPLETE AND CORRECT
 MECHANICAL INFORMATION NOW OR COMPLETE INFORMATION MAY
 BE SUBMITTED BY THE A/C CONTRACTOR UNDER A SEPARATE
 PERMIT.
  
  
  
 RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 *** THERE WAS NOT INFORMATION SUBMITTED. THE COMMENTS
 BELOW ARE THE ORIGINAL COMMENTS.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES). SEC. M1401.3 OF 2010 FBC-RESIDENTIAL.
  
 2- MECHANICAL PLANS SUBMITTED:
 A) ARCHITECT TO REVISE THE TRANSFER DUCTS INFORMATION
 FOR THE BALANCED RETURN AIR. 14" DUCT DOESN'T FIT ON A
 12"X12" GRILL. SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 B) LIST ON THE PLAN THE EQUIPMENT MANUFACTURER AND
 MODEL NUMBER THAT WAS USED FOR THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]