Plan Review Notes
Plan Review Notes For Permit 15030959
Permit Number 15030959
Review Stop G
Sequence Number 2
Notes
Date Text
2015-05-06 14:18:581) SHT. PM2 - GAS RISER - THE DRYERS ARE SHOWN AS 96
 CFH EACH BUT IN THE GAS LOAD TABLE THEY ARE SHOWN AS 90
 MBH.CLARIFY.
 2) THE TOTAL CFH/MBH LOAD ON THE SYSTEM THAT I
 CALCULATED IS 1,547 CFH.YOU HAVE CLCULATED 1469 MBH.
 PLEASE RE-CHECK YOUR CALCULATIONS.
 3) THERE ARE 7 DIFFERENT CFH LOADS ON THE GAS RISER
 DIAGRAM WHERE THERE ARE NO INCREASES IN THE NUMBER OF
 APPLIANCES. CLARIFY.
 4) THE GAS SIZING TABLES YOU HAVE LISTED (A2-2, 2-4,
 5-1, 5-2, & 3-4) ARE NOT LISTED IN THE 2010 FBC-FUEL
 GAS CODE. HOW CAN 5 DIFFERENT SIZING TABLES BE UTILIZED
 FOR ONE TYPE OF PIPING MATERIAL AT A SET DEVELOPED
 LENGTH? CLARIFY. THE SYSTEM SHALL BE SIZED PER THE
 SIZING TABLES IN CHAPTER 4 OF THE 2010 FBC-FUEL GAS
 CODE.
 5) THE PLAN SHOWS THE PIPING MATERIAL AS COPPER. COPPER
 SHALL NOT BE USED IF THE GAS CONTAINS MORE THAN AN
 AVERAGE OF 0..3 GRAINS OF HYDROGEN SULFIDE PER 100
 STANDARD CUBIC FEET OF GAS PER THE 2010 FGC
 SEC.403.4.3, 403.5.2. SINCE THIS IS A SAFETY ISSUE
 DOCUMENTATION FROM FLORIDA PUBLIC UTILITIES WILL BE
 REQUIRED STATING THE CONTENT OF HYDROGEN SULFIDE IN
 THEIR LINES.
 6) EXPLAIN HOW THE CALCULATIONS FOR THE REQUIRED
 COMBUSTION AIR WERE DONE. I DO NOT UNDERSTAND YOUR
 CALCULATIONS. THE RESULTING VALUE IS 16.29 OF WHAT?
 NOTHING IS IDENTIFIED. CLARIFY.THESE CALCULATIONS DO
 NOT APPEAR TO COMPLY WITH CHAPTER 304 OF THE 2010
 FGC.SEE THE MANUF. SPECS FOR THE DRYER FOR THE MIN.
 REQD. MAKE-UP AIR.
 7) THE PLANS STATE THAT THE VENTS SHALL BE A MIN. OF 28
 GAUGE.ARE THESE SINGLE WALL VENTS? IF SO, THE MINIMUM
 THICKNESS SHALL GALVANIZED SHEET STEEL NOT LESS THAN
 0.0304 INCH THICK. INDICATE THE THICKNESS OF THE 28
 GAUGE VENT PIPE PER THE 2010 FGC SEC.503.7.
 8) INDICATE ON THE PLANS IF THE DRYERS WILL BE
 INDIVIDUALLY VENTED THROUGH THE ROOF OR INTERCONNECTED
 WITH OTHER DRYERS.THE MANUF. SPECS RECCOMMEND
 INDIVIDUAL VENTING.IF THE FLUES ARE INTERCONNECTED,
 THEN THE VENTING SHALL COMPLY WITH THE VENTING TABLES
 IN CHAPT. 304 OF THE 2010 FGC.
  
 I SUGGEST THE DESIGN PROFESSIONAL CONTACT ME TO SET UP
 AN APPOINTMENT TO REVIEW MY PLAN REVIEW COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  