Plan Review Notes For Permit 15030968 |
Permit Number |
15030968 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-10-28 07:40:37 | 2ND REVIEW: FBC 2010 | | | | THESE ARE REPEAT COMMENTS FROM THE PREVIUOS REVIEW. | | | | THE FOLLOWING APPLIES TO THE PLANNED CONVERSION OF THE | | GARAGE TO LIVING SPACE. | | | | FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402 | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION | | | | FBC- 107.3.5.3 PROVIDE A MECHANICAL PLAN/SPECIFY | | EQUIPMENT PER FBC-R M16. IT APPEARS YOU PLAN TO PUT A | | MECHANICAL UNIT IN THE REAR WALL, BUT THE WALL IS | | REQUIRED TO BE FIRE RATED THEREFORE YOU MAY NOT CHOOSE | | THIS LOCATION FOR THE UNIT. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|