2015-05-14 15:01:105/14/2015
 PROJECT: LAUNDRY
 PERMIT#: 15030959
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 4TH ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) IDENDIFY THE SCALE. WPB AMENDMENTS TO THE FBC
 107.2.1 THROUGH 107.2.5
  
 2)THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. NEC 700.12(F)
  
 3) VERIFY THE ALLOWABLE AMPACITY OF EACH CONDUCTOR
 SHALL BE REDUCED AS SHOWN IN TABLE 310.15(B)(2)(A). SEE
 ANNEX B
  
 4) BOXES AND CONDUIT BODIES SHALL BE OF SUFFICIENT SIZE
 TO PROVIDE FREE SPACE FOR ALL ENCLOSED CONDUCTORS. IN
 NO CASE SHALL THE VOLUME OF THE BOX, AS CALCULATED IN
 314.16(A), BE LESS THAN THE FILL CALCULATION AS
 CALCULATED IN 314.16(B). THE MINIMUM VOLUME FOR CONDUIT
 BODIES SHALL BE AS CALCULATED IN 314.16(C). NEC 314.16
  
 5) USE ANNEX C, THE CONDUIT AND TUBING FILL TABLES TO
 DETERMINE THE MAXIMUM FILL CAPACITY FOR CONDUCTORS AND
 FIXTURE WIRES OF THE SAME SIZE IN CONDUIT OR TUBING
 USED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  