2015-05-14 15:01:10 | 5/14/2015 |
| PROJECT: LAUNDRY |
| PERMIT#: 15030959 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 4TH ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| FEE(S). |
| |
| 1) IDENDIFY THE SCALE. WPB AMENDMENTS TO THE FBC |
| 107.2.1 THROUGH 107.2.5 |
| |
| 2)THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. NEC 700.12(F) |
| |
| 3) VERIFY THE ALLOWABLE AMPACITY OF EACH CONDUCTOR |
| SHALL BE REDUCED AS SHOWN IN TABLE 310.15(B)(2)(A). SEE |
| ANNEX B |
| |
| 4) BOXES AND CONDUIT BODIES SHALL BE OF SUFFICIENT SIZE |
| TO PROVIDE FREE SPACE FOR ALL ENCLOSED CONDUCTORS. IN |
| NO CASE SHALL THE VOLUME OF THE BOX, AS CALCULATED IN |
| 314.16(A), BE LESS THAN THE FILL CALCULATION AS |
| CALCULATED IN 314.16(B). THE MINIMUM VOLUME FOR CONDUIT |
| BODIES SHALL BE AS CALCULATED IN 314.16(C). NEC 314.16 |
| |
| 5) USE ANNEX C, THE CONDUIT AND TUBING FILL TABLES TO |
| DETERMINE THE MAXIMUM FILL CAPACITY FOR CONDUCTORS AND |
| FIXTURE WIRES OF THE SAME SIZE IN CONDUIT OR TUBING |
| USED. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |