2015-05-12 16:04:15 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) "B PHASE 208V TO GROUND ON A 120/240 DELTA HI LEG |
| ELECTRICAL DISTRIBUTION SYSTEM. THERE SHOULD BE NO |
| SINGLE POLE 120V BREAKERS INSERTED INTO ANY "B" PHASE |
| SLOTS IN ANY 3 PHASE DELTA PANEL BOARDS. |
| |
| 2) ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY |
| VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO |
| REACH THE EXIT IS NOT READILY APPARENT TO THE |
| OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1 |
| |
| 3) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 |
| |
| 4) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT |
| SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. |
| EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT |
| EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL |
| BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND |
| BY ONE OF THE WIRING METHODS OF NEC CHAPTER 3. NEC |
| 700.12(F) |
| |
| 5) VERIFY CONDUIT AND BOX FILL AS WELL AS CONDUCTOR |
| DERATING. |
| |
| 6) CORRECT THE SCALE THE PLAN IS DESIGNED TO. |
| |
| 7) CORRECT THE SIZE OF THE ARCHITACT'S SEAL. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |