Plan Review Notes
Plan Review Notes For Permit 15030959
Permit Number 15030959
Review Stop P
Sequence Number 1
Notes
Date Text
2015-04-03 06:06:171) THE WASHERS AND DRYERS SHALL COMPLY WITH THE FL.
 ACCESSIBILITY CODE SECS. 611.3 FOR THE LOCATION OF
 OPERABLE PARTS OF THE MACINES AND 611.4 FOR THE HEIGHT
 REQUIREMENTS FOR MACHINE DOORS FOR THE TOP LOADING AND
 FRONT LOADING MACHINES.SHOW ALL THE DIMENSIONS ON THE
 PLANS.
 2) THE PLANS SHOW 3 NEW DRYERS. ACTUALLY ALL THE
 EXISTING DRYERS HAVE BEEN REPLACED.INDICATE THIS ON THE
 PLANS. IDENTIFY ALL DRYERS ON THE PLANS AND NOTE THAT
 THEY ARE BEING REPLACED. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 3) SHT. A-2 ELEVATION B-B DOES NOT CORRELATE WITH A-1.
 SHOW THE ALCOVE (NEW DRYER AREA) WALLS, ETC.
 4) NOTE ON THE PLAN IF THE EXISTING TOILET ROOM IS
 UNDERGOING ANY ALTERATION. IF SO, IT SHALL COMPLY
 W/2010 FL. ACCESSIBILITY CODE.
 5) THE PLAN SHOWS MOST OF THE DRAINAGE PIPING AND WATER
 PIPING AS EXISTING. ACTUALLY, MOST OF THIS PIPING WAS
 REMOVED WITHOUT PERMITS. THE PLANS SHALL CLARLY REFLECT
 THE ENTIRE SCOPE OF WORK TO BE DONE AND EXACTLY WHAT IS
 NEW PIPING TO BE INSTALLED.WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 6) THE SANITARY RISER SHOWS 5" DRAINAGE PIPE. THIS IS
 AN ODD SIZE PIPE. CLARIFY.
 7) THE WAY THE SANITARY RISER IS DESIGNED AND DRAWN IS
 EXTREMELY CONFUSING AND IS NOT CODE COMPLIANT.SUBMIT A
 SANITARY RISER THAT CLEARLY REFLECTS THE INSTALLATION.
 SIZE ALL VENTS, STANDPIPES, AND ALL SECTIONS OF THE
 HORIZONTAL DRAIN. INDICATE THE PITCH OF THE SANITARY
 LINES. SOME SANITARY LINES ARE SHOWN AS 2 3/8". THIS IS
 NOT A STANDARD SIZE.WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 8) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER
 FPC SEC.708.3.4 AND AT EACH CHANGE OF DIRECTION GREATER
 THAN 45 DEGREES .FPC SEC.708.3.3.
 9) THE SANITARY RISER SHOWS A 5" LINE CONNECTING INTO
 ANOTHER 5" LINE. CLARIFY.
 10) SIZE ALL SECTIONS OF THE WATER AND SANITARY RISERS
 WHEN THEY ARE RESUBMITTED.
 11) THE HOT WATER LINE ON THE RISER CONNECTS TO
 NOTHING. THE DROP IS NOT CONNECTED TO ANYTHING.
 12) SHOW ON THE PLANS HOW THE WATER AND DRAINAGE LINES
 WILL BE SUPPORTED. SUPPORT SPACING SHALL COMPLY WITH
 TABLE 308.5 OF THE 2010 FPC.
 13) INDICATE THE TYPE OF PIPE MATERIAL FOR THE WATER
 AND DRAINAGE LINES. WPB AMEND.TO 2010 FPC SEC.107.2.1.
 140 SUBMIT MANUF. SPECIFICATION SHEETS FOR THE WASHERS.
 WASHERS SHALL COMPLY W/ ASSE 1007.
  
 GAS
 14) SIZE ALL THE NEW AND EXISTING GAS PIPING AND
 VENTS.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 15) INDICATE THE TOTAL DEVELOPED LENGTH OF THE GAS
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 GAS OUTLET.INDICATE THE PSI OF THE GAS SYSTEM,THE TYPE
 OF PIPE BEING INSTALLED, AND THE TOTAL LOAD OF THE
 SYSTEM.
 16) INDICATE THE GAS SIZING TABLE THAT IS BEING USED TO
 SIZE THE SYSTEM.INDICATE ON THE PLAN IF THE GAS IS LP
 OR NATURAL GAS.
 17) INDICATE ON THE PLAN IF THE DRYERS ARE STACKED
 DRYERS. IF SO, THE GAS RISER SHALL SHOW THE GAS
 CONNECTIONS TO ALL DRYERS.
 18) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE GAS
 DRYERS. DRYERS SHALL BE LISTED AND LABELED PER THE 2010
 FGC SEC. 301.3.
 19) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL GAS
 APPLIANCES PER 2010 FGC SEC. 304.1.
 20) SUBMIT DETAILS FOR THE GAS VENTS. INDICATE TYPE OF
 VENT, SIZE OF VENT, BTU LOAD ON THE VENT.
 22) THERE WERE A NUMBER OF EXISTING GAS VALVES THAT
 WERE NOT CONNECTED TO AN APPLIANCE. ANY GAS VALVES NOT
 CONNECTED TO AN APPLIANCE SHALL BE EQUIPPED WITH A
 VALVE AND CAPPED.INDICATE THESE ON THE GAS RISER.
 230 THE GAS PIPING SHALL BE PROPERLY BONDED PER THE
 2010 FGC SEC.310.1.
 A THOROUGH REVIEW COULD NOT BE DONE DUE TO THE LACK OF
 INFORMATION ON THE DRAWINGS. ADDITIONAL COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF THE DOCUMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  