2015-05-01 18:31:33 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2 | | COPIES). SEC. M1401.3 OF 2010 FBC-RESIDENTIAL. | | | | 2- MECHANICAL PLANS SUBMITTED: | | A) ARCHITECT TO REVISE THE TRANSFER DUCTS INFORMATION | | FOR THE BALANCED RETURN AIR. 14" DUCT DOESN'T FIT ON A | | 12"X12" GRILL. SEC. M1602.4 OF 2010 FBC-RESIDENTIAL. | | | | B) LIST ON THE PLAN THE EQUIPMENT MANUFACTURER AND | | MODEL NUMBER THAT WAS USED FOR THE EQUIPMENT SIZING | | CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|