2015-04-06 12:03:034/6/2015
 PROJECT: LAUNDRY
 PERMIT#: 15030959
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WPB AMENDMENTS TO THE FBC 107.3.2
 ADDITIONAL INFORMATION IS REQUIRED. THE ELECTRICAL PLAN
 SUBMITTED ON SHEET E-1 INDICATES ALL ELECTRICAL
 CIRCUITRY IS EXISTING. HOWEVER, SHEET A-1 INDICATES THE
 INSTALLATION OF 3 NEW DRYERS AND 17 NEW WASHERS,
 A) PROVIDE A RISER DIAGRAM TO INDICATE THE ELECTRICAL
 SERVICE ENTRANCE, ALL MAIN OCPD(S) AND PANELS.
 B) PROVIDE PANEL SCHEDULES INCLUDING THE OCPD(S) AND
 WIRE SIZES FOR ALL AFFECTED CIRCUITRY AND FEEDERS.
 C) PROVIDE LOAD CALCULATIONS FOR THE PANELS AND FOR THE
 ELECTRICAL SERVICE.
  
 2) WPB AMENDMENTS TO THE FBC 107.3.2
 A) ADDITIONAL CLARIFICATION IS REQUIRED. INDICATE ALL
 CIRCUITRY ON THE FLOOR PLAN. INDICATE WHAT IS EXISTING
 TO REMAIN AND WHAT IS PROPOSED TO BE NEW.
 B) INDICATE THE REQUIRED MEANS OF DISCONNECT FOR ALL
 FIXED IN PLACE APPLIANCES. NEC 422
  
 3) NEC 700.12, 700.16
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS EMERGENCY AND
 EXIT LIGHTING EQUIPMENT SHALL BE CLEARLY IDENTIFIED AT
 THE DISTRIBUTION PANEL. NEC 700.12
 EMERGENCY LIGHTING SHALL BE DESIGNED AND INSTALLED SO
 THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT,
 SUCH AS THE BURNING OUT OF A LAMP, CANNOT LEAVE IN
 TOTAL DARKNESS ANY SPACE THAT REQUIRES EMERGENCY
 ILLUMINATION. INDICATE THE REQUIRED EMERGENCY AND EXIT
 LIGHTING ON THE LIGHTING PLAN. NEC 700.16
  
 4)NEC 422.60
 PROVIDE EQUIPMENT MANUFACTURER DOCUMENTATION FOR ALL
 NEW EQUIPMENT INDICATING LISTING REQUIREMENTS AND
 ELECTRICAL CHARACTERISTICS SUCH AS LOAD, VOLTAGE AND
 FREQUENCY. NEC 422.60
  
 5) WPB AMENDMENTS TO THE FBC 107.3.2
 IDENTIFY ROOM DESIGNATIONS ON THE FLOOR PLAN AND
 INDICATE THE LOCATIONS FOR THE ELECTRICAL SERVICE
 ENTRANCE METER/MAINS EQUIPMENT AND PANELS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  