2015-04-06 12:03:03 | 4/6/2015 |
| PROJECT: LAUNDRY |
| PERMIT#: 15030959 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) WPB AMENDMENTS TO THE FBC 107.3.2 |
| ADDITIONAL INFORMATION IS REQUIRED. THE ELECTRICAL PLAN |
| SUBMITTED ON SHEET E-1 INDICATES ALL ELECTRICAL |
| CIRCUITRY IS EXISTING. HOWEVER, SHEET A-1 INDICATES THE |
| INSTALLATION OF 3 NEW DRYERS AND 17 NEW WASHERS, |
| A) PROVIDE A RISER DIAGRAM TO INDICATE THE ELECTRICAL |
| SERVICE ENTRANCE, ALL MAIN OCPD(S) AND PANELS. |
| B) PROVIDE PANEL SCHEDULES INCLUDING THE OCPD(S) AND |
| WIRE SIZES FOR ALL AFFECTED CIRCUITRY AND FEEDERS. |
| C) PROVIDE LOAD CALCULATIONS FOR THE PANELS AND FOR THE |
| ELECTRICAL SERVICE. |
| |
| 2) WPB AMENDMENTS TO THE FBC 107.3.2 |
| A) ADDITIONAL CLARIFICATION IS REQUIRED. INDICATE ALL |
| CIRCUITRY ON THE FLOOR PLAN. INDICATE WHAT IS EXISTING |
| TO REMAIN AND WHAT IS PROPOSED TO BE NEW. |
| B) INDICATE THE REQUIRED MEANS OF DISCONNECT FOR ALL |
| FIXED IN PLACE APPLIANCES. NEC 422 |
| |
| 3) NEC 700.12, 700.16 |
| THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. THE BRANCH CIRCUIT THAT FEEDS EMERGENCY AND |
| EXIT LIGHTING EQUIPMENT SHALL BE CLEARLY IDENTIFIED AT |
| THE DISTRIBUTION PANEL. NEC 700.12 |
| EMERGENCY LIGHTING SHALL BE DESIGNED AND INSTALLED SO |
| THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT, |
| SUCH AS THE BURNING OUT OF A LAMP, CANNOT LEAVE IN |
| TOTAL DARKNESS ANY SPACE THAT REQUIRES EMERGENCY |
| ILLUMINATION. INDICATE THE REQUIRED EMERGENCY AND EXIT |
| LIGHTING ON THE LIGHTING PLAN. NEC 700.16 |
| |
| 4)NEC 422.60 |
| PROVIDE EQUIPMENT MANUFACTURER DOCUMENTATION FOR ALL |
| NEW EQUIPMENT INDICATING LISTING REQUIREMENTS AND |
| ELECTRICAL CHARACTERISTICS SUCH AS LOAD, VOLTAGE AND |
| FREQUENCY. NEC 422.60 |
| |
| 5) WPB AMENDMENTS TO THE FBC 107.3.2 |
| IDENTIFY ROOM DESIGNATIONS ON THE FLOOR PLAN AND |
| INDICATE THE LOCATIONS FOR THE ELECTRICAL SERVICE |
| ENTRANCE METER/MAINS EQUIPMENT AND PANELS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |