2015-05-12 16:04:15REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) "B PHASE 208V TO GROUND ON A 120/240 DELTA HI LEG
 ELECTRICAL DISTRIBUTION SYSTEM. THERE SHOULD BE NO
 SINGLE POLE 120V BREAKERS INSERTED INTO ANY "B" PHASE
 SLOTS IN ANY 3 PHASE DELTA PANEL BOARDS.
  
 2) ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS NOT READILY APPARENT TO THE
 OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1
  
 3) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
  
 4) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF NEC CHAPTER 3. NEC
 700.12(F)
  
 5) VERIFY CONDUIT AND BOX FILL AS WELL AS CONDUCTOR
 DERATING.
  
 6) CORRECT THE SCALE THE PLAN IS DESIGNED TO.
  
 7) CORRECT THE SIZE OF THE ARCHITACT'S SEAL.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]