Plan Review Notes For Permit 15030968 |
Permit Number |
15030968 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-10-28 07:43:27 | 2ND REVIEW: FBC 2010 NEC 2008 | | | | THE PLAN INDICATES THE DESIGN IS TO COMPLY WITH THE | | 2014 NFPA 70 NEC, WHICH IS NOT THE ADOPTED CODE IN | | EFFECT. THE CODE IN EFFECT AT THE TIME OF APPLICATION | | IS THE NEC 2008, BUT YOU MAY CHOOSE THE FBC 5TH EDITION | | RESIDENTIAL IF YOU WISH. | | | | THE ELECTRICAL DESIGN IS UNCLEAR. IS A NEW SERVICE | | PROPOSED? A RISER DIAGRAM IS PROVIDED THAT APPEARS TO | | BE NEW WORK. THERE ARE ALSO MANY NOTES REFERING TO AREA | | NOT ON THE PLAN SUCH AS BATHROOMS AND KITCHENS. ARE YOU | | DOING WORK IN THE PRIMARY BUILDING. ADDITIONALLY, THE | | PANEL SCHEDULE IS TOO SMALL AND NOT LEGIBLE. PROVIDE A | | MORE CLEAR PLAN. | | | | 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | CONFORM TO THE PROVISIONS OF THIS CODE. AND RELEVANT | | LAWS, | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|