Plan Review Notes
Plan Review Notes For Permit 15030974
Permit Number 15030974
Review Stop M
Sequence Number 1
Notes
Date Text
2015-05-01 18:31:33RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES). SEC. M1401.3 OF 2010 FBC-RESIDENTIAL.
  
 2- MECHANICAL PLANS SUBMITTED:
 A) ARCHITECT TO REVISE THE TRANSFER DUCTS INFORMATION
 FOR THE BALANCED RETURN AIR. 14" DUCT DOESN'T FIT ON A
 12"X12" GRILL. SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 B) LIST ON THE PLAN THE EQUIPMENT MANUFACTURER AND
 MODEL NUMBER THAT WAS USED FOR THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved